HY 1600kV/70kA Impulse Voltage/Current Test Facility (한양대학교 1600kV/70kA 충격 전압/전류 시험설비 구축)

  • Chang, Yong-Moo;Kim, Cheol-Ho;Hwang, Ryul;Lee, Bang-Wook;Koo, Ja-Yoon
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.11a
    • /
    • pp.229-229
    • /
    • 2009
  • This Impulse Voltage and Current Test System is designed for performing of impulse voltage tests with Lightning impulse voltage 1.2/50(LI) up to 1520kV peak value and switching impulse voltages 250/2500(SI) up to 1120kV peak valu acc. to IEC 60060-1, and furthermore for impulse current test, e.g. testing of arrester sections($U_{res}$=95kV)with current impulses 4/10 and 8/20 up to 70kA peak value.

  • PDF

Lightning Impulse Breakdown Characteristic of Dry-Air/Silicone Rubber Hybrid Insulation in Rod-Plane Electrode

  • Kwon, Jung-Hun;Seo, Cheong-Won;Kim, Yu-Min;Lim, Kee-Joe
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.3
    • /
    • pp.1181-1187
    • /
    • 2015
  • Sulfur hexafluoride (SF6) gas is used widely in electric power equipment such as Gas Insulated Switchgear (GIS), Gas Insulation transmission Line (GIL), and Gas Circuit Breaker (GCB). But applications of SF6 should be restricted because SF6 gas is one of the greenhouse effect gases. To reduce use of SF6 gas, a study on eco-friendly alternative insulation medium is needed. In this paper, we investigated lightning impulse (LI) breakdown of dry-air which is attracting attention as an ecofriendly alternative gas and the LI breakdown of hybrid insulation combined with dry-air and solid insulation (Room-Temperature Vulcanizing Silicone Rubber-RTV SIR) and dry-air in inhomogeneous fields according to gap distance and pressure. The experiment results showed that the LI breakdown strength of hybrid insulation system was higher than that of dry-air insulation system. It was verified that the development of technology related to eco-friendly power apparatus compact such GIS, GCB and GIL can be used as basic research data.

Influence of SF6/N2 Gas Mixture Ratios on the Lightning Streamer Propagation Characteristics of 22 kV MV Circuit Breaker

  • Gandhi, R.;Chandrasekar, S.;Nagarajan, C.
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.4
    • /
    • pp.1663-1672
    • /
    • 2018
  • In recent times, gas insulated medium voltage (MV) circuit breakers (CB) form a vital component in power system network, considering its advantages such as reduced size and safety margins. Gas insulation characteristics of circuit breakers are generally measured by lightning impulse (LI) test according to IEC standard 60060-1 as a factory routine test. Considering the environmental issues of $SF_6$ gas, many research works are being carried out towards the mixture of $SF_6$ gases for high voltage insulation applications. However, few reports are only available regarding the LI withstand and streamer propagation characteristics (at both positive and negative polarity of waveform) of $SF_6/N_2$ gas mixture insulated medium voltage circuit breakers. In this paper, positive and negative polarity LI tests are carried out on 22 kV medium voltage circuit breaker filled with $SF_6/N_2$ gas mixture at different gas pressures (1-5 bar) and at different gas mixture ratios. Important LI parameters such as breakdown voltage, streamer velocity, time to breakdown and acceleration voltage are evaluated with IEC standard LI ($1.2/50{\mu}s$) waveform. Weibull distribution analysis of LI breakdown voltage data is carried out and 50% probability breakdown voltage, scale parameter and shape parameter are evaluated. Results illustrate that the $25%SF_6+75%N_2$ gas filled insulation considerably enhances the LI withstand and breakdown strength of MV circuit breakers. LI breakdown voltage of circuit breaker under negative polarity shows higher value when compared with positive polarity. Results show that maintaining the gas pressure at 0.3 MPa (3 bar) with 10% $SF_6$ gas mixed with 90% $N_2$ will give optimum lighting impulse withstand performance of 22 kV MV circuit breaker.

Development of National Lightning Impulse Voltage Standard Measuring Technology (뇌충격전압 국가표준 측정기술 개발)

  • Kim, M.K.;Jeong, J.Y.;Kim, I.S.
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1744-1746
    • /
    • 2003
  • This paper represents the development of national standard (NS) for lightning impulse (LI) voltage measuring system rated 400 kV. A traceability of the NS to the international standard could be achieved by the intercomparison test with Helsinki University. According to the IEC 60060-2, a measurement uncertainty was assessed. As a result of the tests, a measurement uncertainty and step response characteristics were satisfied with the requisite for NS.

  • PDF

Characteristics of lightning impulse breakdowns in inhomogeneous $SF_6$ gas gap (불평등전장에서 $SF_6$ 기체의 뇌임펄스 절연파괴특성)

  • Lee, B.H.;Choi, H.S.;Oh, S.K.;Li, F.
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1921-1923
    • /
    • 2004
  • V-p characteristics and the discharge luminous characteristics in inhomogeneous $SF_6$ gas gap under the positive and negative lightning impulse voltages are presented. The test gap was composed of the plane-to-plane with a needle-shaped protrusion. The applied voltage and the predischarge current were measured by the electric field sensor and the shunt of 50 ${\Omega}$, respectively. The light emission signals were observed by a photomultiplier tube, and a high-speed camera. In a consequence, the dielectric strengths of $SF_6$ gas gap under positive lightning impulse voltages were independent of the gas pressure. In the presence of the positive polarity, the branches of discharge channel were created and the directions of the discharge paths were random. On the other hands, the discharge paths of the negative polarity were more thicker and brighter.

  • PDF

Transient impedance characteristics according to the injection position of deep-driven ground rods (심매설 접지전극의 전류인가위치에 따른 과도접지임피던스 특성)

  • Lee, Bok-Hee;Li, Feng;Lee, Su-Bong;Lee, Song-Zhu;Jeon, Byung-Wook;Eom, Ju-Hong;Cho, Sung-Chul;Lee, Tae-Hyung
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.05a
    • /
    • pp.297-300
    • /
    • 2008
  • This paper presents the behaviors of transient and conventional grounding impedances of a deep-driven ground rods associated with the injection point of lightning impulse currents. The transient impedance of deep-driven ground rods under lightning impulse currents were higher than the static ground resistance. The transient grounding impedances strongly depend on the injection point and size of grounding electrodes and the rising time of impulse current. Reduction of ground system inductance is an important factor to lightning surge protection.

  • PDF

Dielectric Characteristics of SF6 and Dry-Air Gases under Lightning Impulse Voltage (뇌임펄스전압에 대한 SF6와 dry-air의 절연특성)

  • Li, Feng;Yoo, Yang-Woo;Kim, Dong-Kyu;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.8
    • /
    • pp.142-149
    • /
    • 2010
  • This paper describes dielectric characteristics of $SF_6$ and dry-air gases under lightning impulse voltages in a quasi-uniform electric field. In order to simulate to a quasi-uniform electric field, electric field utilization factor of the used sphere-plane electrode is 71[%]. The gas pressure of $SF_6$ ranges from 0.1 to 0.2[MPa] and that of dry-air ranges from 0.2 to 0.6[MPa]. Electrical breakdown voltages of $SF_6$ and dry-air gases are measured and analyzed as functions of the polarity of lightning impulse voltage and gas pressure. As a result, the electrical breakdown voltage of both gases under the positive lightning impulse voltage is higher than that under the negative one. The electrical breakdown voltage in $SF_6$ is almost higher than 2.67 times compared to dry-air. The results presented in this paper can be used as a useful information to evaluate the capability of alternative insulation gases for $SF_6$ in power distribution equipment with prominent ability against lightning surge.

Breakdown Characteristics of $SF_{6}/N_{2}$ Gas Mixtures According to a change in Temperature (온도변화에 따른 $SF_{6}/N_{2}$ 혼합가스의 절연특성)

  • Lee, Bok-Hee;Li, Feng;Choi, Jong-Hynk;Baek, Young-Hwan;Jeong, Dong-Chul;Kim, Seong-Weon
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.1455-1456
    • /
    • 2007
  • This paper presents the experimental results on impulse breakdown characteristics under a highly non-uniform electric field in $SF_{6}/N_{2}$ gas mixtures according to a change in temperature. Test temperature ranges from $-25^{\circ}C$ to $25^{\circ}C$. The impulse predischarge breakdown developments are investigated by the measurements of current pulse and discharge luminous events. As a result, the predischarge development mechanisms for both positive and negative polarities are same. When increasing the temperature, breakdown voltage due to lightning impulse voltage is increased in negative polarity. On the other hand, when increasing the temperature, breakdown voltage due to lightning impulse voltage is not changed in positive polarity.

  • PDF

Effects of the Injected Number and Amplitude of 8/20 [μs] Impulse Current on the Life of ZnO Varistors (8/20 [μs] 임펄스전류의 인가횟수와 크기가 ZnO바리스터의 수명에 미치는 영향)

  • Lee, Bok-Hee;Li, Feng
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.1
    • /
    • pp.118-124
    • /
    • 2007
  • This paper presents the effects of the injected number and amplitude of impulse current on the service life of ZnO varistors for low voltages. To analyze the effects of lightning impulse currents on the performance of ZnO varistors, the measurements of resistive leakage current and power dissipation at the power frequency ac voltage before and after the injections of the $8/20[{\mu}s]$ impulse currents were made. As a consequence, the duration and amplitude of resistive leakage current flowing through ZnO varistor were increased with increasing the number of injections of the $8/20[{\mu}s]$ impulse currents. It is desirable that the service life of ZnO varistors should be evaluated as a function of the number and amplitude of lightning impulse current.

Characteristics of leakage currents flowing through ZnO varistor exposed to surge currents (서지전류가 입사된 ZnO 바리스터에 흐르는 누설전류의 특성)

  • Lee, Bok-Hee;Li, Feng;Lee, Su-Bong
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2006.05a
    • /
    • pp.338-341
    • /
    • 2006
  • This paper presents the leakage current characteristics of ZnO varistors exposed to the $8/20{\mu}s$ lightning impulse currents as functions of the number of injection and amplitude of impulse currents. The surge simulator system ECAT that can generate $8/20{\mu}s$ impulse currents with a peak short-circuit of $5[kA_p]$ was used. Leakage currents flowing through ZnO varistors subjected to the $8/20{\mu}s$ impulse currents were measured under 60 Hz AC voltages. The trend curves of resistive leakage current of ZnO varistors were analytically calculated.

  • PDF