• 제목/요약/키워드: shorted-turn

검색결과 38건 처리시간 0.025초

터빈 발전기 회전자 권선의 층간단락 분석 (Analysis of Shorted Turns in Turbine Generator Rotor Windings)

  • 김희동;김병래;최형주
    • 전기학회논문지
    • /
    • 제60권8호
    • /
    • pp.1555-1559
    • /
    • 2011
  • Turbine generator(13.8 kV, 137.5 MW) has high bearing vibration at rotation speed. Shorted turns in generator rotor windings have strong correlation with increased field current which is thus related to increase in bearing vibration. The recurrent surge oscillograph (RSO) test is performed on the rotor winding in turbine generator to detect shorted turns. The result of the RSO test indicates that shorted turns of rotor winding are generated in two locations. The RSO test was capable of identifying the presence, number, and location of shorted turns in generator rotor windings.

발전기 운전중 회전자 계자권선의 단락 진단기법에 관한 연구 (Shorted-Turn Detction Techniques for Generator Rotor)

  • 이영준;김희동;빅종정;주영호;조지원;이병하
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 E
    • /
    • pp.1721-1724
    • /
    • 1998
  • A shorted-turn test was performed at the Pyungtaek combined cycle power plant on gas. turbine generator #4. The test was conducted using a permanent flux probe and digital oscilloscope. The flux probe installed in the generator air gap, senses the field winding slot leakage flux and produces a voltage proportional to the rate of change of the flux. This pattern of flux variation is a signature unique to each field winding. We have also applied a waveform analysis technique that can identify the pole location, slot number, and number of shorted-Turns with each slot.

  • PDF

발전기 회전자 턴 단락 현상에 따른 전자계 특성 해석 (Electromagnetic Characteristics Analysis of Generator with the shorted turn rotor field winding)

  • 조원영;김병국;조윤현;황돈하;강동식;김용주
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 추계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.35-37
    • /
    • 2005
  • Large generators are subject to high mechanical and electrical stress which may lead to deterioration of the insulation. The rotors, in particular, may develop short circuits particularly and there is a need for the operators to be aware of this situation. In this paper, the electromagnetic characteristics of the generator with shorted turns in rotor field winging is analyzed by FEM and the detection algorithm method of the shorted turn rotor slot position is proposed.

  • PDF

발전기 회전자의 층간단락 센서리스 진단기법 및 특성 해석 (Sensorless Diagnosis Method and Characteristic Analysis of Short-Circuited Turn for Generator Rotor)

  • 김선자;전윤석;이승학;최규하
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2003년도 추계학술대회 논문집
    • /
    • pp.210-213
    • /
    • 2003
  • Short-circuited can have significant effects on a generator and its performance. One of effective method detecting inter-turn short circuits on round rotor winding is a method using sensor detecting. But the method needs duplicate design of sensor for characteristic change according to types and forms of generator. Thus rotor shorted-turn diagnosis method without sensor is needed for detecting short turn when generator is driven. Diagnosis method without sensor depend on change of electric property in generator For the reason, this paper presents characteristic analysis of shorted-turns in generator by detecting the output voltage of generator.

  • PDF

Development of Inter-Turn Short Circuits Sensor for Field Winding of Synchronous Generator

  • Nam J-H;Jeon Y-S;Choe G-H;Lee S-H;Jeong S-Y;Yoo B-Y;Ju Y-H;Lee Y-J;Shin W-S
    • 전력전자학회:학술대회논문집
    • /
    • 전력전자학회 2001년도 Proceedings ICPE 01 2001 International Conference on Power Electronics
    • /
    • pp.56-59
    • /
    • 2001
  • An effective method of detecting inter-turn short circuits on round rotor windings is described. Shorted-turns can have significant effects on a generator and its performance. A method of detecting inter-turn short circuits on rotor windings is described. The approach used is to measure the rate of change of the air-gap flux density wave when the rotor is at operating speed and excitation is applied to the field winding. The inter-turn short circuits sensor for synchronous generator's field winding has been developed. The sensor, installed in the generator air-gap, senses the slot leakage flux of field winding and produces a voltage waveform proportional to the rate of change of the flux. For identification of reliability for sensor, a inter-turn short circuits test was performed at the West-Inchon combined cycle power plant on gas turbine generator and steam turbine generator. This sensor will be used as a detecting of shorted-turn for field winding of synchronous generator. The purpose of this paper is to describe the design and operation of a sensitive inter-turn short circuits detector. In this paper, development of inter-turn short circuits sensor for field winding of synchronous generator and application in a field.

  • PDF

MCSA를 이용한 BLDC 전동기의 고정자 권선 고장 진단 (Winding Fault Diagnosis for BLDC Motor using MCSA)

  • 이대성;양철오;김준영;김대홍;문용선;박규남;송명현
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2011년도 제42회 하계학술대회
    • /
    • pp.1876-1877
    • /
    • 2011
  • In this paper, a winding fault diagnosis method base on MCSA(Motor Current Signature Analysis) for BLDC motor is proposed. This method is programmed by LabVIEW for winding fault diagnosis. For winding fault diagnosis, two types of winding fault(shorted turn at one pole, shorted turn at two pole in same phase) are put intentionally in on phase. The motor current is collected by hole sensor, and transformed by the Park's transform, and then the Park's Vector Pattern are obtained, Usually this pattern is formed an ellipse, so a proper threshold value of distortion ratio(the ratio of the shortest axis and longest axis of ellipse) is suggested for winding faults diagnosis.

  • PDF

발전기 운전중 회전자 진단에 관한 연구 (On-Line Diagnosis Method for Generator Rotor Windings)

  • 이영준;공태식;김희동;주영호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2002년도 하계학술대회 논문집 C
    • /
    • pp.1846-1849
    • /
    • 2002
  • A shorted-turn test was performed at the Sininchon combined cycle power plant on gas turbine generators. The test was conducted using a permanent flux probe and on-line diagnosis system. The flux probe installed in the generator air gap senses the field winding slot leakage flux and produces a voltage proportional to the rate of change of the flux. This pattern of flux variation is a signature unique to each field winding. We have also applied a voltage waveform analysis technique that can identify the pole location, slot number and number of shorted-turn with each slot.

  • PDF

Simplified Impedance Modeling and Analysis for Inter-Turn Fault of IPM-type BLDC motor

  • Kim, Byeong-Woo;Kim, Kyung-Tae;Hur, Jin
    • Journal of Power Electronics
    • /
    • 제12권1호
    • /
    • pp.10-18
    • /
    • 2012
  • This paper proposes a finite element method (FEM)-based model of an interior permanent magnet (IPM)-type BLDC motor having stator inter-turn faults. We also propose impedance modeling of the magnetic characteristics. By integrating the developed model with a current-controlled voltage source inverter (CCVSI) model, the distributed characteristics of an inter-turn fault operated by a six-switch inverter are investigated considering speed control. Moreover, this paper presents the flux density distribution and torque characteristics for analyzing the inter-turn fault of an IPM-type BLDC motor. Additionally, fault impedance is required to calculate the circulating current that causes magnetic distortion. Thus, this paper proposes a method for estimating the circulating current taking into account the voltage at the shorted turn and the rotating speed. The analysis data were verified experimentally.

발전기 회전자의 층간단락 감지기 개발 (Development of Inter-Turn Short Circuits Sensor for Rotor Winding of Synchronous Generator)

  • 남종하;이승학;최규하
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제51권6호
    • /
    • pp.307-312
    • /
    • 2002
  • Inter-turn short circuits can have significant effects on a generator and its performance. The Inter-turn short circuits sensor for synchronous generator's field winding has been developed. The sensor, installed in the generator air-gap, senses the slot leakage flux of field winding and produces a voltage waveform proportional to the rate of change of the flux. For identification of reliability for sensor, a shorted- turn test was performed at the Seoinchon combined cycle power plant on gas turbine generator and stim turbine generator. This sensor will be used as a detecting of Inter-turn short circuits for synchronous generator's field winding.

평판형 전자기 엑츄에이터의 집중매개변수 모델링 및 해석 (Lumped Parameter Modelling and Analysis of Flat Coil Actuator with Shorted Turn)

  • 황기일;김진호;이정훈
    • 한국자기학회지
    • /
    • 제20권4호
    • /
    • pp.149-152
    • /
    • 2010
  • 평판형 전자기 엑츄에이터는 이동코일과 가이드 사이의 마찰이 없기 때문에 초정밀 제품에 널리 사용된다. 전자기 엑츄에이터의 성능 검증에 가장 많이 사용되는 방법 중 한 가지는 유한요소해석 방법이다. 하지만 유한요소해석 방법은 해석 시간이 많이든다는 단점이 있다. 유한요소해석 방법의 대안으로 계산시간은 짧지만 높은 정확도의 해석 결과를 도출해 낼 수 있는 집중매개 변수모델 해석방법이 많이 사용되고 있다. 본 논문에서는 평판형 전자기 엑츄에이터의 집중매개변수 모델링을 생성하고 시뮬레이션을 통해 성능을 검증하고 그 결과를 유한요소해석 결과와 비교해 본다.