• Title/Summary/Keyword: 단로기(DS)

Search Result 9, Processing Time 0.033 seconds

The signal analysis of PD in DS for GIS (GIS 단로기 내부의 부분방전 신호분석)

  • Kim, Jong-Seo;Kim, Jin-Tea;Cheon, Min-Ou;Park, No-Bong;Park, Yong-Pil
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.679-682
    • /
    • 2004
  • GIS equipment has problems on confidence according to long-time usage, development of diagnosis technique has been importantly recognized accordingly. Therefore. measurement and analysis of PD has been generally used much equipment of GIS. But, in case of measurement of PD at field, real trouble signals are difficult to classify noise. Accordingly, a variety of trouble conditions for DS were simulated, and detected signals were analyzed by the application of electrical and mechanical methods. For this analysis, detected signals were accumulated according to phase-magnitude with the application of Induction sensor, and then we analyzed the characteristics. For the simulation experiment, we made DS for 170kV GIS and analyzed the characteristics of detected signals with the application of neural network algorithm.

  • PDF

Analysis of trouble signal of inner DS for GIS (GIS 단로기 내부의 이상신호 분석)

  • Kim, Jong-Seo;Lee, Eun-Suk;Park,, Yong-Pil
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07b
    • /
    • pp.1207-1210
    • /
    • 2004
  • Recently, because GIS equipment has problems on confidence according to long-time usage, development of diagnosis technique has been importantly recognized. Therefore. measurement and analysis of PD has been generally used much equipment of GIS. But, in case of measurement of PD at field, real trouble signals are difficult to classify noise. Accordingly, a variety of trouble conditions for DS were simulated, and detected signals were analyzed by the application of electrical and mechanical methods. For this analysis, detected signals were accumulated according to phase-magnitude with the application of Induction sensor, and then we analyzed the characteristics. For the simulation experiment, we made DS for 170kV GIS and analyzed the characteristics of detected singals with the application of neural network algorithm

  • PDF

The signal interpretion of PD on DS for GIS (GIS 단로기의 부분방전 신호해석)

  • Kim, Jong-Seo;Park, Yong-Pil;Lee, Eun-Suk;Jeong, Seung-Cheon;Lim, Young-Bae
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.04a
    • /
    • pp.1-4
    • /
    • 2004
  • Recently, because GIS equipment has problems on confidence according to long-time usage, development of diagnosis technique has been importantly recognized. Therefore. measurement and analysis of PD has been generally used much equipment of GIS. But, in case of measurement of PD at field, real trouble signals are difficult to classify noise. Accordingly, a variety of trouble conditions for DS were simulated, and detected signals were analyzed by the application of electrical and mechanical methods. For this anslysis, detected signals were accumulated according to phase-magnitude with the application of Induction sensor, and then we analyzed the characteristics. For the simulation experiment, we made DS for 170kV GIS and analyzed the characteristics of detected singals with the application of neural network algorithm.

  • PDF

The diagnosis of internal trouble on DS for GIS using PD detection (부분방전 검출을 이용한 GIS 단로기 내부이상 진단)

  • Kim, Jong-Seo;Lee, Eun-Suk;Cheon, Jong-Cheol
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.11a
    • /
    • pp.575-578
    • /
    • 2003
  • Recently, because GIS equipment has problems on confidence according to long-time usage, development of diagnosis technique has been importantly recognized. Therefore. measurement and analysis of PD has been generally used much equipment of GIS. But, in case of measurement of PD at field, real trouble signals are difficult to classify noise. Accordingly, a variety of trouble conditions for DS were simulated, and detected signals were analyzed by the application of electrical and mechanical methods. For this analysis, detected signals were accumulated according to phase-magnitude with the application of Induction sensor, and then we analyzed the characteristics. For the simulation experiment, we made DS for 170kV GIS and analyzed the characteristics of detected singals with the application of neural network algorithm.

  • PDF

The Analysis of trouble signal on DS for GIS using Neural Network (신경회로망을 이용한 GIS용 단로기의 이상신호 패턴분석)

  • Kim, Jong-Seo;Park, Yong-Pil;Cheon, Jong-Cheol;Lee, Eun-Suk
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07b
    • /
    • pp.1196-1199
    • /
    • 2003
  • Recently, the development of diagnosis technique with high confidence is important on power equipment, for this reason is use for measurement and analysis of PD with prior appearance of insulation breakdown. In this paper, we presents the analysis of trouble signal to use ${\phi}-Q$ method which display 2D and 3D Equipment of simulation has made independently DS for 170kV GIS of one phase with same on field. The detected signal through the sensor of Induction and Acoustic Emission is classified to use characteristic neural network algorithm and then it is analysis.

  • PDF

The Analysis of trouble signal on DS for GIS using detection of PD (부분방전 검출을 이용한 GIS용 단로기의 이상신호 분석)

  • Kim, Jong-Seo;Lee, Eun-Suk;Cheon, Jong-Cheol;Park, Yong-Pil
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.05d
    • /
    • pp.29-32
    • /
    • 2003
  • Recently, the development of diagnosis technique with high confidence is important on power equipment, for this reason is to use for measurement and analysis of PD with prior appearance of insulation breakdown In this paper, we presents the analysis of trouble signal to use both method of general analysis of $\Phi$-Q-N in PD and statistical parameter by this interpretation Equipment of simulation has made independently DS for 170kV GIS of one phase with same on field. The detected signal through the sensor of Induction and Acoustic Emission is classified which used to characteristic neural network algorithm and then it is analysis.

  • PDF

Development of Evaluating Technology for the Capability of Carrying Short-Circuit Current at Electrical Contacts in EHV Disconnecting Switches (초고압 단로기 접점의 단락전류 통전성능 평가기술 개발)

  • Oh, Yeon-Ho;Song, Ki-Dong;Chong, Jin-Kyo
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.1
    • /
    • pp.46-51
    • /
    • 2008
  • Extra-high voltage(EHV) disconnecting switch(DS) consists of the electrical contacts and mechanical parts which actuate the contacts. When the short-circuit condition occurs, a large amount of current flows through the electrical contact in disconnecting switches and this causes considerable temperature rise due to Joule heating. If the temperature rise is higher than the melting point of contact material, the DS contact becomes melting and cannot be usable anymore. For this reason, the analysis for capability of carrying short-circuit current in DS contacts must be performed at a design stage. Here, we proposed a numerical technique for evaluating the capability of carrying short-circuit current at electrical contacts in EHV DS. In this numerical approach, the mechanical and thermal analyses were simulated to check the capability of carrying short-circuit current. First, the applied pressure at contact parts was analyzed considering the mechanical properties, and then contact resistance was calculated by an empirical equation. Finally, thermal analysis was performed with resistance variation at electrical contacts. To verify these numerical results, the distributions of temperature in DS were experimentally measured and compared with each other. The results from experiments were agreed well with those from the proposed numerical simulations.

Fatten Analysis of Trouble Signal on DS for GIS using Neural Network (신경회로망을 이용한 GIS용 단로기의 이상신호 패턴분석)

  • 김종서;이은석;천종철
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.16 no.12S
    • /
    • pp.1310-1315
    • /
    • 2003
  • GIS(Gas Insulated Switchgear) is power equipment with excellent dielectric strength and is economy merit in high confidence and stability. But, because of structural characteristics, this is difficult to monitor externally and provide much loss in the event of an accident. Recently, because equipment of GIS is occurring problem of confidence used for a long time, development of diagnosis technique have been importantly recognized. therefore, measurement and analysis of PD much has been generally used for equipment of GIS. But, in case of measurement of PD at field, real trouble signals is difficult to classify noise. Accordingly, a variety of trouble conditions for DS are simulated, and detected signals are analyzed by the application of electrical and mechanical methods. For this analysis, detected signals are accumulated according to phase-magnitude with the application of induction sensor, and then we analyzed the characteristics. For the simulation experiment, we make DS for 170KV GIS and analyze the characteristics of detected signals with the application of neural network algorithm. last, we have measured DS for GIS at field, and then have analyzed detected signals.

The Analysis of Patten on Trouble Signal defected in the DS of 170kv GIS (170kV GIS 단로기 이상신호 패턴분석)

  • Kim, Jong-Seo;Cheon, Jong-Cheol;Lee, Eun-Suk
    • Proceedings of the KIEE Conference
    • /
    • 2003.07c
    • /
    • pp.1759-1761
    • /
    • 2003
  • Recently, the development of diagnosis technique with high confidence is important on power equipment, for this reason is use for measurement and analysis of PD with prior appearance of insulation breakdown In this paper, we presents the analysis of trouble signal to use ${\Phi}$-Q method which display 2D and 3D Equipment of simulation has made independently DS for 170kV GIS of one phase with same on field. The detected signal through the sensor of Induction and Acoustic Emission is classified to use characteristic neural network algorithm and then it is analysis.

  • PDF