• Title/Summary/Keyword: Islanding phenomenon

Search Result 27, Processing Time 0.027 seconds

A Study of Non-Detection Zone using AFD Method applied to Grid-Connected Photovoltaic Inverter for a variety of Loads (계통연계형 태양광발전 인버터에 사용된 AFD기법의 다양한 부하에 따른 단독운전 불검출영역에 대한 고찰)

  • Ko, Moon-Ju;Choy, Ick;Choi, Ju-Yeop
    • Journal of the Korean Solar Energy Society
    • /
    • v.26 no.1
    • /
    • pp.91-98
    • /
    • 2006
  • Islanding phenomenon of utility-connected photovoltaic power conditioning systems(PV PCS) can cause a variety of problems and must be prevented. If the real and reactive power supplied by PV PCS are closely matched to those of load, islanding detection by passive methods becomes difficult. The active frequency drift(AFD) method, called the frequency bias method, enables islanding detection by forcing the frequency of the voltage in the islanding to drift up or down. In this paper, non-detection zone(NDZ) of AFD is analyzed for the islanding detection method of utility-connected PV PCS by the simulation software tool PSIM.

A Novel Method for Anti-Islanding Using Reactive Power Control (무효전력 제어를 통한 새로운 독립운전 검출법)

  • Jeong Jin-Beom;Choi Bong-Ju;Ahn Kang-Soon;Kim Hee-Jun
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.54 no.4
    • /
    • pp.208-216
    • /
    • 2005
  • Recently, the study of islanding phenomenon, maintains its operation even when the utility grid is removed has lead to the trend of utility interactive inverters in photovoltaic generation systems. In this paper, a novel Anti-islanding method is presented. the proposed method can keep the real average power component constant by MPPT control and cause the load current frequency with only change of reactive power component under the islanding condition. its periodical change of Reactive power component can decrease the NDZ(Non-Detective zone) so that the detection of various loads will be possible. the insufficient effect if additional reactive power component to the grid is proved theoretically and the islanding detection is also confirmed from a experimental result with a inverter for 3kW photovoltaic generation system applied the proposed Anti-islanding method.

Novel AFD method of islanding detection with a periodic zero current for improving on islanding detection for grid-connected Photovoltaic inverters (계통연계형 태양광발전 인버터를 위한 주기적인 영전류 구간을 가지는 새로운 AFD 단독운전 검출기법)

  • Ko, Moon-Ju;Choy, Ick;Choi, Ju-Yeop;Song, Seung-Ho;Lee, Ki-Ok
    • Journal of the Korean Solar Energy Society
    • /
    • v.26 no.4
    • /
    • pp.17-23
    • /
    • 2006
  • This paper proposes a novel active frequency drift (AFD) method for the islanding prevention of grid-connected photovoltaic inverter. To detect the islanding phenomenon of grid-connected photovoltaic (PV) inverters concerning about the safety hazards and the damage to other electric equipments, many kinds of anti-islanding methods have been presented. Among them, AFD method using chopping fraction enables the islanding detection to drift up (or down) the frequency of the voltage during the islanding situation. In this paper, injecting the periodic zero current into the basic AFD method is proposed. This proposed method shows the analytical design value of cf to meet the test procedure of IEEE Std. 1547 with various load conditions. Detection of islanding is verified using simulation tool PSIM.

Novel islanding detection method for grid connected PV system (계통연계형 태양광발전시스템의 새로운 단독운전 검출기법)

  • Jung, Young-Seok;So, Jung-Hun;Yu, Byung-Gyu;Yu, Gwon-Jong;Choi, Jae-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2005.07b
    • /
    • pp.1705-1707
    • /
    • 2005
  • This paper proposes a novel active frequency drift(AFD) method for the islanding prevention of grid-connected photovoltaic inverter. To detect the islanding phenomenon of grid-connected photovoltaic(PV) inverters concerning about the safety hazards and the damage to other electric equipments, many kinds of anti-islanding methods have been presented. Among them, AFD method using chopping fraction(cf) enables the islanding detection to drift up(or down) the frequency of the voltage during the islanding situation. However, the performance of the conventional AFD methods, which have a certain value of cf only, is inefficient and difficult to design the appropriate cf value analytically to meet the limit of harmonics. In this paper, the periodic chopping fraction based on an AFD method is proposed. This proposed method shows the analytical design value of cf to meet the test procedure of IEEE Std. 929-2000 with the power quality and islanding detection time. To verify the validation of the proposed method, the islanding test results are presented. It is confirmed that the proposed method has not only less harmonic distortion but also good performance of islanding detection compare with the conventional AFD method.

  • PDF

A Simulation for Anti-islanding Method in PV-AF System and Existing Anti-islanding Method (PV-AF시스템에서 단독운전 방지기법 및 기존 단독운전 방지기법의 시뮬레이션 해석 및 비교)

  • Kim, Gyeong-Hun;Seo, Hyo-Ryong;Lee, Soek-Ju;Park, Min-Won;Yu, In-Keun;Jeon, Jin-Hong;Kim, Seul-Gi;An, Jong-Bo
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.206-207
    • /
    • 2007
  • Islanding is the electrical phenomenon in a part of a power network disconnected from the utility, where the loads are entirely supplied by PV systems, and where the voltage and frequency are maintained around nominal values. But islanding may result in power-quality issues, interference to grid-protection devices, equipment damage, and even personnel safety hazards[4]. Therefore, islanding must be detected and stopped. The existing anti-islanding methods have NDZ(None-detection Zone) or power quality degradation. But PV-AF power generation system has the function of not only shunt active filter but also anti-islanding method without NDZ. In this paper, It is proved that PV-AF system has originally the function of anti-islanding without not only NDZ and but current distortion

  • PDF

A Novel Method for Anti-Islanding Using Reactive Power (무효전력 제어를 이용한 새로운 독립운전 방지 기법)

  • Choi, Bong-Joo;Jeong, Jin-Beom;Kim, Hee-Jun;Baek, Soo-Hyun;Lee, Ju;Ahn, Kang-Soon
    • Proceedings of the KIEE Conference
    • /
    • 2004.10a
    • /
    • pp.203-206
    • /
    • 2004
  • An islanding occurs when the utility grid is removed but distributed sources continuo to operate and provide power to local loads and grid. This can cause a significant risk to safety and equipment. This report present a novel anti-islanding method to prevent an islanding phenomenon. The proposed method changes the reactive power of the load. Therefore the phase difference between output voltage and current is periodically changed within decided value. When the utility-grid is removed, the frequency of output voltage and current will increase or decrease. And the proposed system will detect the change of frequency and shut down the distributed source. While the conventional methods have some difficulties in detecting particular islanding condition such as a small change in loading, the proposed method can detect most conditions. The performance was verified through experiments.

  • PDF

Islanding detection of grid-connected inverter in parallel operation (병렬운전에서의 계통연계형 인버터의 단독운전 검출)

  • Jung, Young-Seok;Yu, Byung-Gyu;So, Jung-Hun;Yu, Gwon-Jong;Choi, Jae-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.232-233
    • /
    • 2007
  • In this paper, phenomenon of islanding parallel inverters in an ac-distributed system is proposed. The paper explores the test results of the parallel-connected inverters in grid-connected system. The test results are devised and analyzed taking into account the power quality and the islanding performance. The islanding test methods applied. Experimental results are provided from two 2 kVA inverters connected in parallel, showing the features of islanding test.

  • PDF

THD Analysis of Output Current for Active Frequency Drift Method in Anti-islanding (능동적 주파수 변환기법의 출력전류 고조파 왜형율 분석)

  • Lee, Ki-Ok;Choi, Ju-Yeop;Choy, Ick;Yu, Gwon-Jong;An, Jin-Ung
    • Journal of the Korean Solar Energy Society
    • /
    • v.30 no.1
    • /
    • pp.7-12
    • /
    • 2010
  • As many grid-connected photovoltaic power conditioning systems (PVPCS)are installed in many residential areas simultaneously, these have raised potential problems of network protection on electrical power system. One of the numerous problems is an Islanding phenomenon. In this paper, active frequency drift (AFD) method, one of the anti-islanding methods which is analyzed by current magnitude compensation and calculation of the fundamental component. Both harmonic component and RMS value of the output current for THD analysis are provided and verified by simulation.

Output Power Analysis of Active Frequency Drift Method for Anti-Islanding (단독운전방지를 위한 능동적 주파수 변환기법의 출력전력 분석)

  • Lee, Ki-Ok;Choi, Ju-Yeop;Choy, Ick;Yu, Gwon-Jong;An, Jin-Ung
    • Journal of the Korean Solar Energy Society
    • /
    • v.29 no.6
    • /
    • pp.75-80
    • /
    • 2009
  • Recently, as the grid-connected photovoltaic power conditioning systems (PVPCS) are installed in many residential areas, these have raised potential problems of network protection on electrical power system. One of the numerous problems is an Islanding phenomenon. In this paper, active frequency drift (AFD) method, one of the anti-islanding methods which is analyzed by current magnitude compensation and calculation of RMS value of the output power is proposed and verified by simulation.

Output Power Analysis for Active Frequency Drift Method (AFD 기법의 출력전력 분석)

  • Lee, Ki-Ok;Choi, Ju-Yeop;Choy, Ick;Yu, Gwon-Jong
    • 한국태양에너지학회:학술대회논문집
    • /
    • 2009.11a
    • /
    • pp.297-302
    • /
    • 2009
  • As the grid-connected photovoltaic power conditioning systems (PVPCS) are installed in many residential areas, these have raised potential problems of network protection on electrical power system. One of the numerous problems is an Islanding phenomenon. In this paper, active frequency drift (AFD) method, one of the anti-islanding analyzed by current magnitude compensation and calculation of RMS value of the output power.

  • PDF