Power Monitoring and Distributed Control by Digital Relay (디지털 계전기를 이용한 전력감시 및 분산제어)

  • Lee, Sung-Hwan;Park, Sang-Bae;Ahn, Ihn-Seok
    • Journal of the Korean Society of Industry Convergence
    • /
    • v.4 no.3
    • /
    • pp.263-266
    • /
    • 2001
  • In this paper, intelligent methods using digital protection relay in power SCADA system is developed in order to protect power systems by means of timely fault detection during operation and control at starting for induction motor which have various load environments and capacities in power systems. The digital protective relay was designed with DSP CPU(TMS320C31) to protect and measure more quickly and precisely. The test result on the basis of KEMC 1120 and IEC60255, show that the operation time error of the digital motor protection relay is improved within ${\pm}5%$. Also, we can control motors at starting according to starting types with simple method as programmable sequence editor. So we can improve the demerits of high cost and much manhour for rework.

  • PDF

Adaptive undervoltage protection scheme for safety bus in nuclear power plants

  • Chang, Choong-koo
    • Nuclear Engineering and Technology
    • /
    • v.54 no.6
    • /
    • pp.2055-2061
    • /
    • 2022
  • In the event of a short-circuit accident on a 4.16 kV non-safety bus, the voltage is temporarily lowered as backflow occurs on the safety bus. In such cases, the undervoltage relay of the safety bus shall not pick up the undervoltage so as not to interfere with the operation of the safety motors. The aim of this study is to develop an adaptive undervoltage protection scheme for the 4.16 kV safety bus considering the faults on the 13.8 kV and 4.16 kV non-safety buses connected to secondary windings of the three winding transformers, UAT and SAT. The result of this study will be the adaptive undervoltage protection scheme for the safety bus of nuclear power plants satisfying functional requirements of the safety related medium voltage motors. The adaptive undervoltage protection scheme can be implemented into an integrated digital protective relay to make user friendly and reliable protection scheme.

A Study on the Digital Protective Relay for Generator Fault Protection (발전기 고장보호를 위한 디지털 계전기에 관한 연구)

  • Jang, Nak-Won;Park, Jeong-Do;Lee, Sung-Hwan
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.33 no.8
    • /
    • pp.1232-1238
    • /
    • 2009
  • As power facilities are getting higher at capacity, the monitoring and diagnosis of generators for fault detection and protection has attracted intensive interest. In case of an after-fault in high capacity rotating machines, the recovering cost is usually very expensive and additional time is necessary for returning in a normal situation. In this paper, we developed the protection program for the generator fault protection system and each module of the digital protective relay H/W for loading the protection program. The protective relay H/W was designed to have EMC characteristics for prohibiting from fault operation in bad power systems.

A Study of the Operating Characteristic for Voltage Restrained Overcurrent Relay using the ATPDraw5.7p4 Modeling Data (ATPDraw5.7p4 모델링 데이터를 이용한 전압억제 과전류계전기 동작특성에 관한 연구)

  • Park, Chul-Won;Ban, Yu-Hyeon
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.61 no.1
    • /
    • pp.23-28
    • /
    • 2012
  • The market of domestic Power Plant Generator Protection and Control System (GPCS) is narrow and required the high reliability, and technology. So, it is still operated as turn-key. In recent years, digital relays has evolved into IED can perform the control and monitoring functions without central monitoring based on IEC61850 international standards communications, and attention for advancement of smart grid and ECMS has been increased in South Korea. The increasing attention on multi-function IED, DGPS(digital generator protection system), for internal fault protection of large generator results in starting a national project in South Korea, the IED prototype development for next-generation power units. The voltage restrained overcurrent relay have been used as back-up overcurrent protection for generators. In this paper, voltage restrained overcurrent relay is one of the back-up protective factors in generator protection IED was presented. For evaluation performance of the voltage restrained overcurrent relay, the data of ATPDraw5.7p4 modeling was used.

The Study of Fast Frequency Measurement Technique for Protection Relay (계전기를 위한 고속의 주교수 계측 알고리즘)

  • Kim, Beung-Jin;Lee, Chang-Ho;Park, Jong-Chan
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.211-213
    • /
    • 2005
  • In this paper, the frequency compensator for digital protective relay is introduced. Due to sudden appearance of generation-load or fault in power system, the frequency can deviate from its nominal value. The Orthogonal filter adopted to digital protective relay is exposed to the problem. Therefore, the frequency variation makes a difficult to protective function and power measurement in digital protective relay. The essential property of the proposed algorithm presented is its outstanding immunity to both signal orthogonal component magnitudes and DFT filter gain variations which ensures below 0.05Hz accuracy of estimation. Additionally, the proposed method has excellent characteristics with low signal sampling rate. Based on the frequency estimation, author design under frequency protection relay for generator and verifies its performance with several experimental tests.

  • PDF

A Study on Design of Digital Protective Relay for Transformer Using a DSP (DSP를 이용한 변압기용 디지털 보호계전기 설계에 관한 연구)

  • 서희석;권기백
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.6
    • /
    • pp.39-46
    • /
    • 2003
  • In this papers, We studied system requirement specification, hardware design and implementation, protective algorithm and software design method to implement digital protective relay which has high trust and high function of protection as well as control and metering for power transformers. Protective relay for transformer is implemented on real time using DSP, which is the specific processor for digital signal processing, as a result, it is completed by the wide improvement of arithmetic capability of protective relay. Reliability is proved testing operating value and operating time, reset value and reset time of an relaying element using protective relay tester made in NF Corporation of Japan.

A Study on the Digital DC Protection Relay through with Field Adoption Test in the DC Distribution System (직류급전시스템 시험적용 사례를 통한 디지털 직류 보호계전기에 관한 연구)

  • Ko, In-Suk;Cha, Kwang-Seok;Min, Byung-Hoon
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.55 no.12
    • /
    • pp.646-652
    • /
    • 2006
  • This study identifies the comparison of Technical specification and Characteristics of DC Protection Relay(ETCPU200) used in DC Distribution System in Korea. ETCPU200 has completed Field Test and approved its capability by finding out causes of recent operations through lately developed digital DC protection relay in parallel operation at Maebong-Substation, Sangbong-Substation, Nakseongdae-Substation, Euljirosaga-Substation, Jegi-Substation and Chongyangri T/P area. It also examines additional features for efficient System Analysis and Operations.

Development of the digital protection relay for protecting distributed generation (분산전원 보호용 디지털 보호계전기 개발)

  • Cho, Chul-Hee;Lee, Byeong-Ho;Oh, Eui-Seok;Ko, Chul-Jin;Kang, Sang-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2005.07a
    • /
    • pp.181-183
    • /
    • 2005
  • The existing distribution networks are growing with an increase of power demand more and more. Therefore, for efficient operation of distribution networks, operators are much in need of distributed generation. This paper describes a development of the digital protection relay(HIMAP) for protecting distributed generation which is expected to play an increasing role in electric power systems in the near future. This paper particularly introduces frequency protective algorithm and reverse power protective algorithm among the relaying algorithms for protecting distributed generation in distribution networks and resents capability of a developed digital protection relay including these algorithms.

  • PDF

A Study on The Development and Function Test of Digital Transformer Protection Relay Using The Induced Voltage (유기전압비를 이용한 디지털형 변압기 보호계전기 개발 및 성능시험에 관한 연구)

  • Jung, Sung-Kyo;Lee, Jae-Kyung;Kim, Han-Do;Choi, Dae-Gil;Kang, Yong-Chul;Kang, Sang-Hee
    • Proceedings of the KIEE Conference
    • /
    • 2001.11b
    • /
    • pp.216-218
    • /
    • 2001
  • The transformer role is very important in power system operation and control; also its price is very expensive. Therefore many kinds of the efforts for transformer protection have been executed. So for as, current differential relay(87) has been mainly used for transformer protection. But current differential relaying method has several troubles as followings. Differential current can be occurred by transformers inrush current between winding1 and winding2 of transformer when transformer is initially energized. Also harmonic restrained element used in current differential relaying method is one of the causes of relays mal-operation because recently harmonics in power system gradually increase by power switching devices(SVC, FACTS, DSC, etc). Therefore many kinds of effort have been executed to solve the trouble of current differential relay and one of them is method using ratio of increment of flux linkages(RIFL) of the primary and secondary windings. This paper introduces a novel protective relay for power transformers using RIFL of the primary and secondary windings. Novel protective relay successfully discriminates between transformer internal faults and normal operation conditions including inrush and this paper includes real time test results using RTDS(Real Time Digital Simulator) for novel protective relay. A novel protective relay was designed using the TMS320C32 digital signal processor and consisted of DSP module. A/D converter module, DI/DO module, MMI interface module and LCD display module and developed by Xelpower co., Ltd.

  • PDF

A Study on the Digital DC Protection Relay through with Field Adoption Test in the DC Distribution System (직류급전시스템 시험적용 사례를 통한 디지털 직류 보호계전기에 관한 연구)

  • Cha, Kwang-Seok;Ko, In-Suk;An, Tae-Pung;Min, Byung-Hoon
    • Proceedings of the KSR Conference
    • /
    • 2006.11b
    • /
    • pp.606-615
    • /
    • 2006
  • This study identifies the comparison of Technical specification and Characteristics of DC Protection Relay(ETCPU200) used in DC Distribution System in Korea. ETCPU200 has completed Field Test and approved its capability by finding out causes of recent operations through lately developed digital DC protection relay in parallel operation at Maebong-Substation, Nakseongdae-Substation, Euljirosaga-Substation, Jegi-Substation and Chongryangri T/P area. It also examines additional features for efficient System Analysis and Operations.

  • PDF