HY 1600kV/70kA Impulse Voltage/Current Test Facility

한양대학교 1600kV/70kA 충격 전압/전류 시험설비 구축

  • Chang, Yong-Moo (Applied Research Center for Electro-Fusion Technology, Hanyang University) ;
  • Kim, Cheol-Ho (Applied Research Center for Electro-Fusion Technology, Hanyang University) ;
  • Hwang, Ryul (Applied Research Center for Electro-Fusion Technology, Hanyang University) ;
  • Lee, Bang-Wook (Applied Research Center for Electro-Fusion Technology, Hanyang University) ;
  • Koo, Ja-Yoon (Applied Research Center for Electro-Fusion Technology, Hanyang University)
  • 장용무 (한양대학교 퓨전전기기술응용연구센터) ;
  • 김철호 (한양대학교 퓨전전기기술응용연구센터) ;
  • 황률 (한양대학교 퓨전전기기술응용연구센터) ;
  • 이방욱 (한양대학교 퓨전전기기술응용연구센터) ;
  • 구자윤 (한양대학교 퓨전전기기술응용연구센터)
  • Published : 2009.11.12

Abstract

This Impulse Voltage and Current Test System is designed for performing of impulse voltage tests with Lightning impulse voltage 1.2/50(LI) up to 1520kV peak value and switching impulse voltages 250/2500(SI) up to 1120kV peak valu acc. to IEC 60060-1, and furthermore for impulse current test, e.g. testing of arrester sections($U_{res}$=95kV)with current impulses 4/10 and 8/20 up to 70kA peak value.