Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference (한국전기전자재료학회:학술대회논문집)
- 2004.07b
- /
- Pages.1207-1210
- /
- 2004
Analysis of trouble signal of inner DS for GIS
GIS 단로기 내부의 이상신호 분석
- Published : 2004.07.05
Abstract
Recently, because GIS equipment has problems on confidence according to long-time usage, development of diagnosis technique has been importantly recognized. Therefore. measurement and analysis of PD has been generally used much equipment of GIS. But, in case of measurement of PD at field, real trouble signals are difficult to classify noise. Accordingly, a variety of trouble conditions for DS were simulated, and detected signals were analyzed by the application of electrical and mechanical methods. For this analysis, detected signals were accumulated according to phase-magnitude with the application of Induction sensor, and then we analyzed the characteristics. For the simulation experiment, we made DS for 170kV GIS and analyzed the characteristics of detected singals with the application of neural network algorithm