• 제목/요약/키워드: High voltage switchgear

검색결과 79건 처리시간 0.023초

$SF_6$ 상태에 따른 절연파괴전압 비교분석에 관한 연구 (The analysis & comparative method on the breakdown voltage in $SF_6$)

  • 최은혁;윤대희;박광서;박원주;주재현;최상태;이광식
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 학술대회 논문집
    • /
    • pp.335-338
    • /
    • 2004
  • In this paper the experiments of insulation characteristics by temperature change of $SF_6$ gas and insulation characteristics about liquid $SF_6$ in GIS(Gas Insulated Switchgear) were described. From this result, at low temperature, the breakdown voltage was increased with a drop of temperature and an increase of the inner pressure in GIS. The ability of insulation in liquid $SF_6$ was higher than that of the highly pressurized $SF_6$ gas. A liquid $SF_6$ discharge characteristics was caused by bubble formed evaporation of liquid $SF_6$ and bubble when high voltage apply to electrode. Corona was happened to weak bubble and was proceed to new bubble breakdown.

  • PDF

GIS에 있어서의 과도과전압(過渡過電壓) 측정용(測定用) 센서 (A Voltage Sensor for measurement of Very Fast Transients in GIS)

  • 이복희;백용현;하촌달치;서촌준언;석정승
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1990년도 하계학술대회 논문집
    • /
    • pp.297-300
    • /
    • 1990
  • The measurement of very fast transients generated by disconnecting switches in gas-insulated switchgear(GIS) have to deal with the problems such as reliability, interference pich-up, optimal design of high voitage equipments. This paper presents a new developed voltage sensor to measure the very fast transients, the basic theory of the measuring method, the design, structure of planar capacitive voltage probe are described. Finally the examples of modelling tests on an actual site GIS are discussed.

  • PDF

평등/불평등 전계하의 제조공기(I-Air)에 대한 압력별 절연파괴강도 특성 (Dielectric Strength for Imitation Air with Pressure Variation under Uniform and Non-Uniform Fields)

  • 이창욱;이창훈;최은혁;이상호;이광식
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2007년도 추계학술대회 논문집
    • /
    • pp.263-266
    • /
    • 2007
  • In this paper approves (AC and DC) high voltage by experimental GIS(Gas Insulated Switchgear) chamber and (AC and DC) power source to study breakdown characteristics by pressure(P) change and change of electrode distance(d) at (AC and DC) high voltage of Imitation I-Air, $N_2$ : $O_2$ = 79(%) : 21[%]) to alternate $SF_6$ and achieved research. Gave P change of I-Air to study I-Air's Dielectric Strength using uniform and non-uniform fields(sphere-sphere and Needle-Plane electrode) and studied relations dielectric strength($V_D$) by each P different d.

  • PDF

초고압 GIS용 절연스페이서의 성능평가 (Performance Evaluation on Epoxy Insulation Spacer for Extra High-voltage GIS)

  • 허종철;정주영;오창수;양대일;박정후
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2005년도 제36회 하계학술대회 논문집 C
    • /
    • pp.2220-2222
    • /
    • 2005
  • Epoxy Insualtion spacers for supporting the conductors and partitioning the sections in $SF_6$ Gas insulated Switchgear(GIS), require higher electrical, Thermal and mechanical reliability with other principal components in GIS to be operated without any failure in use. In this paper, we describe the results of the performance evaluation of electrical and mechanical properties for extra high-voltage GIS according to KEPCO spec. and the requirements of the insulators for GIS specified by IEC 62271-203(2004).

  • PDF

500MVA 대전력시험설비의 모터구동시스템 (Drive system for 500MVA high-power testing facility)

  • 정흥수;나대열;김선구;노창일;김원만;이동준
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 B
    • /
    • pp.858-860
    • /
    • 2003
  • This paper introduces the drive system for 500MVA short-circuit generator. Drive system is usually low-voltage, but this system is 2300V high-voltage using Insulated Gate Bipolar Transistor(IGBT). Drive system consists of switchgear, 18-pulse transformer, converter(source bridge), inverter(load bridge) and control rack. In this paper, It describes the function and construction of each part.

  • PDF

The Insulation Evaluation of N2:O2 Mixture Gas

  • Lee, Sang-Ho;Choi, Eun-Hyeok;Lim, Dong-Young;Park, Kwang-Seo;Kim, Se-Dong;Lee, Kwang-Sik
    • 조명전기설비학회논문지
    • /
    • 제24권7호
    • /
    • pp.41-46
    • /
    • 2010
  • With the improvement of industrial society, high quality electrical energy, simplification of operation and maintenance, and ensuring reliability are being required. Also we request an urgent change from $SF_6$ gas to an environment-friendly gas insulation material. In this paper, the experiments of breakdown characteristics by pressure and gap change of $N_2/O_2$ mixture gas through a GIS (Gas Insulated Switchgear) model were described. This paper reviews basic data of the surface discharge characteristics for Teflon resin in not only pure $N_2$, $N_2:O_2$ mixture gas as being focused on environmentally-friendly insulating gas, but also $SF_6$. Also, insulation characteristics by breakdown voltage and surface discharge voltage of $N_2:O_2$ mixture gas in the experimental chamber were studied.

Breakdown Characteristics of SF6 in Different State and Bubble Movements under AC High-Voltage

  • Choi, Eun-Hyeok;Lim, Chang-Ho;Yoon, Dae-Hee;Park, Kwang-Seo;Kim, Lee-Kook;Lee, Kwang-Sik
    • Journal of Electrical Engineering and Technology
    • /
    • 제2권2호
    • /
    • pp.257-262
    • /
    • 2007
  • In this paper the experiments of breakdown characteristics by temperature change of $SF_6$ gas($GSF_6$), and $SF_6$ liquid ($LSF_6$) in model GIS (Gas Insulated Switchgear) are described. From the experiment's results, the breakdown characteristics classify the vapor stage of $SF_6$ according to Paschen's law, in which the gas & liquid coexisted stage of voltage value increases, resulting in much deviation and the breakdown of voltage ($V_B$) low stage as the interior of the chamber gets filled with a mixture of $SF_6$ that is not liquefacted and remaining air that cannot be ventilated. The ability of $LSF_6$ insulation is higher than the high-pressurized $SF_6$ gas. The breakdown characteristics of $LSF_6$ were produced by bubble formed evaporation of $LSF_6$ and bubbles caused by high electric emission. It is considered in this paper that the results are fundamental data for electric insulation design of superconductor and cryogenic equipments machinery that will be studied and developed in the future.

교류전압 인가 상태에서 저압 진공관의 방전현상 (Ion Transport and High Frequency Dielectric of the Hollandite Nax$(Ti_{8-x}Cr_x)O_{16}$)

  • 왕강;최용성;이경섭
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2008년도 추계학술대회 논문집 Vol.21
    • /
    • pp.243-244
    • /
    • 2008
  • We experimentally investigated discharge phenomena inside vacuum interrupter at 1 to 20 Torr to simulate the vacuum leakage. We used glass type of vacuum interrupter where the internal pressure and the type of gasses can be varied according to requirement. The experiment is conducted under ac applied voltage and the experimental circuit is constructed to simulate the actual circuit used in cubical type insulated switchgear. We used two types of gases such as air and $SF_6$. The use of glass type vacuum interrupter allowed us to measure discharges occurring in vacuum interrupter optically. We measured and discussed the discharge occurring in both gases with a current transformer and ICCD camera. We a1so revealed that electromagnetic wave spectra emitted by the discharge have same frequency range for both gasses.

  • PDF

Discrimination of Insulation Defects in a Gas Insulated Switchgear (GIS) by use of a Neural Network Based on a Chaos Analysis of Partial Discharge (CAPD)

  • Jung, Seoung-Yong;Ryu, Cheol-Hwi;Lim, Yun-Sok;Lee, Ja-Ho;Koo, Ja-Yoon
    • Journal of Electrical Engineering and Technology
    • /
    • 제2권1호
    • /
    • pp.118-122
    • /
    • 2007
  • In this work, experimental investigation is carried out in order to design and fabricate the UHF sensor that is able to detect the partial discharges produced from 10 artificial defects introduced into the real scale 70kV GIS mock-up under high voltage within a well shielded room. As well, in order to verify the on-site applicability of our method, the newly proposed CAPD (chaos analysis of partial discharge) is combined with spectral analysis for identifying the nature of 10 artificial defects under investigation. The PD pattern recognition of each defect has been fulfilled by applying our ANN software. The result indicates that the recognition rate reaches up to 80% by the newly proposed method while the traditional PRPD analysis method allows us to obtain 41%. In consequence, it can be pointed out that the proposed method seems likely to be applicable to the real GIS at the site.

부분방전검출 신뢰도 향상을 위한 UHF 센서개선 및 성능검증 (Performance Verification and Improvement of UHF Sensor for the Increasement of the Partial Discharge Detection Reliability)

  • 김원규;김민수;백영식
    • 전기학회논문지
    • /
    • 제63권10호
    • /
    • pp.1461-1466
    • /
    • 2014
  • GIS(Gas Insulated Switchgear) is important power apparatus which have strong dielectric strength, supply electric power and is a part of the power system. Most substation type is configured as GIS. Recently, because of continuous increasement of GIS demand resulted from high quality & big capacity of electric power, the necessity of the preventive & diagnosis system is being expanded gradually. GIS partial discharge occurred on the UHF band is detected effectively by the method to IEC 60270 that recommend to be able to detect the apparent minimum discharge, 5 pC. Additionally, the UHF sensor should be installed to detect PD signal if Partial discharge signal, 5 pC occur in every part of GIS. Currently PD diagnosis system applying UHF sensor for GIS with various voltage level like 154 kV, 345 kV, 765 kV have been operated. And it is necessary to measure and analyze insulation breakdown phenomenon of inside GIS exactly. In this paper, we proposed Fat-dipole patch UHF sensor that is developed and more sensitive, excellent wide-range characteristic than the exising UHF sensor. And we performed KERI (Korea Electrotechnology Research Institute) reference test, which showed the excellent result for the all tests.