• Title/Summary/Keyword: illuminating equipment

Search Result 240, Processing Time 0.022 seconds

Fault Current Calculation and Coordination by IEC Standards (IEC 표준에 의한 고장전류 계산과 보호협조)

  • Son, Seok-Geum
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.12
    • /
    • pp.6-12
    • /
    • 2014
  • The safety and reliability of the power system short-circuit current, the short-circuit current depends on the failure to obtain the objective is to quickly eliminate the breaking capacity of the circuit-breaker selection of the cable, the insulation of electrical equipment and protective relay an important factor in determining the level correction and protective relay selection scheme to be meaningful. Standards used in the domestic circuit breaker is applied to the production of IEC standard, but the American National Standards (ANSI / IEEE) by NEMA specification of the fault current calculations and the application of the asymmetric coefficient Korea. Therefore, in this paper, the IEC 60909 standard IEC breaker fault current calculation method and the method for selection of system configurations reviewed and protection system for reviewing the configuration of various protective relays appropriate correction and the correction value is main protection, back-up protection the equipment so that the period of protection relay coordination to minimize accidents and accident protection to minimize interruptions proposed for cooperation.

A Development and Performance Assessment of On-Line Monitoring System for Optical Fiber Composite Underground Distribution Network using DTS (DTS를 활용한 광복합 지중 배전계통 실시간 감시시스템 개발 및 성능평가)

  • Cho, Jin-Tae;Kim, Ju-Yong;Lee, Hak-Ju;Cho, Hwi-Chang;Choi, Myeong-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.6
    • /
    • pp.115-121
    • /
    • 2011
  • Intelligent distribution equipment is inevitable to realize self-healing which is one of smart grid functions in distribution network. Therefore, most of distribution equipment have been developed with self diagnostic sensors. However, it is not effective to construct on-line monitoring system for underground distribution cable because of high cost and low sensitivity. Recently, optical fiber composite cable is being considered for communication and power delivery in order to cope with increasing communication in distribution network. This paper presents the design and performance assessment results of underground cable on-line monitoring system using DTS(Distributed Temperature Sensing) and optical fiber composite underground cable.

Review of Insulation Performance in Synthetic Air and Dry Air for High Voltage Equipment in Distribution Class (배전급 전력설비를 위한 친환경 가스의 절연성능검토)

  • Lim, Dong-Young;Choi, Eun-Hyeok;Choi, Byoung-Ju;Choi, Sang-Tae;Lee, Kwang-Sik;Bae, Sungwoo
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.29 no.12
    • /
    • pp.33-39
    • /
    • 2015
  • This paper examines the insulation performance of synthetic air and dry air. This examination was conducted based on dielectric strength in uniform and non-uniform field, electric field distribution by interior structure and defects in gas insulation switchgear (GIS) and insulation performance in different temperatures. From this review, it was found that eco-insulation gas required to possess low moisture content for power equipment in the distribution class. The results of this paper are valuable to ensure the insulation design and insulation reliability of GIS using air.

A Selection of Optimal Weighting matrix for Model Following Multivariable Control System to Boiler-Turbine Equipment Using GA (GA를 이용한 보일러-터빈 설비의 모델 추종형 다변수 제어 시스템 설계를 위한 취적 가중치 행렬의 선정)

  • ;黃現俊
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.13 no.2
    • /
    • pp.234-234
    • /
    • 1999
  • The aim of this paper is to suggest a design method of the optimal model following control system using genetic algorithm (GA). This control system is designed by applying GA with reference model to the optimal determination of weighting matrices Q, R that are given by LQ regulator problem. The method to do this is that all the diagonal elements of weighting matrices are optimized simultaneously by GA, in the search domain selected adequately. And we design the model following control system to boi1er-turbine equipment by the proposed method. The model following control system designed by this method has the better command tracking performance than that of the control system designed by the trial-and-error method. The effectiveness of this control system is verified by computer simulation.

A Neuro Fuzzy Controller Using Auto-tuning Width of Membership Function for Equipment Systems (설비시스템을 위한 소속함수 폭의 자동동조를 사용한 뉴로퍼지 제어기)

  • 이수흠;방근태
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.11 no.2
    • /
    • pp.102-109
    • /
    • 1997
  • The width of fuzzy membership function and control rule has an effect on performance of the fuzzy controller for electric equipment systems. In this paper, the neuro-fuzzy controller is proposed to im¬prove the performance of fuzzy controller. It has the width of membership function, that is adapted to the electrical parameter using multi-layer neural network, it is applied to first order electric power system with dead time and various plant constant. The related simulation resolts show that the pro¬posed neuro fuzzy controller are superior characteristics of improved performance

  • PDF

A Study on the Design Standard of Substation Facility Density and Demand Factor in Office Buildings (사무소용건물의 변전시설밀도 및 수용률 기준설정에 관한 연구)

  • 김세동;정동효
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.6 no.6
    • /
    • pp.42-48
    • /
    • 1992
  • This paper shows a reasonable design standard of substation facility density and demand factor in office buildings, that was made by the systematic and statistical way considering actual conditions, such as investigated electric equipment capacity, electric power consumption, etc for 121 buildings. The saving of electric equipment investment, the decrease of power loss, the improvement of facilities utilization and the decrease of electric power rates an be contributed by the application of the design standard must be applied by the revision of current regulations and laws.

  • PDF

Development of the Digital Dimmer System (디지털 디머 시스템 개발 연구)

  • Jung, Seung-Hwan;Choy, Ick;Choi, Ju-Yeop
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.5
    • /
    • pp.108-115
    • /
    • 2008
  • Recently, a demand of the digital dimmer system is increasing steadily, but domestic research is not sufficient to the expectation. In this paper, a digital dimmer equipment is developed and resented to compose a system. Digital dimmer system compose console and dimmer rack. Console controls of user interface and a total system, and dimmer rack controls brightness of lighting equipment by a way of phase angle control with each illumination level to get from console.

The Study of the Circulation Current Control Scheme on Single Phase Inverter System (단상 인버터 시스템에서 순환 전류 제어 기법에 관한 연구)

  • Lee, Woo-Cheol
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.2
    • /
    • pp.60-69
    • /
    • 2014
  • This paper proposed the circulation current control scheme in the single phase inverter system. The load experiment of the power conversion system including the UPS usually uses the passive components such as resistors and inductors. Therefore, the energy consumption is serious problem. In addition, the system is out of order when it is installed in the local area, and the load experiment can not perform adequately after troubleshooting, because there is no the load equipment, and the power capacity is not enough in the local area. The paper does the research on the circulation current control scheme, it does not need the load equipment, and the load current can reuse as the input current of the equipment. Instead of the conventional method the voltage-voltage and voltage-current control scheme introduced the parallel converter concept is newly proposed, and the validity of the proposed control scheme is investigated by both simulation and experimental results.

Development of UV-IR Camera using IR Module and Improved UV Filter Transmittance (투과율 향상 UV 필터와 IR 모듈을 이용한 자외선-적외선(UV-IR) 카메라 개발)

  • Kim, Young-Seok;Shong, Kil-Mok;Bang, Sun-Bae;Kim, Chong-Min;Choi, Myeong-Il;Kim, Woo-Jin
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.12
    • /
    • pp.37-43
    • /
    • 2012
  • UV-IR diagnostic technology is being used for predictive maintenance of high voltage equipment together with IR-thermography and ultrasonic devices. In this paper, the UV-IR camera design, fabrication, and perform a simple test to be take advantage of the diagnostic equipment. UV-IR camera developed a $6.4^{\circ}{\times}4.8^{\circ}$ of the field of view as a conventional camera to diagnose a wide range of slightly enlarged, and power equipment to measure the distance between the camera and the distance meter has been attached. In a distance of 5m with the UV-IR it is possible to detect partial discharge with a PD level of 2.5 pC and a RIV(Radio Influence Voltage) level of $3.6dB{\mu}V$.

Research for Implementation of Real-time Power Measurement and Storage System (소규모 전력시스템를 위한 실시간 전원 계측 및 저장 시스템 구현에 관한 연구)

  • Seo, Jong-Wan;Suh, Hee-Seok;Shin, Myong-Chul
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.7
    • /
    • pp.29-36
    • /
    • 2007
  • According to the using of electric power source such as solar cell, fuel cell and wind energy, consumer is supplied from distributed generator and electric power company. Therefore, it is required that the real-time measurement and control instrument for those distributed generator. In this paper, describes the development of measuring equipment for the power system with distributed generator. The equipment has real-time measure function and communication with PC via USB port, which is used for various purposes such as investigation of transient state, and is compared with measurement instrument to verify the reliability.