• Title/Summary/Keyword: Ventilation터널화재

Search Result 115, Processing Time 0.033 seconds

A Study on Fire ventilation design of road tunnel (도로터널에서의 화재환기 설계에 관한 연구)

  • Kim, Myung-Bae;Choi, Byung-Il;Choi, Jun-Seok;Han, Yong-Shik
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.6 no.2
    • /
    • pp.129-139
    • /
    • 2004
  • The several assumptions and design parameters to determine the ventilation rate in tunnel ventilation system were examined. In longitudinal ventilating tunnel, the ventilation rate has been determined by the critical velocity above which the smoke propagation to the upstream of ventilating air is prevented. Based upon the examination of assumptions and experimental results, we suggested the improved method to determine the critical velocity. In transverse ventilating tunnel, we found that the ventilation rate has been determined in accordance with the custom rather than fire-smoke dynamics such as the critical velocity in the longitudinal ventilating tunnel. It is because the ventilation rate in the transverse ventilation system has been determined by considering only the ventilation of contaminant by vehicle. To improve the ventilation design parameters based upon the fire-smoke dynamics, we conducted model tunnel fire experiments. From the experimental results, smoke propagating distance and smoke filling were suggested as the design parameter to determine the ventilation rate in transverse ventilating tunnel. And tunnels in Europe designed by the custom is found to have the dangerous nature in view of fire safety.

  • PDF

Numerical Predictions of Fire Characteristics of Passenger Train Fire in an Underground Subway Tunnel, Depending on Change of Location of Ventilation Facility (지하철 터널내의 객차 화재발생시 환기실 위치변화에 따른 화재특성의 수치적 연구)

  • Son, Bong-Sei;Chang, Hee-Chul
    • Fire Science and Engineering
    • /
    • v.22 no.5
    • /
    • pp.1-8
    • /
    • 2008
  • The study is to perform numerical analysis of train fire characteristics in an underground subway tunnel, depending the different locations of ventilation facility. To study the characteristics of train fire, two kinds of worst-case scenarios are selected, based on escape distance, escape time, and fire zone, and trends and thermal environments of tunnel are analyzed by changing the locations of ventilation facility for times. Fire characteristics is calculated by using FLUENT v.6.3.26, and turbulent flow is calculated by using the standard k-${\varepsilon}$ model. The numerical results show distribution of carbon monoxide concentration, temperature, and velocity. The results of this study will contribute to building the most suitable ventilation systems when designing subway stations and tunnels.

The Smoke Propagating Distance in the Reduced-scale Model for a Subway Railroad Tunnel (축소 모형을 이용한 지하철터널에서의 연기전파거리 측정)

  • Kim, Myung-Bae;Choi, Byung-Il;Oh, Chang-Bo;Han, Yong-Shik
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.7 no.4
    • /
    • pp.295-304
    • /
    • 2005
  • The smoke propagating distances are measured in case that a fire occurs within the subway railroad tunnel. The tunnel is 800m long and the dimension of the cross-section is. Three vertical shafts exist for smoke ventilation. The experiments are performed using the 1/50 reduced-scale model. The smoke propagating distances are measured by thermocouples and by visualization for the accuracy. In order to understand the effect of a fire size and ventilation capacity of the shafts on the smoke propagating distance, 9 test scenarios are chosen. Based on the results, the smoke propagating distance is shown to be important criteria for the ventilation design of the tunnel.

  • PDF

The Effects of Tunnel Geometrical Characteristics and Canopy Installation on the Ventilation and Fire Propagation (터널의 기하학적 형태 및 캐노피 설치가 터널 환기 및 화재 확산에 미치는 영향 분석)

  • Lee, Chang-Woo;Suh, Ki-Yoon;Kim, Jung-Wook
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.8 no.4
    • /
    • pp.325-334
    • /
    • 2006
  • Understanding the airflow characteristics within the canopy structure installed between closely adjacent tunnels either for light adaptation or for protection from snow hazards is required for the normal ventilation as well as safety system design. Grade, horizontal alignment, cross-sectional area and shape are known to substantially influence the fire smoke behavior and their influences raise great concern for the safety design. This paper aims at studying the effects of tunnel geometrical characteristics and canopy installation on the ventilation and fire propagation through CFD analysis. In the case of 145m long canopy, 50% opening ratio is preferred with respect to the airflow pattern and ventilation efficiency. When a 20MW fire occurs in a 1.8km-long tunnel and four 1250mm reversible jet fans are instantly turned on, smoke concentration at 40m downstream of the fire decrease 13% for the upgrade tunnel with 2% gradient and increases 20% for -2% gradient, compared to the standard horizontal tunnel. Backlayering is observed within 45m-long segment toward the entrance in 2% down-graded tunnel. In a rectangular tunnel, there is no significant difference of smoke concentration as well as velocity profile from the standard crown tunnel. Three-laned tunnel shows lower level of both profiles and backlayering is detected up to 50m upstream of the fire, while the risky situation rapidly disappears thereafter.

An Experimental Study on the Ventilation velocity of the Variation of Burning rate in Tunnel Fires - Heptane pool fire case (터널 화재시 배연속도가 연소율변화에 미치는 실험적 연구 - Heptane 풀화재 경우)

  • Ryou, Hong-Sun;Yang, Seung-Shin
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.7 no.2
    • /
    • pp.109-117
    • /
    • 2005
  • In this study, the 1/20 reduced-scale experiments using Froude scaling were conducted to investigate the ventilation velocity of the variation of burning rate in tunnel fires. The heptane square pool fire with heat release rate ranging from 3.71~15.6 kW were used. The burning rate of fuel was obtained by measuring mass using load cell and temperature distributions were measured by K-type theomocouples in order to investigate smoke movement. The ventilation velocity in the tested tunnel was controlled by inverter of the wind tunnel. In heptane pool fire case, the increase in ventilation velocity incresed the burning rate due to the direct supply of oxygen to the fire plume. For the same dimensionless velocity($\bar{V}$), burning rate increased as the size of pool fire decreased.

  • PDF

A study on safety evaluation by changing smoke ventilation mode in subway tunnels (지하철터널 환기변환모드에 따른 안전성 평가에 관한 연구)

  • Rie, Dong-Ho
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.5 no.4
    • /
    • pp.389-400
    • /
    • 2003
  • In order to recommend the mechanical smoke exhaust operation mode, Subway Environmental Simulation (SES) is used to predict the airflow of the inlet and outlet tunnel for the subway station. Fire Dynamic Simulation (FDS) is used the SES's velocity boundary conditions to clarity the smoke exhaust effectiveness by the variations with mechnical ventilation system. We compared each 6 types of smoke exhaust systems for the result of smoke density and temperature distributions for 1.5m height from the subway station base in order to clarify the safety evaluation for the heat and smoke exhaust on subway fire.

  • PDF

Experimental study on the effect of exhaust ventilation by shafts for case of fire in long traffic tunnels (장대 교통터널 화재시 수직갱의 배연효과에 관한 실험적 연구)

  • Yoo, Yong-ho;Yoon, Chan-hoon;Yoon, Sung-wook;Kim, Jin
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.7 no.1
    • /
    • pp.27-36
    • /
    • 2005
  • The objective of this study was to analyze the smoke movement and to investigate the effect of exhaust ventilation using by shafts for case of fire in long tunnels. Based on Froude modeling, the 1/50 scaled model tunnel (20 m long) was constructed by acrylic tubes and test were carried out systematically. The results of the shaft height test show that the effect on exhaust ventilation by a shaft delays the propagation time of backlayering, and the temperature decreases as the shaft height increases. If the fire occurs downstream of the shaft, the backlayering develops to get stronger by the shaft exhaust effect and then the propagation of CO and temperature increase along with propagation of CO. That is to say, in the case of fire downstream of the shaft, the shaft has the advantage of smoke exhaust effects, but it might result in a dangerous situation for the escaping passengers due to the more developed backlayering.

  • PDF

An Experimental Study on the Effect of Longitudinal Ventilation on the Variation of Burning Rate in Tunnel Fires (터널 화재시 종류식 환기가 연소율 변화에 미치는 영향에 관한 실험적 연구)

  • Yang Seung Shin;Kim Sung Chan;Ryou Hong Sun
    • Tunnel and Underground Space
    • /
    • v.15 no.1 s.54
    • /
    • pp.55-60
    • /
    • 2005
  • In this study, the 1/20 reduced-scale experiments using Froude scaling were conducted to investigate the effect of longitudinal ventilation on the variation of burning rate in tunnel fires. The methanol square pool fires with heat release rate ranging from 3.57 kW to 10.95 kW were used. The burning rate of fuel was obtained by measured mass using load cell and temperature distribution were measured by K-type theomocouples in order to investigate smoke movement. The wind tunnel was connected with one side of the tested tunnel, and logitudinal ventilation velocity in the tested tunnel was controlled by power of the wind tunnel. In methanol fire case, the increase in ventilation velocity decreased the turning rate due to the direct cooling of fire plume. For the same dimensionless velocity(V), homing rate decreased as the size of pool fire increased.

A Study on Jet Fan Start Time in Medium-Length Tunnel Fires (중규모터널 방재용 제트팬 초기 가동시간에 관한 연구)

  • Kim, Doo-Young;Lee, Chang-Woo
    • Tunnel and Underground Space
    • /
    • v.20 no.6
    • /
    • pp.465-474
    • /
    • 2010
  • Although the number of medium-length road tunnels, less than 1 km in length, has increased recently more than 30 percent each year, their ventilation and fire safety system design guidelines have not been established yet. The guidelines for long tunnel design are adopted even for the medium-length road tunnels. Therefore the necessity is brought up to optimize the ventilation and fire safety systems based on their own design guidelines. This study aims at determining the optimal start time of jet fan in case of 20 MW fires by analyzing smoke backlayering range, temperature distribution, range of poor visibility, evacuation time and critical velocity. The CFD study results are expected to contribute to propose the optimal fan operation mode.

Study on Heat and Smoke Exhaust Characteristics for Different Operating Modes of Platform and Tunnel Fans during a Passenger Train Fire (전동차 화재시 승강장 및 터널 환기실의 팬 작동에 따른 열 및 연기 배출 특성 연구)

  • Chang, Hee-Chul;Kim, Tae-Kuk;Son, Bong-Sei;Park, Won-Hee
    • Fire Science and Engineering
    • /
    • v.22 no.1
    • /
    • pp.61-67
    • /
    • 2008
  • This study is focused on the numerical predictions of heat and smoke exhaust characteristics in an underground subway station stopping a fire train. Various ventilation operating modes with the fan equipped the platform and tunnels are considered. Distributions of temperature, carbon monoxide and visibility at a height of 1.7 m(breath height) above the platform are analysed for different ventilation fan operation mode. The numerical results show that smoke and heat is rapidly removed through tunnel by operating the tunnels fans. We suggested that during evacuation of passengers is not completed, the ventilation system in the platform is activated. After completion of passenger evacuation tunnel fans are activated but the fans in the platform are stopped.