Grounding Characteristics Analysis of the Rod-Type Grounding Electrodes used for Electric Distribution Systems

배전계통에 사용되는 봉형 접지전극의 접지 특성 분석

  • 김경철 (홍익대학교 전기공학과) ;
  • 정지원 (홍익대학교 전기공학과)
  • Received : 2011.03.03
  • Accepted : 2011.05.06
  • Published : 2011.06.30

Abstract

Grounding system insures a reference potential point for electric devices and also provides a low impedance path for fault currents or transient currents in the earth. The ground impedance as function of frequency is necessary for determining its performance since fault currents could contain a wide range of frequencies. In this paper, the grounding resistance, grounding impedance and transient grounding impedance are measured by using 3-point fall-of-potential method in order to analyse grounding characteristics of the copper and concrete rod grounding electrodes. An equivalent transfer function model of the ground impedance and transient grounding impedance are identified from the measured values by using ARMA method and evaluated by comparing the conventional grounding impedance.

Keywords

References

  1. IEEE Std 142-2007, IEEE Recommended Practice for Electric Power Distribution for Industrial Plants.
  2. IEEE Std 80-2000, IEEE Guide for Safety in Ac Substation Grounding.
  3. NESC(National Electrical Safety Code), 2006 Edition.
  4. F.A. Wenner, “A Method of Measuring Resistivity”, National Bureau of Standards, 1916.
  5. L. Ljung, “System Identification”, Prentice Hall, 1999.
  6. KSC IEC 62305, “피뢰시스템”, 2007.
  7. “Digital Earth Tester Model MEGGER DET 2/2”, AVO International Ltd., 2000.
  8. “CDEGS User's Guide”, SES Technologies Ltd., 2007.
  9. IEEE std 81-1983, “IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth surface Potential of a Ground system”, IEEE Inc., 1983.
  10. “Instruction Manual for ABEM Transmeter ASA4000”, ABEM Instrument Inc., Sweden 1999.
  11. MATLAB User's Guide, “System Identification Toolbox”, Math Work, 2007.