• Title/Summary/Keyword: Partial insulation

Search Result 462, Processing Time 0.027 seconds

Partial Discharge Detection of High Voltage Switchgear Using a Ultra High Frequency Sensor

  • Shin, Jong-Yeol;Lee, Young-Sang;Hong, Jin-Woong
    • Transactions on Electrical and Electronic Materials
    • /
    • v.14 no.4
    • /
    • pp.211-215
    • /
    • 2013
  • Partial discharge diagnosis techniques using ultra high frequencies do not affect load movement, because there is no interruption of power. Consequently, these techniques are popular among the prevention diagnosis methods. For the first time, this measurement technique has been applied to the GIS, and has been tested by applying an extra high voltage switchboard. This particular technique makes it easy to measure in the live state, and is not affected by the noise generated by analyzing the causes of faults ? thereby making risk analysis possible. It is reported that the analysis data and the evaluation of the risk level are improved, especially for poor location, and that the measurement of Ultra high frequency (UHF) partial discharge of the real live wire in industrial switchgear is spectacular. Partial discharge diagnosis techniques by using the Ultra High Frequency sensor have been recently highlighted, and it is verified by applying them to the GIS. This has become one of the new and various power equipment techniques. Diagnosis using a UHF sensor is easy to measure, and waveform analysis is already standardized, due to numerous past case experiments. This technique is currently active in research and development, and commercialization is becoming a reality. Another aspect of this technique is that it can determine the occurrences and types of partial discharge, by the application diagnosis for live wire of ultra high voltage switchgear. Measured data by using the UHF partial discharge techniques for ultra high voltage switchgear was obtained from 200 places in Gumi, Yeosu, Taiwan and China's semiconductor plants, and also the partial discharge signals at 15 other places were found. It was confirmed that the partial discharge signal was destroyed by improving the work of junction bolt tightening check, and the cable head reinforcement insulation at 8 places with a possibility for preventing the interruption of service. Also, it was confirmed that the UHF partial discharge measurement techniques are also a prevention diagnosis method in actual industrial sites. The measured field data and the usage of the research for risk assessment techniques of the live wire status of power equipment make a valuable database for future improvements.

Development of On-Line Monitoring System for Pumped Storage Generator/Motor (양수발전소 발전-전동기 운전중 감시 시스템의 개발)

  • 김희동;주영호
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.53 no.3
    • /
    • pp.168-174
    • /
    • 2004
  • On-line monitoring system(OMS) has been developed for the pumped storage generator/motor The OMS is applied to diagnosis of the PD(partial discharge) activity of stator insulation, the shorted-turn of rotor winding and the variation of the air-gap between stator and rotor. The OMS consists of DAS(data acquisition system), main server system, gateway and display PC. The DAS measures the PD, the shorted-turn and air-gap from three sensors installed on the generator/motor. The gateway controls the data which sent by DAS. The main server system saves the data, analyzes the data and conducts the diagnostic algorithm. The display PC shows the diagnostic results of partial discharge, shorted-turn and air-gap. Field tests were conducted using PDA(partial discharge analyzer). The results of the OMS and PDA measurements can be directly correlated with normalized quantity number(NQN), PD magnitude(Qm) and PD pattern.

Comparative analysis of PRPD method and UHF sensor method for Partial Discharge in air (공기중 부분방전에 대한 PRPD측정법과 UHF센서측정법의 비교분석)

  • Lee, K.W.;Lee, Y.H.;Park, S.H.;Jang, D.U.;Kang, S.H.;Lim, K.J.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.07b
    • /
    • pp.882-885
    • /
    • 2002
  • Assessing the condition of air insulation by measuring electromagnetic wave generated in it by partial discharges gives warning of developing faults and breakdown which may give some bad effects to other thing concerned with it. Electromagnetic wave are taken from UHF antenna with 20k ~ 2GHz frequency range. The signal waveform and FFT(Fast Fourier Transform) results from UHF antenna for PD(partial discharge) generated from two different electrode(needle-plane, needle-needle) configurations are shown and it is processed by using PRPD($\Phi-q-n$ distribution) method. Cumulative pulse sequence during 100 period is compared with PRPD method. This also will show the possibility of making apparent distinction between two PD sources.

  • PDF

Time Delay Characteristics of Radiated Electromagnetic Wave with Partial Discharge (부분방전시 방사전자파의 시간지연특성)

  • Kim, Hae-Joon;Park, Kwang-Seo;Lee, Hyun-Dong;Kim, Ki-Chai;Lee, Kwang-Sik
    • Proceedings of the KIEE Conference
    • /
    • 2001.07c
    • /
    • pp.1774-1776
    • /
    • 2001
  • The most of faults in gas insulation of power facilities are caused by partial discharge. Therefore we simulated partial discharge and measured the radiated electromagnetic wave emitted from partial discharge in the $SF_6$ gas by biconical antenna. This paper describes time delay characteristics of radiated electromagnetic waves with distance between antenna and discharge source.

  • PDF

PD Measurement in oil with defects (결함별 절연유중 부분방전 측정 연구)

  • Sun, J.H.;Yi, S.H.;Kim, K.H.
    • Proceedings of the KIEE Conference
    • /
    • 2004.11d
    • /
    • pp.67-69
    • /
    • 2004
  • Since partial discharges in power transformers weaken their insulation performance the detection of partial discharge is very important for prevention of fatal incidents. This study describes use of electromagnetic coupler for measurement of partial discharge of transformers. Spiral antennas of which bandwidth is 0.5GHz to 3GHz were used as coupler and setup in chamber for partial discharge tests. Test results showed that outputamplitudes are increased with PD increase and frequencies of signal measured by these antennas are mostly distributed below about 800MHz.

  • PDF

Detection of Ultrasonic Signals by PD at the High Voltage Winding (고압권선에서 발생하는 부분방전에 의한 초음파 신호 검출)

  • Kweon, Dong-Jin;Kwak, Hee-Ro;Chung, Sang-Jin;Kim, Han-Sang;Song, Il-Keun;Kim, Kyoung-Wha
    • Proceedings of the KIEE Conference
    • /
    • 1995.11a
    • /
    • pp.456-458
    • /
    • 1995
  • This paper describes a diagnosis of power transformers by on-line detection of ultrasonic signals. Partial discharge in power transformer generates ultrasonic signals. The trend of the ultrasonic signal number can be measured when partial discharge is generated in HV Winding. The trend of the ultrasonic signal number could easily be distinguished by taking moving average. The insulation failure due to partial discharge in transformers can be predicted based in the trend analysis of the number of ultrasonic signals caused by partial discharge.

  • PDF

The Application of Pre-Breakdown Partial Discharge Detection Method for Breakdown of Investigation of Long Distance XLPE Cable (장조장 XLPE 케이블 절연 파괴 원인 규명을 위한 전구차단 장치의 응용)

  • Lee, C.Y.;Kim, D.W.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07c
    • /
    • pp.1827-1829
    • /
    • 2002
  • This paper describes AC test for long delivered drum length of cable using pre-breakdown partial discharge detection(PPD) method, which can be applied to observe the causes of electrical breakdown of EHV XLPE insulation. This method is to de-energize applied voltage to cable rapidly using pre-breakdown partial discharge, and is able to prevent complete breakdown. By this effect, defects such as voids, metal particles and protrusion in cable can be observed clearly. AC resonant test set was used for PPD method. Localization of partial discharge was performed by time difference detection of the traveling wave. Accuracy of localization was 1% to the length of test cable. Through several experiments with XLPE cable, successful results of PPD method were obtained.

  • PDF

A Technique for Removing Adjacent Induction Noise Mixed with Partial Discharge Signals of High Voltage Rotating Machines (고압 회전기 부분방전 신호에 혼합된 인접상 유도 잡음 제거 기법)

  • Youn, Young-Woo;Yi, Sang-Hwa;Hwang, Don-Ha;Choo, Young-Bae;Kang, Dong-Sik
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.2
    • /
    • pp.335-341
    • /
    • 2009
  • Analysis of the partial discharge signal, a technique to diagnose the stator winding insulation is a key function for the diagnosis of high voltage rotating machines and requires high precision. To satisfy this requirement, various denoising techniques such as filtering and differential methods were proposed. However, these techniques can not eliminate a adjacent induction noise that decreases reliability of the diagnosis. A simple novel denoising algorithm, therefore, is proposed for removing the adjacent induction noise in this paper. The algorithm shows good performance in the real partial discharge signals measured by 13kV class capacitive couplers installed at hydro-generator in Dae-cheong Dam.

Characteristics of Ultra High Frequency Partial Discharge Signals of Turn to Turn Defect in Transformer Oil (절연유 내 변압기 Turn간 결함에 의한 부분방전의 극초단파 전자기파 신호 특성)

  • Yoon, Jin-Yul;Ju, Hyung-Jun;Goo, Sun-Geun;Park, Ki-Jun
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.10
    • /
    • pp.2000-2004
    • /
    • 2009
  • In general, for the condition monitoring of a power transformer using the UHF PD measuring technique, detection of any partial discharge, identifying the defect in the transformer and locating the insulation defect are necessary. In this paper one of the most frequent detects which can result in turn to turn fault in power transformer was examined for identifying the defect. In order to model the defect, as a discharge source, a partial discharge cell was used for experimental activity. Magnitude of electromagnetic wave signals and corresponding amount of apparent discharge were measured simultaneously against phase of applied voltage to the discharge cell. Frequency range and phase resolved partial discharge signals were measured and analyzed. The results will be contributed to build the defect database of power transformer and to decrease the occurrence of transformer faults.

A Study on the Algorithm for Detection of Partial Discharge in G15 Using Wavelet Transform (웨이브렛 변환을 이용한 GIS의 부분방전 검출 알고리즘에 관한 연구)

  • 강진수;김철환
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.52 no.1
    • /
    • pp.25-34
    • /
    • 2003
  • Gas insulated switchgear(GIS) is an important equipment in a substation. It is highly desirable to measure a partial discharge(PD) in GIS which is a symptom before insulation breakdown occurs. The issue is that the PD signal is weak and sensitive to external noise. In this paper, the algorithm for detection of PD in GIS using wavelet transform is proposed. The wavelet transform provides a direct quantitative measure of spectral content, "dynamic spectrum", in the time-frequency domain. The recommended mother wavelet is 'Daubechies' wavelet. 'db4', the most commonly applied mother wavelet in the power quality analysis, can be used most properly in disturbance phenomena which occurs rapidly for a short time. Through the procedure of wavelet transform, noise extraction and reconstruction, the signal is Analyzed to determine the magnitude of PD in GIS. In experimental results, we can know that partial discharge is exactly detected in combination of Dl and D2 using wavelet transform.transform.