Deterioration Characteristics of ZnO Surge Arrester Blocks for Power Distribution Systems Due to Impulse Currents (임펄스전류에 의한 배전용 ZnO 피뢰기 소자의 열화특성)

  • Lee, Bok-Hee;Cho, Sung-Chul;Yang, Soon-Man
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.3
    • /
    • pp.79-86
    • /
    • 2013
  • In order to analyze the electrical performance of ZnO surge arresters stressed by the combined DC and AC voltages that are generated in DC/AC converter systems, the leakage current properties of ZnO surge arrester blocks deteriorated by impulse currents were investigated. The test specimens were deteriorated by the 8/$20{\mu}s$ impulse current of 2.5kA and the leakage currents flowing into the deteriorated zinc oxide(ZnO) arrester blocks subjected to the combined DC and power frequency AC voltages are measured. As a result, the leakage currents flowing through deteriorated ZnO surge arrester blocks were higher than those flowing through the fine ZnO surge arrester blocks and the larger the injection number of 8/$20{\mu}s$ impulse current of 2.5kA is, the greater the leakage current is. The leakage current-voltage curves(I-V curves) of the fine and deteriorated ZnO surge arrester blocks stressed by the combined DC and AC voltages show significant difference in the low conduction region. Also the cross-over phenomenon is observed at the voltage close to the knee of conduction on plots of I-V curves.

Analysis of Transient Voltage by Lightning Stroke at 345kV Step-up Transformer (345kV 승압용 변전소의 뇌격에 의한 이상전압 해석)

  • Cho, Man-Young;Shin, Ho-Jeon;Huh, Jae-Sun;Kim, Jae-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.10
    • /
    • pp.95-101
    • /
    • 2012
  • Typically, large scale power generation facilities are linked to 345kV transmission line through a step-up transformer. If the value of transient voltage by generating lightning stroke is large more than electric equipment's BIL, devices insulation is destroyed. LA(Lighting Arrester) is used as a main means of prevention. However, the installation of LA takes the constraints of installation place and expensive installation costs. Therefore, we need to carefully study whether installation of installation can be omitted and the most efficient place of installation. In this paper, we simulated the transient voltage detected by lightning stroke at each equipments in the 345kV transmission power grid by using EMTP-RV program.

Insulation Characteristics of Dry-air Insulated Switchgear for 72.5 kV Wind Power Generation (72.5 kV 풍력 발전용 Dry-air Switchgear의 절연 특성)

  • Chan-Hee Yang;Jin-Seok Oh;Hee-Tae Park;Young-il Kim
    • Journal of Wind Energy
    • /
    • v.15 no.2
    • /
    • pp.5-9
    • /
    • 2024
  • This paper describes the insulation breakdown characteristics of 72.5 kV dry-air insulated switchgear under development for installation in a wind power generator when a lightning impulse voltage is applied. For this study, the weak point of insulation due to the electric field concentration of the switchgear's internal shape was identified by finite element method (FEM) analysis, and the shape was actually simulated to measure and analyze the polarity of the lightning impulse voltage and the insulation breakdown characteristics according to the gas pressure at dry-air pressures of 0.1 Mpa to 0.45 Mpa. This study derives the maximum electric field with a 50 % discharge probability for each switchgear internal insulation vulnerable point based on the actual test and electrical simulation, which will be useful as reference data for supplementing and changing insulation design in the future.

Soil Ionization Phenomena around a Hemispherical Electrode Stressed by Impulse Voltages (임펄스전압에 의한 반구형 전극계에서 토양의 이온화 현상)

  • Heo, Dae-min;Kim, Hoe-gu;Lee, Bok-hee
    • KEPCO Journal on Electric Power and Energy
    • /
    • v.2 no.4
    • /
    • pp.601-608
    • /
    • 2016
  • The electrical characteristics of the soil where a ground electrode is buried vary with regions, seasons and environmental factors. Electrical discharge in the vicinity of the ground electrode will occur differently and significantly affect the performance of the grounding system. It is necessary to analyze discharge and ionization characteristics of soils when the grounding system is designed. The aims of this investigation are to understand correlation between the soil ionization and the transient ground impedance. This paper presents the experimental results on the soil ionization parameters and the transient ground resistance due to the soil ionization around a hemispherical ground electrode stressed by lightning impulse voltages.

Acoustic Emission Monitoring of Lightning-Damaged CFRP Laminates during Compression-after-Impact Test

  • Shin, Jae-Ha;Kwon, Oh-Yang
    • Journal of the Korean Society for Nondestructive Testing
    • /
    • v.32 no.3
    • /
    • pp.269-275
    • /
    • 2012
  • Carbon-fiber reinforced plastic(CFRP) laminates made of nano-particle-coated carbon fibers and damaged by a simulated lightning strike were tested under compression-after-impact(CAI) mode, during which the damage progress due to compressive loading has been monitored by acoustic emission(AE). The impact damage was induced not by mechanical loading but by a simulated lightning strike. Conductive nano-particles were coated directly on the fibers, from which CFRP coupons were made. The coupon were subjected to the strikes with a high voltage/current impulse of 10~40 kA within a few ${\mu}s$. The effects of nano-particle coating and the degree of damage induced by the simulated lightning strikes on AE activities were examined, and the relationship between the compressive residual strength and AE behavior has been evaluated in terms of AE event counts and the onset of AE activity with the compressive loading. The degree of impact damage was also measured in terms of damage area by using ultrasonic C-scan images. The assessment during the CAI tests of damaged CFRP showed that AE monitoring appeared to be useful to differentiate the degree of damage hence the mechanical integrity of composite structures damaged by lightning strikes.

Effects of the Injected Number and Amplitude of 8/20 [μs] Impulse Current on the Life of ZnO Varistors (8/20 [μs] 임펄스전류의 인가횟수와 크기가 ZnO바리스터의 수명에 미치는 영향)

  • Lee, Bok-Hee;Li, Feng
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.1
    • /
    • pp.118-124
    • /
    • 2007
  • This paper presents the effects of the injected number and amplitude of impulse current on the service life of ZnO varistors for low voltages. To analyze the effects of lightning impulse currents on the performance of ZnO varistors, the measurements of resistive leakage current and power dissipation at the power frequency ac voltage before and after the injections of the $8/20[{\mu}s]$ impulse currents were made. As a consequence, the duration and amplitude of resistive leakage current flowing through ZnO varistor were increased with increasing the number of injections of the $8/20[{\mu}s]$ impulse currents. It is desirable that the service life of ZnO varistors should be evaluated as a function of the number and amplitude of lightning impulse current.

Breakdown Voltage and PD Characteristics of $SF_6/CF_4$ Mixtures in Nonuniform Field (불평등 전계에서 $SF_6/CF_4$ 혼합가스의 절연내력과 PD특성)

  • Hwang, Cheong-Ho;Sung, Heo-Gyung;Huh, Chang-Su
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.57 no.4
    • /
    • pp.635-640
    • /
    • 2008
  • New gas mixtures are now finding applications such as interrupting media for high-voltage circuit breakers. These mixtures consist of a high content of carbon tetrafluoride($CF_4$) added to sulfur hexafluoride($SF_6$). Nowdays $SF_6$ has been established for the use in gas insulated substations due to its high insulation withstand level and good arc quenching capability. At this paper Breakdown characteristics were investigated for $SF_6/CF_4$ mixtures when AC voltage and standard lightning impulse voltage(LI) was applied in a needle-plane electrodes. And partial discharge(PD) experiments were carried out in the test chamber which was made in needle-plane electrode. And ${\Phi}$-Q-N distribution of partial discharge signals was analyzed. The total pressure of the $SF_6/CF_4$ mixtures was varied within the range of 0.1-0.5 Mpa in the test chamber. The breakdown voltage in needle-plane electrode displayed N shape characteristics for increasing the content of $SF_6$ at positive impulse voltage and the PD inception voltage was increased slightly when pressure of $SF_6/CF_4$ Mixtures was increased. Maximum PD inception voltage is showed in 80% SF6/20%$CF_4$.

Failure Rate Estimation of MOV for Condition Monitoring of Surge Protective Devices (서지보호기의 상태 감시를 위한 MOV의 고장률 예측)

  • Kim, Dong Jin;Kim, Young Sun;Park, Jae Jun;Lee, Ki Sik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.9
    • /
    • pp.1302-1307
    • /
    • 2013
  • MOV(Metal Oxide Varistor) is the most important part of SPD(Surge Protective Device) which can protect electric facilities from an impulse current such as a lightning. So far, the fault of MOVs have decided only by surge count without considering magnitude of surge current and an amount of input energy. This paper proposed the fault prediction algorithm for the MOV using look up table made by surge count and input current data which have non-linear characteristics for input current and are estimated by high voltage experimental results. Proposed algorithm was proved by experiment on verification at a high voltage laboratory.

Breakdown Characteristics of Soils Caused by Impulse Currents (임펄스전류에 의한 토양의 절연파괴특성)

  • Lee, Bok-Hee;Lee, Kang-Soo;Kim, Hoe-Gu
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.4
    • /
    • pp.103-109
    • /
    • 2010
  • In this paper, breakdown characteristics of soil in a coaxial cylindrical electrode system stressed by impulse currents were experimentally investigated. The breakdown voltage and current waveforms for 4 types of soils were measured, and the threshold electric field intensity, the time-lag to breakdown and the voltage-current (V-I) curves were analyzed and discussed. As a result, the breakdown voltage and current waveforms are strongly dependent on the grain size of soil, and the voltage and current waveforms for gravel and sand differ from those for silt and loess. The threshold electric field intensity Ec is increased in the order of gravel, sand, loess and silt. The V-I curves for all test samples show a 'cross-closed loop' of ${\infty}$-shape. Also, the time-lag to breakdown for gravel and sand are longer than those for silt and loess. It is expected that the results presented in this paper will provide useful information on the design of improving transient performance of a grounding electrode system subjected to lightning current considering the soil ionization.

The Study on the Impulse Characteristic of Secondary Arresters in Power Distribution System (가공 배전선로 중성선과 가공지선 겸용시의 임펄스 특성 연구)

  • Kang, Moon-Ho;Kim, Dong-Myeong;Song, Il-Keun;Chun, Sung-Nam
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.297-299
    • /
    • 2004
  • In multi-ground distribution system, overhead ground wire and neutral wire are parallel connected to offer the electrical power energy and protect damage of lightning strokes. Therefore a case where the two wires become single wire, the power company can get the benefit such as installation cost saving and line fault protection by simplify of distribution line. In this paper we describe the result of impulse test in both system ; one is the present power system the other is unified power system parallel connected overhead ground wire and neutral wire. As a result of this impulse test, the present power system get lower impulse voltage than the unified power system.

  • PDF