• Title/Summary/Keyword: Transient grounding impedance

Search Result 68, Processing Time 0.02 seconds

Characteristics of Transient Grounding Impedance under Surge Currents (서지전류에 대한 과도접지임피던스의 특성)

  • Lee, Deok-Hui;Park, Jong-Sun
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.48 no.11
    • /
    • pp.717-723
    • /
    • 1999
  • The transient characteristics of grounding systems play a major role in the protection of power equipments, electronic circuits and info-communication facilities against surges which arise from lightning or ground faults. Electronic devices are very weak against lightning surges injected from grounding systems and can be damaged. The malfunction and damage of electronic circuits bring about bad operation performances, a lot of economical losses, and etc. Therefore, in order to obtain the effective protection measure of electronic devices from overvoltages and lightning surges, the analysis of the transient grounding impedances in essential. One of this work is to examine the transient behaviors of grounding impedances under steplike currents for various grounding systems. And the other of this work is to evaluate the transient behaviors of a grid with rods under impulse currents and to investigate the effect of grounding lead wire. Transient grounding impedances of a grid with rods under impulse current waves have been measured as a parameter of the length of the grounding leads. Z-t, Z-i and V-i curves of transient grounding impedance under impulse current waveforms have been measured and analyzed. It was found that the grounding impedance gives the inductive, resistive and capacitive aspects under steplike current. Transient grounding impedance characteristics were very different with shapes, geometries of ground electrodes. Also, they were dependent on the waveform and magnitude of impulse current.

  • PDF

Characteristics of Grounding Impedances of Carbon Compound Grounding Electrodes (탄소혼합물 접지전극의 접지임피던스의 특성)

  • Lee, Kang-Soo;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.5
    • /
    • pp.54-60
    • /
    • 2011
  • This paper presents characteristics of frequency-dependent grounding impedance and transient grounding impedance for the carbon compound grounding electrode used in the installation of computerized electronic equipment and lightning protection system. The frequency-dependent grounding impedances were measured by applying sinusoidal currents in the frequency range from 100 [Hz] to 10[MHz], and the transient grounding impedances were examined by subjecting the impulse current with the front-time between 1~80[${\mu}s$]. As a result, the ground resistance of the carbon compound grounding electrode is less than that of another type grounding electrodes. The transient grounding impedance is relatively low and the conventional grounding impedance is rather lower than the ground resistance. The frequency-dependent grounding impedance of the carbon compound grounding electrode is capacitive and the grounding impedance is decreased with increasing the frequency of injected currents. Therefore in the case that the carbon compound grounding electrode is jointly used with large-scaled grounding electrodes, it is possible to reduce the high frequency grounding impedance of the integrated grounding electrode system.

Analysis for the impulsive impedance of counterpoise (매설지선의 임펄스임피던스의 해석)

  • Joe, Jeong-Hyeon;Kim, Jong-Ho;Beak, Young-Hwan;Kim, Dong-Seong;Lee, Gang-Su;Kim, Ki-Bok;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.05a
    • /
    • pp.88-91
    • /
    • 2009
  • For lightning currents, a grounding system shows the transient grounding impedance characteristics. A grounding system for protection against lightning should be evaluated by the transient grounding impedance, not it's ground resistance. The transient grounding impedance varies with the shape of ground electrode and earth characteristics as well as the waveform of lightning surge current. For the analysis and practical use of transient grounding impedance, the characteristics of transient grounding impedance should be analyzed theoretically and this paper suggests the theoretical analysis for the transient grounding impedance of counterpoise by using the distributed parameter circuit model. EMTP and Matlab are used to simulate the distributed parameter circuit model of counterpoise and the adequacy of the distributed parameter model of counterpoise is examined by comparing the simulated results with the measured results.

  • PDF

Simulated Analysis for the Transient Impedance Behaviors of Counterpoises Subjected to the Impulsive Currents (임펄스전류에 의한 매설지선의 과도임피던스특성에 대한 모의해석)

  • Joe, Jeong-Hyeon;Lee, Bok-Hee
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.10
    • /
    • pp.1861-1868
    • /
    • 2009
  • A ground electrode subjected to lightning surge current shows the transient impedance behaviors. The ground electrode for protection against lightning should be evaluated in view of the transient grounding impedance and conventional grounding impedance, not ground resistance. The transient impedance characteristics of ground electrodes are influenced by the shape of ground electrode and the soil characteristics, as well as the waveform of lightning surge current. In order to propose a simulation method of analyzing the transient impedance characteristics of the grounding system in practical use, this paper suggests a theoretical analysis method of distributed parameter circuit model to simulate the transient impedance characteristics of counterpoise subjected to lightning surge current. EMTP and Matlab programs were employed to compute the transient grounding impedances of three counterpoises with different lengths. As a consequence, the simulated results using the proposed distributed parameter circuit model are in good agreement with the measured results.

Grounding Characteristics Analysis of the Rod-Type Grounding Electrodes used for Electric Distribution Systems (배전계통에 사용되는 봉형 접지전극의 접지 특성 분석)

  • Kim, Kyung-Chul;Jung, Ji-Won
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.6
    • /
    • pp.49-56
    • /
    • 2011
  • Grounding system insures a reference potential point for electric devices and also provides a low impedance path for fault currents or transient currents in the earth. The ground impedance as function of frequency is necessary for determining its performance since fault currents could contain a wide range of frequencies. In this paper, the grounding resistance, grounding impedance and transient grounding impedance are measured by using 3-point fall-of-potential method in order to analyse grounding characteristics of the copper and concrete rod grounding electrodes. An equivalent transfer function model of the ground impedance and transient grounding impedance are identified from the measured values by using ARMA method and evaluated by comparing the conventional grounding impedance.

Transient Impedance Characteristics of Grounding Rods (봉상접지극의 과도임피던스 특성)

  • 김일권;김점식;송재용;길경석
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • 2000.10a
    • /
    • pp.568-572
    • /
    • 2000
  • This paper describes the experimental results of a transient impedance characteristics of grounding rods to a square pulse and standard lightning impulse current. The test were performed on single grounding rod($\phi$ 10mm, 1m) and triple-grounding rods( $\phi$ 10mm, 1m) of equilateral triangles with 5m spacing. For measurements of transient impedance, a pulse generator which can produce square wave of 30ns rise time and 20U Pulse duration was designed and fabricated. In the experiment, transient impedance of the grounding systems have been investigated from the recorded potential and current waveforms. The results showed that the value of the transient impedance is quite higher than the stationary resistance, and provide useful information for the value of a grounding system considered transient characteristics under a high frequency condition such as lightning stokes and ground-fault.

  • PDF

Transient Grounding Impedance Behaviors of Deeply-driven Ground Rods According to the Injection Point of Impulse Currents (임펄스전류의 인가위치에 따른 심매실 봉상 접지전극의 과도접지임피던스 특선)

  • Lee, Su-Bong;Li, Feng;Lee, Seung-Ju;Jeon, Byung-Wook;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.10
    • /
    • pp.62-68
    • /
    • 2008
  • This paper presents the transient and conventional grounding impedance behaviors of deeply-driven ground rods associated with the injection point of impulse currents. The transient grounding impedance strongly depends on the length of deeply-driven ground rod and the rise time and injection point of impulse currents, and the intrinsic inductance of ground rod has a significant affect on the transient grounding impedance of grounding system in fast rise time ranges. The reduction of inductance is decisive to improve the impulse impedance behaviors of deeply-driven ground rods. It is effective that grounding conductor is connected to the top of the ground rod as short as possible.

Transient Impedance of the Ground Grid and Deeply-driven Ground Rod (그리드접지와 심매설 접지전극의 과도임피던스)

  • Lee, Bok-Hee;Lee, Su-Bong;Lee, Tae-Hyung;Jung, Hyun-Uk;Jeong, Dong-Cheol;Gil, Hyoung-Jun
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.05a
    • /
    • pp.240-243
    • /
    • 2005
  • This paper presents the transient behaviors of grounding system impedance against lighting impulse currents. The dynamic characteristics of the deeply driven ground rod and grounding grid subjected to the impulse current with various rise time were investigated. It was found that the transient ground impedance strongly depends on the configuration and size of grounding electrodes and the shapes of impulse currents, and the inductance of grounding electrodes has a significant affect on the transient ground impedance of grounding system in the short time domain.

  • PDF

Grounding Impedance Behaviors Associated with the Current Injection Point and the Length of Counterpoise (매설지선의 길이와 전류인가점에 따른 접지임피던스특성)

  • Li, Feng;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.6
    • /
    • pp.66-71
    • /
    • 2009
  • This paper presents the grounding impedance behaviors of counterpoise exposed to impulse currents. The transient and conventional grounding impedances of three counterpoises having the length of 10, 30 and 50[m] were measured and analyzed as a function of the injection point of impulse currents. As a result, the trend of the conventional grounding impedances measured as a function of injection of impulse current is similar to the transient grounding impedance of counterpoise. The injection point of impulse current has great influence on the transient grounding impedance characteristics of counterpoise. The transient grounding impedance characteristics in a short time range are strongly dependent on the length of counterpoise. The transient characteristics of grounding impedance of 10[m] counterpoise subjected to the impulse current was capacitive behavior, on the other hand, those of 30[m] and 50[m] counterpoises were inductive behavior. It is found that the grounding conductor should be connected to the central point of counterpoise.

Grounding Characteristics Analysis of the Stainless-steel Plate Grounding Electrode for Distribution Poles (배전전주용 스테인리스강판 접지전극의 접지 특성분석)

  • Kim, Kyung-Chul;Lee, Kyu-Jin;Kim, Min-Sung;Jung, Ji-Won
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.8
    • /
    • pp.94-100
    • /
    • 2010
  • Grounding system insures a reference potential point for electric devices and also provides a low impedance path for fault currents or transient currents in the earth. The ground impedance as function of frequency is necessary for determining its performance since fault currents could contain a wide range of frequencies. In this paper, the grounding resistance, grounding impedance and transient grounding impedance are measured by using 3-point fall-of-potential method in order to analyse grounding characteristics of the stainless-steel plate grounding electrode. An equivalent transfer function model of the grounding impedance and transient grounding impedance are identified from the measured values by using ARMA method and evaluated by comparing conventional grounding impedances.