• Title/Summary/Keyword: GCB(Gas Circuit Breaker)

Search Result 53, Processing Time 0.023 seconds

Analysis of Cold Gas Flow in Puffer Type GCB Considering the Real Gas Property of $SF_6$ ($SF_6$ 가스의 실제 기체특성을 고려한 파퍼식 가스차단기 내의 냉가스 유동해석)

  • 김홍규;정진교;박경엽
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.53 no.3
    • /
    • pp.129-134
    • /
    • 2004
  • To analyze the performance of the gas circuit breaker(GCB), the flow field variables such as temperature, pressure and density should be evaluated accurately In the puffer chamber of puffer type GCB, the pressure rise may Exceed 20 bar and in this range of high pressure, $SF_6$ gas deviates the ideal gas property. Therefore, the real gas property of $SF_6$ should be taken into consideration for the accurate analysis of flow field. This paper presents the analysis technique of cold gas flow in GCB employing the real gas state equation of SF6. The FVFLIC method is Employed to solve the axisymmetric Euler equation. To reduce the computational effort of real gas state equation, the relationship between density and pressure is approximated by the polynomial at the temperature of 300K. The proposed method is applied to the test GCB model and simulation results show good agreement with the experimental ones.

Analysis of Thermal Recovery Characteristics for Nozzle of SF6 GCB Considering Nozzle Ablation (노즐용삭을 고려한 SF6 가스차단기 노즐의 열적회복특성 해석)

  • Lee Byeong-Yoon;Song Ki-Dong;Chong Jin-Kyo;Park Kyong-Yop
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.54 no.2
    • /
    • pp.76-82
    • /
    • 2005
  • In this paper, a method for analyzing the thermal recovery characteristics of the nozzle of gas circuit breaker was described. In order to obtain thermal recovery characteristics, the transient simulation of SF6 arc plasma within the nozzle was carried out. In particular, the nozzle ablation was taken into account by simultaneously solving the PTFE concentration equation with the governing equations such as continuity, momentum and energy equation. After that, post arc current calculation was performed with the rate of rise of recovery voltage changed. From the calculated post arc current, it was possible to suggest the thermal recovery characteristics of the nozzle of gas circuit breaker.

Estimation of Interruption Capability of a Serial-Hybrid Type Model Gas Circuit Breaker (직렬-복합소호형 모델 가스차단기의 차단성능평가)

  • 송기동;정진교;박경엽
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.53 no.9
    • /
    • pp.538-544
    • /
    • 2004
  • This paper presents the interruption capability of serial-hybrid type GCB (gas circuit breaker) compared with that of puffer type. First a puffer type model interrupter which has the stroke length of 80 mm has been designed and manufactured. And also, a serial-hybrid type interrupter which has the same design parameters as the puffer type interrupter except the serially arranged thermal-expansion chamber and puffer cylinder has been fabricated. Using a simplified synthetic test facility, the critical interruption capabilities of the two GCBs have been estimated. The critical di/dt, the critical dV/dt of ITRV (initial transient recovery voltage) and the minimum arcing time of the puffer type model GCB were 10.7 A/${\mu}\textrm{s}$, 5.5 kV/${\mu}\textrm{s}$, and 15.0 ms respectively. In the case of serial-hybrid type model GCB, each of the values was 16.6A/${\mu}\textrm{s}$, 11.5 kV/${\mu}\textrm{s}$ and 13.0 ms. As a conclusion of this work, it has been quantitatively confirmed that the hybrid type interrupter can obtain the sufficient interruption capability at the operating force which is so low that puffer type interrupter has not the interruption capability.

Circuit Interruption Performance Evaluation of $SF_6$ GIS Based Results of Cold Flow and Electrical Field Analysis ($SF_6$ 가스절연개폐기의 냉가스유동해석과 전계해석을 기초로 한 차단성능평가)

  • Bae, Dong-Jin;Song, Tae-Hun;Choi, Young-Chan;Lee, Ki-Ju;Kim, Ik-Mo;Kang, J.H.
    • Proceedings of the KIEE Conference
    • /
    • 1999.07a
    • /
    • pp.89-91
    • /
    • 1999
  • The performance of circuit interruption of $SF_6$ puffer cylinder type gas circuit breaker(GCB) has been evaluated from the results of electrical insulation strength which is depend on material property, such as $SF_6$ gas density in circuit breaker tank. In order to determine circuit breaker dimension in the safety criteria. electrical field analysis has been done by finite element method. Gas density of concerned area in the circuit breaker has been calculated. In order to predict small current break performance, Electrical field analysis result must be calculated based the results of density from cold flow dynamics. The proposed method has been carried out and evaluated for 362kV class high voltage GIS.

  • PDF

Interruption Capability of Hybrid Type GCB with High Opening Speed (고속도 개극 시의 복합소호 가스차단기의 차단특성)

  • Song Ki-Dong;Chong Jin-Kyo;Park Kyong-Yop
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.54 no.9
    • /
    • pp.408-413
    • /
    • 2005
  • This paper presents the basic design technology on the hybrid type GCB(gas circuit breakers) through the test results. The three type hybrid interrupters according to the arrangement of the thermal expansion chamber and the puffer cylinder(they are called 'serial type', ' parallel/exchanged type ,' and ' parallel/separated type ' respectively in this work) were designed and manufactured and then the tests of operating characteristics and interrupting were performed using a simplified synthetic test facility. The interruption capability with the type and the opening speed and the pressure rise which is required to interrupt were examined. The change of pressure rise with the number of interruption was given quantitatively and therefore the pressure rise can be predicted. Finally, it was shown that the interruption capability tends to increase with the increasing of opening speed in the puffer type; however, the hybrid type interrupter has a different interruption characteristic.

The Study on Application of Circuit Breaker without Closing Resistor in Short Transmission Line (단거리송전선에서 투입저항이 없는 차단기적용에 관한 연구)

  • 김정배;정영환;송원표
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.53 no.1
    • /
    • pp.31-37
    • /
    • 2004
  • In this paper, the analysis result of the switching surge in substation including GIS(Gas Insulated Switchgear) has been described using the EMTP(Electro Magnetic Transient Program) program. After performing the modeling of the input data, we have reviewed the energization overvoltages of GCB(Gas Circuit Breaker) without closing resistor in 345kV network, according to the conditions of simultaneously operating switch and statistically operating switch. Firstly, it can be known that the energization overvoltage of single line is higher than that of parallel energized line. Secondly, the maximum energization overvoltage obtained in statistics switch is higher than one in simultaneous switch. From these results, it can be known that the phase-to-earth energization overvoltages of $\alpha$-$\beta$ section are less than 2.2 p.u when closing resistor is eliminated. Therefore, it is possible to consider the circuit breaker eliminated the closing resistor in $\alpha$-$\beta$ section.

Hot Gas Analysis of Circuit Breakers By Combining Partial Characteristic Method with Net Emission Coefficient

  • Park, Sang-Hun;Bae, Chae-Yoon;Jung, Hyun-Kyo
    • KIEE International Transaction on Electrical Machinery and Energy Conversion Systems
    • /
    • v.3B no.3
    • /
    • pp.115-121
    • /
    • 2003
  • This paper proposes a radiation model, which considers radiation transport as an important component in hot gas analysis. This radiation model is derived from combining the method of partial characteristics (MPC) with net emission coefficient (NEC), and it covers the drawbacks of existing models. Subsequently, using this proposed model, the arc-flow interaction in an arcing chamber can be efficiently computed. The arc is represented as an energy source term composed of ohmic heating and the radiation transport in the energy conservation equation. Ohmic heating term was computed by the electric field analysis within the conducting plasma region. Radiation transport was calculated by the proposed radiation model. Also, in this paper, radiation models were introduced and applied to the gas circuit breaker (GCB) model. Through simulation results, the efficiency of the proposed model was confirmed.

A Study on the Computational Technique of Cold Gas Flow in Puffer Interrupter (파퍼식 차단부의 냉가스 유동해석기법에 관한 연구)

  • Choi, Y.K.;Song, K.D.;Shin, Y.J.;Park, K.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1997.07a
    • /
    • pp.104-108
    • /
    • 1997
  • The puffer type GCB(gas circuit breaker) has been widely used in modern transmission power system. Understanding the motion of cold $SF_6$ gas flow is essential for the better design of those GCB's. For this purpose, a program using the so-called FLIC(Fluid-In-Cell) method has been developed and applied to a puffer type GCB. The calculated results are compared with those from the measurement and the computation by commercial CFD (Computational Fluid Dynamics) package 'RAMPANT' and show fairly good agreement.

  • PDF

Evaluation Method I of the Small Current Breaking Performance for SF(sub)6-Blown High-Voltage Gas Circuit Breakers (초고압 $SF_6$ 가스차단기의 소전류 차단성능 해석기술 I)

  • 송기동;이병운;박경엽;박정후
    • The Transactions of the Korean Institute of Electrical Engineers B
    • /
    • v.50 no.7
    • /
    • pp.331-337
    • /
    • 2001
  • With the increasing reliability of analysis schemes and the dramatically increased calculating speed, the computer simulation has become and indispensable process to predict the interruption capacity of circuit breakers. Generally, circuit breakers have to possess both the small current and large current interruption abilities and the circuit breaker designers need to evaluate its capacities to save the time and the expense. The analysis of small current and the large current interruption performances have been considered separately because the phenomena occurring in a interrupter are quite different. To analyze the dielectric recovery after large current interruption many physical phenomena such as heat transfer, convection and arc radiation, the nozzle ablation, the ionization of high temperature SF(sub)6 gas, the electric and themagnetic forces and so forth mush be considered. However, in the analysis of small current interruption performance only the cold gas flow analysis needs to be carried out because the capacitive current is to small that the influence from the current can be neglected. In this paper, an empirical equation which is obtained from a series of tests to estimate the dielectric recovery strength has been applied to a real circuit breaker. The results of analysis have been compared with the test results and the reliability has been investigated.

  • PDF

Calculation of Pressure Rise in the Puffer Cylinder of EHV GCB Without Arc (무부하시의 초고압 GCB의 파퍼실린더 내부의 상승압력 계산)

  • Park, K.Y.;Song, K.D.;Choi, Y.K.;Shin, Y.J.;Song, W.P.;Kang, J.H.
    • Proceedings of the KIEE Conference
    • /
    • 1994.07b
    • /
    • pp.1559-1561
    • /
    • 1994
  • At present, the principle of puffer action in high current interruption is adopted in almost of the EHV(Extra High Voltage) and UHV(Ultra High Voltage) GCB(Gas Circuit Breakers). The thermal interruption capability of these GCBs critically depends on the pressure rise in the puffer cylinder at current zero. The pressure rise in the puffer cylinder depends on the puffer cylinder volume, flow passage and leakage area in the interrupter, stroke curve etc. Recently commercial CFD(Computational Fluid Dynamics ) packages have been widely adopted to calculate the pressure distribution in the interrupter. However, there are still several problems with it, e.g. very expensive price, moving boundary problem, computation time, difficulty in using the package etc. Thus, the calculation of the puffer cylinder pressure in simple and relatively correct method is essential in early stage of GCB design. In these paper, the model ing technique and computed results for EHV class GCB (HICO, 145kV 40kA and 362kV 40kA GCB) are presented and compared with available measured results.

  • PDF