• Title/Summary/Keyword: high-tc superconducting fault current limiter(SFCL)

Search Result 54, Processing Time 0.032 seconds

Electromagnetic Behavior of High-Tc Superconducting Fault Current Limiters under the Quench State (켄치 상태에서 고온 초전도 한류기의 전자기적 거동)

  • Hyo-Sang Choi
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.1
    • /
    • pp.38-42
    • /
    • 2004
  • In this paper we analyzed the electromagnetic behavior of a superconducting fault current limiter (SFCL) under the quench state using FEM. The analysis model used in this work is 5.5 KVA meander-line type SFCLs which are currently developed by Superconductor Power System Lab in Korea Electric Power Research Institute. Meshes of 3,650 triangular elements were used in the analysis of this SFCL. Analysis results showed that the distribution of current density was concentrated to inner curved line in meander-line type SFCL and the maximum current density was 14.61 A/$m^2$ and also the maximum Joule heat was 2,030 W/$m^2$ in this region. We think that the new and the modified structure must be considered for an uniform distribution of the electromagnetic field.

Operation Algorithm and Drive Circuit in Power converter of DC reactor type fault Current Limiter (DC Reactor-Type 한류용 전력변환기의 제어 알고리즘 및 전력 소자 구동 회로)

  • 이승제;서호준;이찬주;고태국
    • Proceedings of the Korea Institute of Applied Superconductivity and Cryogenics Conference
    • /
    • 2002.02a
    • /
    • pp.334-336
    • /
    • 2002
  • This study is concerned with the operation algorithm and power switch drive circuit for DC Reactor Type High-Tc Superconducting Fault Current Limiter (SFCL). In the case of SFCL, Power switching operation algorithm are very important problem. So, this driving will determine the performance of SFCL. In this paper, we provide a simple algorithm and easy drive circuit. Through experiment we found that ideal is right.

  • PDF

Improvement of Current Limiting and Recovery Characteristics in Series Connection Type SFCL with Added Third Winding (3차권선이 추가된 직렬연결형 초전도한류기의 전류제한 및 회복 특성 향상)

  • Ko, Seok-Cheol;Han, Tae-Hee;Lim, Sung-Hun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.28 no.8
    • /
    • pp.62-68
    • /
    • 2014
  • The series connection type superconducting fault current limiter (SFCL) with added third winding, which was magnetically coupled in one iron core, was proposed. The proposed SFCL was expected to be more improved by just adding third winding into the conventional series connection type SFCL with two coils. To analyze the contribution of the third winding for the current limiting and the recovery characteristics of the SFCL, the short-circuit tests for the series connection type SFCL with the added third winding were performed together with the analysis on its electrical equivalent circuit. From the comparative analysis on the amplitude of the limited fault current and the power burden of the high-TC superconducting (HTSC) element comprising this SFCL, the improved current limiting and recovery characteristics of the series connection type SFCL using the third winding could be confirmed.

Analysis for Magnetic field generated in the Flux-Lock Type Reactor using HTSC during a fault time (고온초전도체를 이용한 자속구속 리액터의 사고시 발생되는 자계 분석)

  • Lim, Sung-Hun;Choi, Hyo-Sang;Kang, Hyeong-Gon;Ko, Seok-Cheol;Lee, Jong-Hwa;Choi, Myung-Ho;Song, Jae-Joo;Han, Byoung-Sung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07a
    • /
    • pp.601-604
    • /
    • 2003
  • The magnetic field generated in the iron core, which is required for the magnetic field to link each coil of the flux-lock type reactor, affects the fault current limiting characteristics of the flux-lock type high-Tc superconducting fault current limiter(SFCL). By applying numerical analysis for equivalent circuit of flux-lock type SFCL, the magnetic field induced in the iron core including currents of each coil was investigated. Through the analysis of magnetic field, we have analyzed that the magnetic field linked the 3rd coil, which is wound in the iron core, prevents the saturation of the iron core, but decreases the impedance of the flux-lock type SFCL.

  • PDF

Insulation Design for a 13.2kV/630A High-Tc Superconducting Fault Current Limiter (13.2kV/630A급 고온초전도 한류기의 절연설계)

  • Kang, Hyoung-Ku;Lee, Chan-Joo;Ko, Tae-Kuk;Seok, Bok-Yeol
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.941-942
    • /
    • 2007
  • The superconducting fault current limiter (SFCL) consists of superconducting coil for limiting the fault current and cryogenic cooling system for keeping the coil in superconducting condition. The study on the insulation design for superconducting coil and cryogenic cooling system should be elaborately performed to develop a high voltage SFCL. In this paper, insulation design of solenoid coil for 13.2kV/630A SFCL is performed through the AC dielectric breakdown test and lightning impulse dielectric strength test. The dependence of dielectric characteristics on the magnitude of liquid nitrogen pressure is also investigated. Through the investigation, it is verified that dielectric characteristics of sub-cooled nitrogen are strongly enhanced by the pressurization. The electrical insulation design of 13.2kV/630A SFCL is performed by applying the experimental results. The successful insulation design for development of 13.2kV/630A SFCL is confirmed by AC dielectric breakdown tests.

  • PDF

Experimental Analysis of Superconducting Fault Current Limiter Wound with Two Different HTS wires in Parallel

  • Kim, Ji-Tae;Jang, Jae-Young;Park, Dong-Keun;Chang, Ki-Sung;Kim, Young-Jae;Ko, Tae-Kuk
    • Progress in Superconductivity and Cryogenics
    • /
    • v.10 no.2
    • /
    • pp.30-33
    • /
    • 2008
  • Several kinds of superconducting fault current limiters (SFCLs), which reduces huge fault current, have been developing by many research groups. The SFCL has no impedance during normal operation, so it dose not give any influence to electric power system. The resistive type SFCL reduces the fault current with the impedance generated in the superconducting part of the SFCL when the fault current exceeds the critical current of SFCL. In this paper, a new type resistive SFCL made of bifilar coil wound with two different high-Tc superconducting (HTS) wires in parallel. Although a bifilar coil has theoretically no inductance, the bifilar coil made in this paper could generate inductance at fault. The specifications of the used two wires were considerably different, thus current distribution between the two HTS wire was different at fault. When the fault current exceeded the critical current of one wire in the bifilar coil, the momentary sharp increase of impedance was detected. Base on the results, a new resistive type SFCL can generate not only resistance but also inductance, which can be used to control a fault current in the future.

Increase of Operational Current in a SFCL using Series or Parallel Coupling of Coils (코일의 직.병렬결합을 이용한 초전도 사고전류제한기의 동작전류 증가)

  • Lim, Sung-Hun
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.21 no.10
    • /
    • pp.46-51
    • /
    • 2007
  • The fault current limiting characteristics of superconducting fault current limiter(SFCL) using magnetic coupling of two coils were investigated. This SFCL consists of a high-TC superconducting(HTSC) element and two coils with series or parallel connection on the same iron. In normal time, the inner magnetic fluxes generated by two coils are canceled in case that the HTSC element keeps superconducting state. However, in case that the resistance of the HTSC element happens by a short-circuit the magnetic fluxes, not cancelled, induce the voltages across two coils and the fault current can be limited by the impedance of this SFCL. This SFCL has the merit that the operational current of SFCL can be increased higher than the critical current of the superconducting element by adjusting the inductance ratio between two coils. To confirm its operation, the circuit for the fault simulation was constructed. From the measured voltage and current of the SFCL, it was confirmed that the operating current of this SFCL increased more than that of HTSC element's independent operation.

Current Limiting Characteristics According to the Increase of Voltage in Separated Three-Phase Flux-Lock Type Superconducting Fault Current Limiter Using YBCO CC (YBCO CC를 이용한 분리된 삼상 자속구속형 고온초전도 전류제한기의 전압 증가에 따른 전류제한 특성)

  • Doo, Seung-Gyu;Du, Ho-Ik;Kim, Min-Ju;Kim, Yong-Jin;Lee, Dong-Hyeok;Han, Byoung-Sung
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.06a
    • /
    • pp.355-356
    • /
    • 2009
  • In this paper, we investigated the fault current limiting characteristics according to the increase of voltage in the separates three-phase flux-lock type high-Tc superconducting fault current limiter using YBCO CC. The separated three-phase flux-lock type SFCL consists of single-phase flux-phase type SFCL in each phase. Superconductor was using the YBCO CC. To analyze the current limiting characteristics of a three-phase flux-lock type SFCL, the short circuit experiments were carded out fault such as the triple line-to-ground fault. The experimental result shows that fault current limiting characteristics was improved on the high voltage level.

  • PDF

Fabrication and Characteristic Test of the DC Reactor for 6.6kV /200A Inductive Superconducting Fault Current Limiter (6.6kV/200A급 유도형 초전도한류기용 DC 리액터의 제작 및 특성 실험)

  • 안민철;이승제;강형구;배덕권;김현석;고태국
    • Progress in Superconductivity and Cryogenics
    • /
    • v.5 no.2
    • /
    • pp.36-40
    • /
    • 2003
  • Inductive superconducting fault current limiter(SFCL) with DC reator rated on 6.6k $V_{rms}$/200 $A_{rms}$ has been developed in Yonsei University. The development of the DC reactor is the key technology in this type SFCL. This paper deals with the fabrication and characteristic test of the DC reactor. For the development of this magnet, the winding machine for high-Tc superconducting solenoid was manufactured. Using this machine, a large-scale HTS solenoid using Bi-2223 tape was fabricated successfully. This coil has 5 layers which are connected in series each other. The inductance of the DC reactor coil is 84mB. The cooling system was the sub-cooled nitrogen whose temperature is about 65K. The characteristic test of the coil was performed. The full quench current of this coil is about 490A.90A.

Operational Characteristics of SFCL using Magnetic Coupling of Coils (코일의 자기결합을 이용한 초전도 사고전류제한기의 동작특성)

  • Lim, Sung-Hun;Kim, Jae-Chul
    • Proceedings of the KIEE Conference
    • /
    • 2007.04c
    • /
    • pp.68-70
    • /
    • 2007
  • The operational characteristics of superconducting fault current limiter (SFCL) using magnetic coupling of coils were investigated. This SFCL consists of a high-Tc superconducting (HTSC) element and two coils with series or parallel connection on the same iron. This SFCL has the merit that the operational current of SFCL can be increased higher than the critical current of the superconducting element by adjusting the inductance ratio between two coils. To confirm its operation, the circuit for the fault simulation was constructed. From the measured voltage and current of the SFCL, it was confirmed that the resistance of HTSC element comprising this SFCL increased more than that of HTSC element's independent operation.

  • PDF