• Title/Summary/Keyword: Switching Overvoltage

Search Result 72, Processing Time 0.027 seconds

Analysis on the Effect of LCR Filter to Mitigate Transient Overvoltage on the High Voltage Induction Motor Fed by Multi Level Inverter (멀티레벨 인버터 구동 고압유도전동기에시 발생하는 과도과전압 저감을 위한 LCR필터의 효과분석)

  • Kim, Jae-Chul;Kwon, Young-Mok
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.3
    • /
    • pp.45-52
    • /
    • 2006
  • In this paper, we analyze on the effect of LCR filter to mitigate transient overvoltage on the high voltage induction motor fed by H-bridge cascaded 7-level inverter. The switching surge voltage that it was occurred in inverter appears transient overvoltage at the motor input terminal. the transient overvoltage becomes the major cause to occur the insulation failure by serious voltage stress in the stator winding of high voltage induction motor. The effect of transient overvoltage appears more serious in high voltage induction motor than low voltage induction motor. We selected LCR filter for reduction of the transient overvoltage. Consequently, we demonstrated that the LCR filter connected to the invertor output terminals greatly reduces the transient voltage stress and ringing. The results of simulation show the suppression of transient overvoltage at the motor end of a long cable. using EMTP

The Study on Application of Circuit Breaker without Closing Resistor in Short Transmission Line (단거리송전선에서 투입저항이 없는 차단기적용에 관한 연구)

  • 김정배;정영환;송원표
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.1
    • /
    • pp.31-37
    • /
    • 2004
  • In this paper, the analysis result of the switching surge in substation including GIS(Gas Insulated Switchgear) has been described using the EMTP(Electro Magnetic Transient Program) program. After performing the modeling of the input data, we have reviewed the energization overvoltages of GCB(Gas Circuit Breaker) without closing resistor in 345kV network, according to the conditions of simultaneously operating switch and statistically operating switch. Firstly, it can be known that the energization overvoltage of single line is higher than that of parallel energized line. Secondly, the maximum energization overvoltage obtained in statistics switch is higher than one in simultaneous switch. From these results, it can be known that the phase-to-earth energization overvoltages of $\alpha$-$\beta$ section are less than 2.2 p.u when closing resistor is eliminated. Therefore, it is possible to consider the circuit breaker eliminated the closing resistor in $\alpha$-$\beta$ section.

Flying Capacitor DTC Drive with Reductions in Common Mode Voltage and Stator Overvoltage

  • Rahmati, Abdolreza;Arasteh, Mohammad;Farhangi, Shahrokh;Abrishamifar, Adib
    • Journal of Power Electronics
    • /
    • v.11 no.4
    • /
    • pp.512-519
    • /
    • 2011
  • This paper gives a detailed analysis of the direct torque control (DTC) strategy in a five-level drive and proposes a 24-sector switching table. The known problems in low-voltage drives such as bearings currents and an overvoltage phenomenon which leads to premature failure are reviewed and the occurrence of these problems in medium voltage drives has been investigated. Then a solutions to these problems is presented and the switching table to deal with these problems is modified. Simulation and experimental results on a 3kVA prototype confirm the proposed solution. In implementing the above strategy a TMS320F2812 is used.

Analysis on the effect of RC filter to mitigate transient overvoltage on the high voltage induction motor fed by Multi level inverter (멀티레벨 인버터 구동 고압유도전동기에서 발생하는 과도과전압 저감을 위한 RC필터의 효과분석)

  • Kwon, Young-Mok;Kim, Jae-Chul;Kim, Young-Sung;Lee, Yang-Jin
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.399-403
    • /
    • 2005
  • In this paper, we analyze on the effect of RC filter to mitigate transient overvoltage on the high voltage induction motor fed by H-bridge cascaded 7-level inverter. The switching surge voltage becomes the major cause to occur the insulation failure by serious voltage stress in the stator winding of high voltage induction motor. The effect of switching surge appears more serious in high voltage induction motor than low voltage induction motor. Consequently, we demonstrated that the RC filter connected to the motor terminals greatly reduces the transient voltage stress md ringing. The results of simulation show the suppression of transient overvoltage at the motor end of a long cable. using EMTP

  • PDF

Switching Overvoltage Analysis of KEPCO 765KV System by EMTP (EMTP를 이용한 한전 765KV 계통 개폐과전압 해석)

  • Shim, Eung-Bo;Kim, Jeong-Boo;Jeon, Bok-Hyeon
    • Proceedings of the KIEE Conference
    • /
    • 1992.07b
    • /
    • pp.945-948
    • /
    • 1992
  • In this paper, switching overvoltages are analyzed for future 765kv power system using EMTP(Electro Magnetic Transient Program) and compared with TNA (Transient Network Analyzer) study results which was previously undertaken during overseas training in 1980 and 1988. The result shows the maximum of 2.10 PU at midpoint of 310Km transmission line which is higher than those of TNA study by 0.4 PU. The deviation of EMTP result from TNA is caused by limitation of nonlinear representation and also frequency dependent modeling in EMTP. Further analysis are required to get more exact switching overvoltage factors for future KEPCO 765KV system not only by EMTP but also TNA.

  • PDF

Insulation coordination of 765 KV double circuit transmission line (765 KV 2 회선(回線) 송전선(送電線) 절연협조(絶緣協助))

  • Kim, Jeong-Boo;Min, Suk-Won;Lee, Dong-Il
    • Proceedings of the KIEE Conference
    • /
    • 1988.07a
    • /
    • pp.774-777
    • /
    • 1988
  • This paper covers the insulation coordination of 765 KV transmission line in Korea Electric Power Corporation. The design for the lightning, switching surge, and contamination was conducted to increase the reliability of 765 KV line. The authors have used the result of a limited Westinghouse ANACOM swiching surge study of the Korea Electric Corporation's 765 KV Expansion plan. The study investigated the switching surge overvoltage distribution and maximum switching overvoltage when relosing 765 KV lines. They used the technical data of the suspension insulator for the contamination design, which was available from a foreign insulator manufacture. From this paper, the authors find out that the contamination design dominates to determine the number of insulator and the SOV design dominates the air clearance in the tower. Afterwards the authors will confirm this design by Demonstration Test with Korea Electro-technology Research Institute.

  • PDF

Overvoltage Snubber for a Diode-Clamped 3-level IGBT Inverter (다이오드 클램프형 3-레벨 IGBT 인버터용 과전압 방지 스너버)

  • Jung, Jae-Hun;Song, Woong-Hyub;Nho, Eui-Cheol;Kim, In-Dong;Kim, Heung-Geun;Chun, Tae-Won;Yoo, Dong-Wook
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.14 no.6
    • /
    • pp.514-521
    • /
    • 2009
  • This paper deals with a new overvoltage snubber for a diode-clamped 3-level IGBT inverter. Usually most power converters use snubber circuits to protect the switching devices from voltage spike. However, it is difficult for the diode-clamped multi-level converter to be protected from voltage spike with overvoltage snubber since the series connection of the switching devices. To solve the problem the characteristic of a overvoltage snubber for a DC-DC converter is analyzed, and a new snubber for a diode clamped 3-level inverter is proposed. The performance of the proposed snubber is verified through experiments.

A Study on Insulation Performance Enhancement of Existing Transmission Line Considering Overvoltage Analysis Result and Fault Characteristic (과전압 분석 결과와 고장특성을 고려한 기설 송전선로의 절연보강 방법에 관한 연구)

  • Kwak, Joo-Sik;Woo, Jung-Woog;Koo, Kyo-Sun;Kim, Kyung-Tak;Kweon, Dong-Jin
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.12
    • /
    • pp.162-168
    • /
    • 2009
  • This paper describes a study that is to redesign insulation of transmission lines and determine required the numbers of insulators in order to enhance the insulation performance of existing transmission lines which were constructed with standard insulation design, considering overvoltage analysis results, probabilities and characteristics of faults. To ensure proper insulation distance without deteriorating the required performance, EMTP model is established to calculate maximum overvoltage in the line. The fault records and predicted outage rates due to lightning and contamination in the line were investigated and analyzed respectively. It presents a method to determine the numbers of insulators considering the probability and the characteristic of fault.

Analysis of the Harmonic Resonance of Primary Restorative Transmission System Using PSCAD/EMTDC PART II (PSCADI/EMTDC를 이용한 시송전계통의 고조파 공진현상 분석 II)

  • Lee H. J.;Yoo W. K.;Lee K. S.;Park S. M.
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.48-50
    • /
    • 2004
  • The energization of high voltage transmission lines and transformers, that is an inevitable process in most countries as the first restorative action for wide-area blackout, may induce overvoltages such as sustained overvoltage, transient overvoltage and harmonic resonant overvoltage. And these may cause damages to power system equipments or failure of surge arresters. The harmonic resonant overvoltage originates in switching operations and nonlinear characteristics of equipments. Actually it is difficult to predict the occurrence of harmonic overvoltage, since they result from nonlinear characteristics of transformers and other equipments. This paper describes the analysis of domestic primary restorative transmission system using PSCAD/EMTDC. The harmonic resonance is verified and the solution to prevent harmonic resonance is proposed in this paper. As a result, the PSCAD/EMTBC simulation showed slightly conflictive results that had been presented by IEEE Power System Restoration Working Group report.

  • PDF

Investigation of Fault-Mode Behaviors of Matrix Converters

  • Kwak, Sang-Shin
    • Journal of Power Electronics
    • /
    • v.9 no.6
    • /
    • pp.949-959
    • /
    • 2009
  • This paper presents a systematic investigation of the fault-mode behaviors of matrix converter systems. Knowledge about converter behaviors after fault occurrence is important from the standpoint of reliable system design, protection and fault-tolerant control. Converter behaviors have been, in detail, examined with both qualitative and quantitative approaches for key fault types, such as switch open-circuited faults and switch short-circuited faults. Investigating the fault-mode behaviors of matrix converters reveals that converter operation with switch short-circuited faults leads to overvoltage stresses as well as overcurrent stresses on other healthy switching components. On the other hand, switch open-circuited faults only result in overvoltage to other switching components. This study can be used to predict fault-mode converter behaviors and determine additional stresses on remaining power circuit components under fault-mode operations.