The Application of Pre-Breakdown Partial Discharge Detection Method for Breakdown of Investigation of Long Distance XLPE Cable

장조장 XLPE 케이블 절연 파괴 원인 규명을 위한 전구차단 장치의 응용

  • Lee, C.Y. (Electric Research & Technology Center, LG Cable Ltd.) ;
  • Kim, D.W. (Electric Research & Technology Center, LG Cable Ltd.)
  • Published : 2002.07.10

Abstract

This paper describes AC test for long delivered drum length of cable using pre-breakdown partial discharge detection(PPD) method, which can be applied to observe the causes of electrical breakdown of EHV XLPE insulation. This method is to de-energize applied voltage to cable rapidly using pre-breakdown partial discharge, and is able to prevent complete breakdown. By this effect, defects such as voids, metal particles and protrusion in cable can be observed clearly. AC resonant test set was used for PPD method. Localization of partial discharge was performed by time difference detection of the traveling wave. Accuracy of localization was 1% to the length of test cable. Through several experiments with XLPE cable, successful results of PPD method were obtained.

Keywords