DOI QR코드

DOI QR Code

The Study of the Circulation Current Control Scheme on Single Phase Inverter System

단상 인버터 시스템에서 순환 전류 제어 기법에 관한 연구

  • Lee, Woo-Cheol (Hankyong National University Dept. of Electrical Electronic & Control Engineering, Institute for information technology convergence)
  • 이우철 (한경대학교 전기전자제어공학과 IT융합기술연구소)
  • Received : 2013.11.11
  • Accepted : 2013.12.03
  • Published : 2014.02.28

Abstract

This paper proposed the circulation current control scheme in the single phase inverter system. The load experiment of the power conversion system including the UPS usually uses the passive components such as resistors and inductors. Therefore, the energy consumption is serious problem. In addition, the system is out of order when it is installed in the local area, and the load experiment can not perform adequately after troubleshooting, because there is no the load equipment, and the power capacity is not enough in the local area. The paper does the research on the circulation current control scheme, it does not need the load equipment, and the load current can reuse as the input current of the equipment. Instead of the conventional method the voltage-voltage and voltage-current control scheme introduced the parallel converter concept is newly proposed, and the validity of the proposed control scheme is investigated by both simulation and experimental results.

Keywords

References

  1. Jiann-Fuh Chen, Ching-Lung Chu, Tsu-Hua Ai, Ching-Lien Huang, "The burn-in test of three-phase ups by energy feedback method", Power Electronics Specialists Conference, pp. 766-771, 1993.
  2. Suresh Gupta, Vidya Rangaswamy, "Load bank elimination for ups testing", Industry Applications Society Annual Meeting, vol. 2, pp. 1040-1043, 1990.
  3. Chu, C.L, Chen, J.F , "Self-load bank for UPS testing by circulating current method", Electric Power Applications, IEE Proceedings, vol. 141, pp. 191-196, 1994. https://doi.org/10.1049/ip-epa:19941208
  4. Bekiarov. S.B., Nasiri. A., Emadi. A., "A New Reduced Parts On-Line Single-Phase UPS System", Industrial Electronics Society, IECON '03. The 29th Annual Conference of the IEEE, vol. 1, pp. 688-693, 2003.
  5. H. S. Kim, J.H. Han, J.H. Song, "Parallel Operation of Three-Phase Four wire UPS using Droop Control", Journal of the Korean Institute of Illuminating and Electrical Installation Engineers, Vol. 27, No. 4, pp. 88-95, Apr. 2013. https://doi.org/10.5207/JIEIE.2013.27.4.088
  6. W. C. Lee, D. S. Yoo, "Study on DC Charging Algorithm of the Line‐Interactive UPS with Dual Converter Structure", Journal of the Korean Institute of Illuminating and Electrical Installation Engineers, Vol. 19, No. 3, pp. 27-34 May, 2005. https://doi.org/10.5207/JIEIE.2005.19.3.027
  7. W. C. Lee, T. K. Lee, "A Design of a High Performance UPS with Capacitor Current Feedback for Nonlinear Loads", Journal of the Korean Institute of Illuminating and Electrical Installation Engineers, Vol. 26, No. 5, pp. 71-78 May, 2012. https://doi.org/10.5207/JIEIE.2012.26.5.071
  8. H. Cha, S. Lee, T. Vu "A new fast peak detector for single or three-phase unsymmetrical voltage sags", Energy Conversion Congress and Exposition (ECCE), 12-16 Sept. 2010, pp.434 - 440.