A Study on the Reliability Analysis for Smoke Detector using Dust (분진을 이용한 연기감지기 신뢰성 분석에 관한 연구)

  • Hong, Sung Ho;Choi, Moon Soo;Lee, Young Man
    • Journal of the Korean Society of Safety
    • /
    • v.28 no.6
    • /
    • pp.11-16
    • /
    • 2013
  • This paper presents a study on the analyzing reliability of smoke fire detector using accelerated life test. In general, the smoke fire detector is broken by dust which flow in smoke detection chamber. In order to conduct accelerated life test of smoke fire detector dust is set accelerated factor in this paper. The dust is fly-ash which is test particle 5th regulated by KS A 0090. The dust accelerated level is 60 g, 180 g and 360 g and failure time is measured by smoke sensitivity testing. It is considered to failure of detector if detector don't operate within 30 secconds when subjected to an air stream having a velocity of 20 cm/s~40 cm/s containing smoke with a concentration of 15% of rate of light-response of 1 m. The goodness of fit test and mean life prediction conduct using the failure time. The result show that life distribution fits the weibull distribution for failure time data and the mean lifes calculate 22.5 year in domestic product and 14.7 years in overseas product applied dust stress only.

A Study on the Need for Developing a Photoelectric Smoke Detector Detecting Smokes Emitted from Diverse Fire Sources (다양한 화원으로부터 발생된 연기를 감지하는 광전식연기감지기의 필요성에 대한연구)

  • Lee, Jong-Hwa
    • Journal of the Korea Safety Management & Science
    • /
    • v.18 no.1
    • /
    • pp.65-73
    • /
    • 2016
  • In this paper which was performed to bring public attention to the need for developing an photoelectric smoke detector that detects smokes emitted from diverse fire sources, it was confirmed that the photoelectric smoke detector may not respond to certain smoke types depending on the size and color of smoke particles. The test was performed on a photoelectric smoke detector which is being used generally for specific fire targets specified in UL268, including paper fire, wood fire and flammable liquid fire, while the actual response performance of the fire detector, as well as respective smoke particles collected from different fire source which were photographed with a SEM(Scanning electron microscope) were analyzed in the test for this study.

Analysis of the Response Time of a Photoelectric Spot-Type Smoke Detector Depending on the Type of Fires (화원에 따른 광전식 연기감지기 반응시간 분석)

  • Jee, Seung-Wook
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.5
    • /
    • pp.89-94
    • /
    • 2013
  • The fire testing performed for smoke detector model approval in Korea tests only one kind of fire smoke. A photoelectric spot-type smoke detector using Mie scattering is affected by the wavelength of light beam and the particle diameter. According to UL (Underwriters Laboratories Inc.) 268 standard, this paper analyze the characteristic of the response for a photoelectric spot-type smoke detector on sale in Korea using various fire smokes. Probability that the response time is included in non-defective range is 100% in paper fire, 90% in wood fire and 75% in flammable liquid fire, 90% in wood fire and 75% in flammable liquid fire. According to the estimation for population mean of the response time choosing a confidence level of 99%, a maximum of 19% for wood fire and that of 38% for flammable liquid fire are defective. As the result of analysis of smoke particle, this paper is found that these results are caused by the smoke particles are wide variations in size or have very black.

A Study on Response Characteristics of ionization Smoke Detector Influenced by Air Stream (이온화식 연기감지기의 기류응답특성 연구)

  • 이복영;정길순;이병곤
    • Fire Science and Engineering
    • /
    • v.17 no.2
    • /
    • pp.6-9
    • /
    • 2003
  • Recently, forced ventilating air conditioning system has been widely used in modern buildings. However, It is obvious that this kind of system may affect on the response of fire detectors at real fire incidents, especially, on the ionization smoke detector, which is critically influenced by air stream. Therefore we studied to verify the response characteristics of air stream by ionization smoke detector for the design of facilities in practice. In this study, experiments were executed to examine the correlation between air velocity and the ionization detector's responses with var-ious air velocity and smoke densities in the simulated test room. As a result of experiments, ionization detector's operating time is in reverse proportion to air velocity. And the detector shows more sensitive reaction when the velocity of smoke stream increase over 60 cm/s. In addition, it was shown that ionization smoke detector is more sensitive to smoldering fires in paper than that in petro-chemicals.

A Study on Fire Alarm Test of IoT Multi-Fire Detector combined Smoke/CO and Smoke/Temperature Sensors (연기/CO 및 연기/열 복합형 IoT 멀티 화재 감지기의 화재감지실험 연구)

  • Son, Geun­Sik;So, Soo­Hyun
    • Journal of the Society of Disaster Information
    • /
    • v.17 no.2
    • /
    • pp.236-244
    • /
    • 2021
  • Purpose: The purpose of this study is to develop IoT multi-fire detectors combined smoke/carbon monoxide/heat and wireless IoT communication and to confirm the detect performance by smoke generator fire test and cotton wicks fire test. Method: The IoT multi-fire detector combined smoke and CO and combined smoke and heat were experimented the detect performance by smoke generator test and fire test of cotton wicks. And the case of fire alarm was checked. Result: The IoT multi-fire detector combined smoke and CO rung the alarm at the fire test of cotton wicks, did not ring the alarm at the smoke generator test. In comparison, the IoT multi-fire detector combined smoke and heat did not ring the alarm both at the smoke generator test and the fire test of cotton wicks. Conclusion: The IoT multi-fire detector combined smoke and CO detected the only smoke including the carbon monoxide and the IoT multi-fire detector combined smoke and heat did not ring the alarm for lack of heat. As a result, when the developed IoT multi-fire detector was detected the signal more than the set point, the fire alarm was sounded through cotton wicks fire test and smoke generator.

A Study on the Performance Variation Depending on Using Period of Ionization Smoke Detector (이온화식연기감지기의 사용기간 경과에 따른 성능변화 연구)

  • Kim, Shi-Kuk;Baek, Won-Don;Ok, Kyung-Jea;Lee, Chun-Ha
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2008.04a
    • /
    • pp.175-179
    • /
    • 2008
  • This paper studied on the performance variation depending on using period of ionization smoke detector. In korea, there were a lot of loss of lives and property because of fire. In many cases, an alarm equipment didn't operate though it was set up, so it causes the failure of early evacuation and fire suppression. Accordingly, an experiment on the change of ionization smoke detector in capacity performed with ionization smoke detector which is set up with fire objects.

  • PDF

A Study on the Response Characteristics Depending on Service Life of Ionization Smoke Detector (이온화식연기감지기의 사용기간에 따른 응답특성 연구)

  • Baek, Won-Don;Kim, Shi-Kuk;Ok, Kyung-Jea;Lee, Chun-Ha;Jee, Seung-Wook
    • Fire Science and Engineering
    • /
    • v.22 no.4
    • /
    • pp.61-64
    • /
    • 2008
  • This paper studied on the response characteristics depending on service life of ionization smoke detector. The experimental samples used ionization smoke detectors (360 EA) for over 5 years which were influenced by environment set up with fire objects. The experimental method performed operate and non-operate test according to 'Type Approval and Technical Regulation of Detector (KOFEIS 0301)', for estimate the response characteristics of ionization smoke detector depending on service life. The results showed that their response characteristics were rapidly decreasing when the longer their using period. Accordingly, it is desirable that ionization smoke detector has to be changed for early fire detection when passed their service life.

A Study on the Response Characteristics of the Residential Smoke Detector Depending on Controlled Fire Tests (화재실험을 통한 주택용 연기감지기 응답특성에 관한 연구)

  • SaKong, Seong-Ho;Kim, Shi-Kuk;Lee, Chun-Ha;Jung, Jong-Jin
    • Fire Science and Engineering
    • /
    • v.23 no.4
    • /
    • pp.98-103
    • /
    • 2009
  • In this paper, in order to analyze the response characteristics of the smoke detectors which is suitable with the residential fire detector, the paper fire and flammable liquid fire experiment came to be accomplished according to UL Standard for safety for smoke detector for fire alarm signaling systems, UL 268. Also Photoelectric smoke detector, the Analog smoke detector and the single station alarm device came to be used with the specimen and the response characteristics of the smoke detectors which follows in these two types(paper, flammable liquid) test fire came to be analyzed. As a result, according to test fire there was some difference to response characteristics of the smoke detectors.

Revision of the Input Parameters for the Prediction Models of Smoke Detectors Based on the FDS (FDS 기반의 연기감지기 예측모델을 위한 입력인자 재검토)

  • Jang, Hyo-Yeon;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.31 no.2
    • /
    • pp.44-51
    • /
    • 2017
  • Accurate predictions of the activation time for smoke detectors using a fire simulation is are required to ensure the reliability of the RSET (Required Safe Egress Time) calculation in the process of PBD (Performance-Based Design). The objective of this study was to enhance the accuracy of input parameters for the numerical models of smoke detector based on the FDS. To this end, a Fire Detector Evaluator (FDE) developed in previous studies was improved. The uniformities of flow and smoke inside the FDE were improved and accurate measurements of the obscuration per meter (OPM) related to detector operation were also performed through a decrease in the forward scattering of smoke particles. The input parameters using the improved FDE showed a significant difference from the previous FDE quantitatively. In particular, a larger difference was found in a photoelectric detector compared to an ionization detector. Considering that the operating conditions of smoke detectors are affected by the detector type, combustibles, smoke particulars, and color, the database (DB) on the input parameters for various detectors and combustibles should be built to improve the reliability of PBD in future studies.

Development of the Low Power Stand-Alone Smoke and Heat Detector for the Reliability Improvement (신뢰성 개선을 위한 저전력 열연 복합식 단독경보형 감지기 개발)

  • Jee, Seung-Wook;Kim, Si-Kuk;Lee, Jae-Jin;Kim, Pil-Young;Lee, Chun-Ha
    • Fire Science and Engineering
    • /
    • v.26 no.1
    • /
    • pp.74-79
    • /
    • 2012
  • This study is described for development of the stand-alone smoke and heat detector (SASHD) according to the revised in 2011 type approval and performance inspection code for detector. The main improvement of the revised regulation is source. CMOS microcontroller with nano watt technology is use for development of the workable SASHD over 10 years. The low-power SASHD is developed by using the power-saving sleep mode of microcontroller, by making the low-power source voltage checker, heat detector and smoke detector. The stand-alone detector is developed by smoke and heat detector type for reduce false fire alarm. User can choose type of work between the heat detection mode and smoke & heat detection mode. The SASHD can communicate with each them using RS-485 communication supported from microcontroller. So, this study can develop the SASHD that is able to alarm more wide area when fire occurs and reduce a flash fire alarm.