The Analysis of trouble signal on DS for GIS using Neural Network

신경회로망을 이용한 GIS용 단로기의 이상신호 패턴분석

  • Published : 2003.07.10

Abstract

Recently, the development of diagnosis technique with high confidence is important on power equipment, for this reason is use for measurement and analysis of PD with prior appearance of insulation breakdown. In this paper, we presents the analysis of trouble signal to use ${\phi}-Q$ method which display 2D and 3D Equipment of simulation has made independently DS for 170kV GIS of one phase with same on field. The detected signal through the sensor of Induction and Acoustic Emission is classified to use characteristic neural network algorithm and then it is analysis.

Keywords