The signal analysis of PD in DS for GIS

GIS 단로기 내부의 부분방전 신호분석

  • Published : 2004.11.11

Abstract

GIS equipment has problems on confidence according to long-time usage, development of diagnosis technique has been importantly recognized accordingly. Therefore. measurement and analysis of PD has been generally used much equipment of GIS. But, in case of measurement of PD at field, real trouble signals are difficult to classify noise. Accordingly, a variety of trouble conditions for DS were simulated, and detected signals were analyzed by the application of electrical and mechanical methods. For this analysis, detected signals were accumulated according to phase-magnitude with the application of Induction sensor, and then we analyzed the characteristics. For the simulation experiment, we made DS for 170kV GIS and analyzed the characteristics of detected signals with the application of neural network algorithm.

Keywords