Abstract

This paper describes the insulation breakdown characteristics of 72.5 kV dry-air insulated switchgear under development for installation in a wind power generator when a lightning impulse voltage is applied. For this study, the weak point of insulation due to the electric field concentration of the switchgear's internal shape was identified by finite element method (FEM) analysis, and the shape was actually simulated to measure and analyze the polarity of the lightning impulse voltage and the insulation breakdown characteristics according to the gas pressure at dry-air pressures of 0.1 Mpa to 0.45 Mpa. This study derives the maximum electric field with a 50 % discharge probability for each switchgear internal insulation vulnerable point based on the actual test and electrical simulation, which will be useful as reference data for supplementing and changing insulation design in the future.

Keywords

Acknowledgement

이 논문은 2022년도 정부(산업통상자원부)의 재원으로 한국에너지기술평가원의 지원을 받아 수행된 연구임(과제번호 : 20221A1010001C, 과제명 : (세부3)해상풍력 연계 66kV급 핵심기기 및 진단기술 개발)

References

  1. Nam, S. H. and Gang, H. G., 2010, "A study on the analysis of insulation strength characteristics of Dry-air by presssure for the development of environment-freindly high-pressure distribution board", KIEE(The Transactions of the Korean Institute of Electrical Engineers) Vol. 60, No.8, pp.1560 ~ 1565, 2011.
  2. Lee, B., Yoo, Y. Y., Kim, D. G. and Lee, В. H., 2010, "Insulation characteristics of SF6 and Dry-air for Lightning Impulse voltage". JIEIE(Jounal of the Korean Institute of Illuminating and Electrical Installation Engineers) Vol. 24, No.8, pp.142 ~ 149, 2010.
  3. Bang, S. M., Lee, 0. Y., Kim, J. I., Gang, J. 0., Lee, H. S., Go, T. G. and Gang, H. G., 2010, "Insulation characteristics of GN2 for eco-friendly high voltage power equipment Development", KIEE(The Transactions of the Korean Institute of Electrical Engineers) Vol. 63P, No. 4, pp. 356 ~ 360, 2014.
  4. H. Saitoh, K. Morita, T. Kikkawa, N. Hayakawa and H.Okubo, 2002. 8 "Impulse partial Discharge and Breakdown Characteristics of Rod-Plane Gaps in N2-SF6 Gas Mixtures", IEEE Trans, on DEI, Vol.9, No.4, pp.544~550.
  5. EC, 2021, "High-voltage switchgear and controlgear Part 1 : Common specifications for alternating current switchgear and controlgear, IEC 62271-1 Standard, 2.1 Edition, International Electrotechnical Commission.
  6. IEC, 2010, "High-voltage test techniques Part 1 : General definitions and test requirements, IEC 60060-1 Standard, 3.0 Edition, International Electrotechnical Commission.
  7. Goverment of the Republic of Korea, 2020, "South Korea's 2050 Carbon Neutral strategy".