• Title/Summary/Keyword: distribution line conductor

Search Result 47, Processing Time 0.024 seconds

The Installation Technique of Grounding Electrode Conductors for Metal Oxide Distribution Surge Arresters (배전용 피뢰기의 접지도선 설치기법)

  • Lee, B.H.;You, I.S.;Lee, T.R.;Ahn, C.H.;Youn, J.S.;Youn, H.H.;Kim, J.S.;Kim, J.C.
    • Proceedings of the KIEE Conference
    • /
    • 2001.07c
    • /
    • pp.1718-1720
    • /
    • 2001
  • The route of surge arrester connection is very important because bends and kinds of leads increase the impedance to lightning surges and tend to nullify the effectiveness of a grounding electrode conductor. There is a need to know how effective installation of lightning surge arresters is made in order to control voltage and to absorb energy at high lightning currents. The effectiveness of a grounding conductor and bonding for 18[kV] metal oxide distribution line arresters was experimentally investigated with lightning and oscillating impulse voltages.

  • PDF

ACSR Inner Corrosion Detection by Eddy Current Sensor (와전류센서를 이용한 ACSR 전선의 내부부식 검출)

  • 강연욱;강지원;양병모;정재기
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.12 no.1
    • /
    • pp.12-19
    • /
    • 1998
  • This paper deals with ACSR(Aluminum Conductor Steel Reinforced) inner corrosion detection using a detector which automatically runs on an ACSR distribution line and inspects the inner corrosion of the conductor by utilization of the nondestructive eddy current test. According to corrosion appearance and development of ACSR, the impedance change of the eddy current coils is theoretically verified. And then specifications and performances of the detector are described. Experimental procedures and desirable test results are reported. In conclusion, this detector can realize the nondestructive detecting of an ACSR inner corrosion. Upgrading the maintenance efficiency and improving the reliability of distribution line, whether is covered with insulating materials or not, would be expected by this nondestructive test method.method.

  • PDF

Aging Analysis and Reconductoring of Overhead Conductors for Radial Distribution Systems Using Genetic Algorithm

  • Legha, Mahdi Mozaffari;Mohammadi, Mohammad
    • Journal of Electrical Engineering and Technology
    • /
    • v.9 no.6
    • /
    • pp.2042-2048
    • /
    • 2014
  • In medium voltage electrical distribution networks, reforming the loss reduction is important, and in line with this, the issue of system engineering and use of proper equipment Expansion of distribution systems results in higher system losses and poor voltage regulation. Therefore, an efficient and effective distribution system has become more important. So, proper selection of conductors in the distribution system is crucial as it determines the current density and the resistance of the line. Evaluation of aging conductors for losses and costs imposed in addition to the careful planning of technical and economic networks can be identified in the network design. In this paper the use of imperialist competitive algorithm; genetic algorithm; is proposed to optimal branch conductor selection and reconstruction in radial distribution systems planning. The objective is to minimize the overall cost of annual energy losses and depreciation on the cost of conductors to improve productivity given the maximum current carrying capacity and acceptable voltage levels. Simulations are carried out on 69-bus radial distribution network using genetic algorithm approaches to show the accuracy as well as the efficiency of the proposed solution technique.

A Study on the Analysis and Limitations of the Same Phase Identification Under 3-Phase Unbalanced Constant Current Loads (3상 불평형 정전류 부하 조건에서의 동 위상 판별에 대한 분석 및 한계에 관한 연구)

  • Byun, Hee-Jung;Shon, Su-Goog
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.6
    • /
    • pp.38-46
    • /
    • 2012
  • In this paper, the necessity for the identification of the absolute phase value is introduced and analyzed for a particular conductor line of a 3-phase type distribution network and the recent methods are also introduced. For the determination of the exact phase value for a specific point in the line, as compared with the phase reference point, the measured phase value must be within a range of ${\pm}60[^{\circ}]$. However, the phase of a particular point can fluctuate depending on the line constant, transformer wiring method, line length, line amperage, etc. A theoretical formulation such as Simulink modeling and analysis for a distribution network are conducted for the identification of phase at a specific point in the line. In particular, through evaluating the effects of unbalanced current loads at the time of determination of the phase value, the limitations of the present method for the determination of phases is described.

Study on Thermal Load Capacity of Transmission Line Based on IEEE Standard

  • Song, Fan;Wang, Yanling;Zhao, Lei;Qin, Kun;Liang, Likai;Yin, Zhijun;Tao, Weihua
    • Journal of Information Processing Systems
    • /
    • v.15 no.3
    • /
    • pp.464-477
    • /
    • 2019
  • With the sustained and rapid development of new energy sources, the demand for electric energy is increasing day by day. However, China's energy distribution is not balanced, and the construction of transmission lines is in a serious lag behind the improvement of generating capacity. So there is an urgent need to increase the utilization of transmission capacity. The transmission capacity is mainly limited by the maximum allowable operating temperature of conductor. At present, the evaluation of transmission capacity mostly adopts the static thermal rating (STR) method under severe environment. Dynamic thermal rating (DTR) technique can improve the utilization of transmission capacity to a certain extent. In this paper, the meteorological parameters affecting the conductor temperature are analyzed with the IEEE standard thermal equivalent equation of overhead transmission lines, and the real load capacity of 220 kV transmission line is calculated with 7-year actual meteorological data in Weihai. Finally, the thermal load capacity of DTR relative to STR under given confidence is analyzed. By identifying the key parameters that affect the thermal rating and analyzing the relevant environmental parameters that affect the conductor temperature, this paper provides a theoretical basis for the wind power grid integration and grid intelligence. The results show that the thermal load potential of transmission lines can be effectively excavated by DTR, which provides a theoretical basis for improving the absorptive capacity of power grid.

Arc Fusion Protection of Covered Conductors Using AFPD (섬락 단선 방지 장치에 의한 피복 절연 가공배전 선로의 유도뢰애 의한 단선 방지)

  • Lee, Yong-Han;Jung, Dong-Hak;Ha, Bok-Nam;NamKung, Do;Kim, Myong-Soo
    • Proceedings of the KIEE Conference
    • /
    • 1997.07c
    • /
    • pp.800-802
    • /
    • 1997
  • After flashover occurs on the overhead distribution line by lighting strokes(direct or induced), the power frequency arc current continues. If lightning flashover occurs on the overhead lines using covered conductors, the power frequency art current with fixed path overheats the conductor, and arc fusion fault can be occurred. There are two categories protecting or reducing methods of arc fusion faults caused by lightning stokes. - Reducing lightning flashover rate : G/W, LA, etc. - Protection by AFPD(Arc Fusion Protection Device) : power follow current interruption. This paper presents lightning surge phenomena on overhead distribution lines and protecting performance of arc fusion Protection devices to the lightning strokes nearby overhead line.

  • PDF

A Study on High Fault Detection In Power System (전력계통의 고임피던스 고장 검출 기법에 관한 연구)

  • Yim, Wha-Yeong;Ryu, Chang-Wan;Ko, Jae-Ho
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.48 no.1
    • /
    • pp.16-21
    • /
    • 1999
  • The analysis of distribution line faults is essential to the proper protections of the power system. A high impedance fault test, which was carried in Korean electric power systems, it was found that a arcing phenomenon occurred during the high level portion of conductor voltage in each cycle. In this paper, we propose a new method for detection of high impedance faults, which uses the arcing fault current difference during high voltage and low voltage portion of conductor voltage waveform. To extract this difference, we diveded one cycle fault current into equal spanned four data windows according to the magnitude of voltage waveform and applied fast fourier transform(FFT) to each data window. The frequency spectrum of current wavefrom in each portion are used as the inputs of neural network and is trained to detect high impedance faults. The proposed method shows improved accuracy when applied to staged fault data and fault-like load.

  • PDF

Optimal Routing of Distribution Network Considering Reliability Indices (신뢰도 지수를 고려한 배전계통의 최적 전력전송경로 결정)

  • 신동환;노병권;김진오
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.48 no.9
    • /
    • pp.1073-1080
    • /
    • 1999
  • Optimal routing of distribution networks can be attained by keeping the line power capacity limit to handle load requirements, acceptable voltage at customer loads, and the reliability indices such as SAIFI, SAIDI, CAIDI, and ASAI limits. This method is composed of optimal loss reduction and optimal reliability cost reduction. The former is solved relating to the conductor resistance of all alternative routes, and the latter is solved relating to the failure rate and duration of each alternative route. The routing considering optimal loss only and both optimal loss and optimal reliability cost are compared in this paper. The case studies with 10 and 24 bus distribution networks showed that reliability cost should be considered as well as loss reduction to achieve the optimal routing in the distribution networks.

  • PDF

The solution for preventing the expansion of cable joint caused by methane($CH_4$) gas to Water proof type of power cable (도체 수밀형 전력케이블의 가교잔사 가스에 의한 직선접속재 부풀음 현상 방지 대책)

  • Kim, Jong-Won;Lee, Ki-Soo;Paek, Heum-Soo;Choi, Bong-Nam;Park, Hee-Cheol
    • Proceedings of the KIEE Conference
    • /
    • 2000.07c
    • /
    • pp.2020-2022
    • /
    • 2000
  • The cross-linked polyethylene(herein after XLPE) insulated power cable emit the methane($CH_4$)gas in the course of chemical cross-linking process. The general stranded conductor easily discharge this methane gas through the gap of each stranded wires. But the special stranded conductor that filled with semi-conducting rubber compound to prevent water penetration which is applied to water proof type of cable(22.9kV CN/CV-W), disturb the methane gas emission. The pre-mold type cable joint shall be expanded gradually by emit of gas left in XLPE insulation. For example, sometimes the corona problem outbreak on a new power distribution line, resulted from the gap between the sleeve and semi-conductive layer of cable joint. If above mentioned problem especially happened on the way of operating. We have to shut down the line and try to discharge the methane gas in cable joint. In this point, we would like to explain the mechanism of methane gas & cable joint and our test result briefly. At last, we are pleased to introduce the solution for preventing reoccurrence of this problem.

  • PDF

Study on Tension and Thermal Properties of Corrosive-fractured Steel Sleeve (강 슬리브 파단 직선 슬리브의 장력 및 열적 특성 분석 연구)

  • Ahn, Sang-Hyun;Kim, Byung-Geol;Kim, Sang-Shu;Sohn, Hong-Kwan;Kim, In-Pyo;Kim, Sung-Kyu
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.21 no.11
    • /
    • pp.1036-1041
    • /
    • 2008
  • According to previous report, aged sleeves of old transmission line showed several defaulted installation patterns, which was biased or corrosive-fractured of steel sleeve installed cases. These defects can cause serious accidents such as rapid increasing of sag or falling out of overhead conductor from sleeves. Consequently, the defects lead to the major power outage. Corrosion of steel sleeve is a typical defect by aging of sleeves. And it occupied almost 25 percent of investigated aged sleeves. This paper studied thermal properties and tension for ACSR conductor in case of fractured steel sleeve model by corrosion. The temperature distribution within overhead conductor has a specific gradient. Thermal properties of splice connectors(sleeve and clamp) showed normal behavior. However, mechanical properties were worse than normal sleeves. The detailed results were presented in the text.