Abstract
This paper presents the grounding impedance behaviors of counterpoise exposed to impulse currents. The transient and conventional grounding impedances of three counterpoises having the length of 10, 30 and 50[m] were measured and analyzed as a function of the injection point of impulse currents. As a result, the trend of the conventional grounding impedances measured as a function of injection of impulse current is similar to the transient grounding impedance of counterpoise. The injection point of impulse current has great influence on the transient grounding impedance characteristics of counterpoise. The transient grounding impedance characteristics in a short time range are strongly dependent on the length of counterpoise. The transient characteristics of grounding impedance of 10[m] counterpoise subjected to the impulse current was capacitive behavior, on the other hand, those of 30[m] and 50[m] counterpoises were inductive behavior. It is found that the grounding conductor should be connected to the central point of counterpoise.
본 논문은 임펄스전류가 인가된 매설지선의 과도접지임피던스특성에 관한 것으로 길이가 10, 30, 50 [m]인 3개의 매설지선에 대하여 입 펄스전류의 인가점을 파라미터로 하여 과도접지임피던스와 규약접지임피던스를 측정하고 분석하였다. 임펄스전류의 상승시간에 대한 규약접지임피던스는 과도접지임피던스와 비슷한 경향이었다. 과도접지임피던스는 임 펄스전류의 인가위치에 영향을 크게 밭으며, 짧은 시간영역에서 과도접지임피던스는 매설지선의 길이에 매우 의존적이다. 임펄스전류가 인가된 10[m]의 매설지선은 용량성 특성이었으나 30[m]와 50[m]의 매설지선은 유도성 특성을 나타내었다. 접지도선은 매설지선의 중앙점에 접속하는 것이 바람직한 것으로 밝혀졌다.