A Study on the Response Characteristics Depending on Service Life of Ionization Smoke Detector

이온화식연기감지기의 사용기간에 따른 응답특성 연구

  • 백원돈 (호서대학교 소방방재학과) ;
  • 김시국 (호서대학교 소방방재학과) ;
  • 옥경재 (호서대학교 소방방재학과) ;
  • 이춘하 (호서대학교 소방방재학과) ;
  • 지승욱 (영남대학교 전기공학과)
  • Published : 2008.11.30

Abstract

This paper studied on the response characteristics depending on service life of ionization smoke detector. The experimental samples used ionization smoke detectors (360 EA) for over 5 years which were influenced by environment set up with fire objects. The experimental method performed operate and non-operate test according to 'Type Approval and Technical Regulation of Detector (KOFEIS 0301)', for estimate the response characteristics of ionization smoke detector depending on service life. The results showed that their response characteristics were rapidly decreasing when the longer their using period. Accordingly, it is desirable that ionization smoke detector has to be changed for early fire detection when passed their service life.

본 논문은 이온화식연기감지기의 사용기간에 따른 응답특성 연구로서 소방대상물에 설치되어 환경의 영향을 받은 5년 이상된 이온화식연기감지기 360개를 시료로 사용하였다. 사용기간에 따른 이온화식연기감지기의 응답특성을 평가하기 위한 실험방법은 '감지기의 형식승인 및 검정기술기준(KOFEIS 0301)'에서 정한 기준에 따라 작동 및 부작동 실험을 실시하였다. 실험결과 사용기간이 오래될수록 이온화식연기감지기의 응답특성이 현저하게 저하되는 것을 확인할 수 있었다. 따라서 일정기간이 경과된 이온화식연기감지기는 조기화재감지를 위해 교체되는 것이 바람직할 것으로 사료된다.

Keywords

References

  1. 내무부.한국소방검정공사, "자동화재탐지설비의 효율 화 방안 및 '97 확인시험결과", 연구논문.기술자료집, Vol. 1, No. 1, pp.3-21(1998)
  2. Robert M. Gagnon, Ronald H. Kirby, "A Designer's Guide to Fire Alarm Systems", NFPA, pp.213- 236(2003)
  3. Richard W. Bukowski, Wayne D. Moore, "Fire Alarm Signaling Systems", NFPA, pp.105-107(2003)
  4. 한국소방검정공사, "감지기의 형식승인 및 검정기술기 준(KOFEIS 0301)"(2006)
  5. 한국소방검정공사, "감지기의 형식승인 및 검정시험세 칙(KOFEIS 0301관련)"(2006)
  6. 이복영, 정길순, 이병곤, "이온화식연기감지기의 기류 응답특성 연구", 한국화재소방학회, Vol. 17, No. 2, pp.6-9(2003)
  7. 방재시험연구원, "화재감지기의 응답특성평가 연구" (2003)
  8. 이복영, 박상태, "감지기 경년변화 성능시험연구", 방 재기술 29호, pp.18-23(2000)