• 제목/요약/키워드: Industrial Switchgear

검색결과 50건 처리시간 0.04초

25.8kV 고체절연스위치기어 개발 (Development of 25.8kV class solid insulated switchgear)

  • 이종혁;마지훈;유련;이재걸;원성연;이석원;김영근;길경석
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2008년도 추계학술대회 논문집 전기기기 및 에너지변환시스템부문
    • /
    • pp.226-228
    • /
    • 2008
  • In recent years, the companies of electric power equipment for MV and HV classes trend to develop the eco-friendly insulated(solid, eco-gas, air etc.) switchgear which replaces existent SF6 gas insulated switchgear due to environmental problems such as global warming and so on. This paper makes reference to the newly developed Solid Insulated Switchgear (SIS) which uses the eco-friendly material such as epoxy for insulation. The insulation of the solid insulated switchgear (SIS) is composed of an epoxy, vacuum and air. The solid insulated switchgear (SIS) is a slate of the art product. The advantages of SIS are advanced reliability, economical efficiency, safety, maintenance free, reduction of installation area and the protection of environment. The solid insulated switchgear (SIS) is FE Analyzed such as electromagnetic, mechanical, thermal and fluid in order to find the optimal design. Thens SIS has been verified by international standard test. (IEC 62271 - 100 and so on.) As a result of this, the solid insulated switchgear (SIS) has been estimated as an alternative for eco-friendly MV class switchgear.

  • PDF

3차원 자계해석을 통한 GIS 모선의 와전류에 의한 온도 상승 (30 Magnetic Analysis on Temperature Rise Resulting from Induced Eddy current In Gas Insulated Switchgear)

  • 이방욱;손종만;강종성;서정민
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2274-2276
    • /
    • 1999
  • In this work, temperature rise and eddy current distribution on the enclosure and conductor of 3 pole gas insulated switchgear were investigated using analytical and experimental measures. The design of the diameters of the conductors and the enclosures of a meal clad gas insulated switchgear is primarily based on the insulation requirements. It is very difficult problem to predict the temperature rise of enclosed switchgear due to the complexity of the phenomena of heat transfer and existence of eddy current loss. To overcome this situations, we focused on the eddy current distribution on the enclosure of switchgear caused by high current 3 pole conductor as a fundamental basis. The experimental results about temperature distribution of 3 pole gas insulated switchgear were reported and measurements are compared with predictions of three-dimensional thermal model for eddy current analysis. As a result, three dimensional numerical analysis found to be in close relationship with experimental results and thermal model is efficient to predict the abnormal temperature rise in switchgear.

  • PDF

중전압 차단 개폐장치의 기술동향과 진단기술 (MV Switchgear Technology Trend and Diagnosis Technology)

  • 이현동;이석원;신양섭;김영근
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 춘계학술대회 논문집 전기설비전문위원
    • /
    • pp.10-12
    • /
    • 2005
  • This paper describes MV switchgear technology trends and diagnosis technology. MV switchgear has been rapidly changed into compact, reliability and safety situation. And suggested road-map to implement condition assessment or condition based maintenance. On-line diagnosis technology, life evaluation technology and system technology are suggested.

  • PDF

산업용 분전반 적용을 위한 3상 전력 관리 장치 시작품 제작에 대한 연구 (The Prototype-Making of a Three-Phase Power Management Device for the Industrial Switchgear)

  • 고윤석;신현용
    • 한국전자통신학회논문지
    • /
    • 제5권5호
    • /
    • pp.498-503
    • /
    • 2010
  • 최근, 전력공급의 안정성과 신뢰성 그리고 고품질화를 위해 인터넷을 기반으로 하는 산업용 디지털 분전반이 새롭게 요구되고 있다. 따라서 본 논문에서는 3상 4선식 전력공급방식을 기반으로 하는 산업용 3상 분전반이 설계된다. 그리고 3상 산업용 분전반을 위한 전력관리 모듈이 시험 제작되며, 끝으로, 3상 전구 부하 시험을 통해 시작품의 3상 전압, 전류 측정 기능이 검증된다.

UHF Sensor를 이용한 SF6 절연 MV 개폐기의 부분방전 검출 시스템 (Partial Discharge Monitoring for $SF_6$ Insulated MV Switchgear using UHF sensors)

  • 이도훈;강원종;신양섭;김영근;오일성;김동명;권태호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.2040-2041
    • /
    • 2007
  • In this paper, the UHF PD(Partial Discharge) sensors for $SF_6$ insulated MV $SF_6$ switchgear have been proposed and related investigations have been performed in order to detect the PD which were produced inside the MV $SF_6$ switchgear. Firstly, the internal type UHF PD sensor based on spiral antenna theory has been developed. This type sensor is highly sensitive and has lowly effect on by on-site noise. Secondly, the external type UHF PD sensor was developed based on log periodic antenna concept. This type sensor is removable and detectable for operating switchgear. These sensors were designed and simulated using RF simulation tool. In order to verify the sensitivity of these sensors, we performed the on-site test using the mock-up switchgears including the artificial defects which were the protrusion on high voltage conductor, free moving metal particle and surface defect on insulator. These mock-up switchgear were installed on the test distribution line.

  • PDF

LabVIEW 기반의 수배전반 누설전류 진단기법 연구 (A Study on the Diagnostic Techniques of Leakage Current for Switch-Gear Based on LabVIEW)

  • 김용성;장성일;최정환;김광호
    • 산업기술연구
    • /
    • 제34권
    • /
    • pp.61-66
    • /
    • 2014
  • Recently, Because the consumption of electricity is increased, having stable electricity supply and diagnosis of the power device is important. In this paper, I propose a diagnostic techniques of the leakage current for switchgear based on LabVIEW NI's. Using the data obtained from the leakage current sensor installed in switchgear panels, in performed continuously diagnosis, notifications and warnings can be the administrator immediately results. It is expected accordingly, the administrator will be able to take prompt action. Using the virtual switchgear with a PXI NI's, war tested the proposed techniques.

  • PDF

72.5kV 20kA 전철용 가스차단기의 압력상승 측정 및 소전류 차단성능해석 (Pressure-Rise Measurement and Analysis of Low Current Interruption Capability of a 72.5kV 20kA Gas Circuit Breaker for Electrical Railway System)

  • 송기동;박경엽;정진교;오연호;민길식;박기엽
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1998년도 하계학술대회 논문집 A
    • /
    • pp.164-166
    • /
    • 1998
  • This paper presents the results of the measured pressure-rise and the analyzed results of the cold gas flow-field in a 72.5kV 20kA gas circuit breaker for the electrical railway system. The analysis of cold gas flow field and the calculation of electric field strength have been performed in 3 types of interrupters and the low current interruption capability has been estimated for each of the gas circuit breaker considering the opening speed, the nozzle shape and the stroke length.

  • PDF

초고압 Gas Insulated Switchgear 구동용 전동기 개발 (Development of Permanent Magnet Synchronous Motor for High voltage Gas Insulated Switchgear)

  • 오영진;정균하;이인우
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.919-920
    • /
    • 2007
  • Currently national High Voltage Gas Insulated Switchgear (GIS) operating mechanism is made up of spring operating mechanism or hydraulic operating mechanism. On the contrary, advanced technology trend in foreign countries replace current mechanical mechanism with electrical motor-drive mechanism that leads to participate GIS bid and increase sales with the point of simplification of driving system and IT application. Therefor it is essential to develop high voltage GIS using the motor-drive system to develop national heavy electric machine industries and catch up the technology to the advanced level. This paper therefore presents design and analysis of permanent synchronous motor for high voltage GIS, verifies the performance by the experimental test.

  • PDF

170kV GIS용 단로기의 현장 사용 실태 조사 (A Study on the Actual Condition Investigation of the Disconnecting Switchgear of 170kV GIS)

  • 이은석;김종서;천종철
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2003년도 하계학술대회 논문집 Vol.4 No.2
    • /
    • pp.1180-1183
    • /
    • 2003
  • 170kV GIS(Gas Insulated Switchgear) is widely used in large industrial factory-electrical facilities of private use because has many benefits. But Other equipments's failures are occurred by GIS failures and give rise economic problems to user. Therefore we will examine the actual condition of the 170kV GIS-electrical facilities of private use and are able to confirm the distribution characteristic analysis of disconnecting switchgear. In this paper, we presents the actual condition investigation of the disconnecting switchgear of 170kV GIS-electrical facilities of private use by post - failure pattern, inspection method, test equipments and so forth.

  • PDF

25.8kV $SF_6$가스절연 스위치기어(GIS)를 대체한 친환경 고체절연 스위치기어(SIS) 개발 (Development of the replaced Eco-friendly SIS with GIS for 25.8kV class)

  • 마지훈;정맹뢰;유련;원성연;이석원;김영근
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.1219_1220
    • /
    • 2009
  • In recent years, the companies of electric power equipment for MV, HV class trend to develop that the eco-friendly insulated(solid, eco-gas, air etc.) switchgear replace with existent SF6 gas insulated switchgear by environmental problems such as global warming and soon. This paper introduces the Solid Insulated Switchgear(SIS) which is the epoxy of eco-friendly insulation material. The characteristic of SIS to introduce in this paper is as following. 1) Eco-friendly. (SF6 gas free) 2) The structure of flexible system. (Expansion) 3) The optimum design. (The Analysis of electrical & mechanical) 4) An Interface treatment between epoxy and insert. (Molding technology) This paper described about some technology for development of SIS.

  • PDF