• Title/Summary/Keyword: Fall-of-potential method

Search Result 77, Processing Time 0.029 seconds

Grounding Characteristics Analysis of the Stainless-steel Plate Grounding Electrode for Distribution Poles (배전전주용 스테인리스강판 접지전극의 접지 특성분석)

  • Kim, Kyung-Chul;Lee, Kyu-Jin;Kim, Min-Sung;Jung, Ji-Won
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.8
    • /
    • pp.94-100
    • /
    • 2010
  • Grounding system insures a reference potential point for electric devices and also provides a low impedance path for fault currents or transient currents in the earth. The ground impedance as function of frequency is necessary for determining its performance since fault currents could contain a wide range of frequencies. In this paper, the grounding resistance, grounding impedance and transient grounding impedance are measured by using 3-point fall-of-potential method in order to analyse grounding characteristics of the stainless-steel plate grounding electrode. An equivalent transfer function model of the grounding impedance and transient grounding impedance are identified from the measured values by using ARMA method and evaluated by comparing conventional grounding impedances.

Design and Implementation of Wideband Grounding Impedance Measurement Device using IQ Demodulation Method (IQ 복조 기법을 이용한 광대역 접지 임피던스 측정기의 설계 및 구현)

  • Kim, Young-Jin;Gil, Hyung-Jun;Kim, Sung-Ju;Kim, Jae Hyung
    • Journal of the Korean Society of Safety
    • /
    • v.31 no.6
    • /
    • pp.19-24
    • /
    • 2016
  • One of key parameters on lightning protection system design of electric, information and communication system is grounding impedance. Earth impedance includes numerous information about earthing performance of grounding system. This paper suggests grounding impedance measuring device which is comprised of wideband current source, voltage and current measuring components. We used IQ Demodulation to measure more accurate phase difference of voltage and current. The range of frequency is up to 1 MHz that is IEEE defined as the range of lightning surge. We compared developed grounding impedance measuring device with existing one to test its performance, and we used grounding system while we implemented measurement and analysing by using fall of potential method IEEE Std.81 proposed.

Measurement Method of the Frequency Dependent Characteristics of Ground Impedance (접지임피던스의 주파수 의존성 측정기법)

  • Eom Ju-Hong;Lee Bok-Hee
    • 한국정보통신설비학회:학술대회논문집
    • /
    • 2004.08a
    • /
    • pp.211-214
    • /
    • 2004
  • The measurement system of ground impedance is based on a computer aided technique. The magnitude and phase of ground impedance were determined by the novel measurement and analysis using the revised fall-of-potential method. The ground impedances of the ground rod of 30 m long are considerably dependent on the frequency. The ground impedance is mainly resistive in the frequency range of 3-20 kHz. At higher frequencies, the reactive components of the ground impedances are no longer negligible and the inductance of the ground rod was found to be the core factor deciding the ground impedance.

  • PDF

The Measurement of the Grounding Resistance Using the Ground Current of the Distribution System (접지선 전류를 시험 전류원으로 활용한 접지저항 측정기법에 관한 연구)

  • Kang, Moon-Ho
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.11a
    • /
    • pp.293-295
    • /
    • 2004
  • Public utilities adopt the grounding rules ; class I, class II, class III and special class III, and install the grounding electrodes in distribution facilities. To keep the safety of the human and the facilities, Public utilities also manage the value of ground resistance in distribution system biennially. At present the Hook-On meter is normally used to measure the ground resistance although it has ${\pm}5[%]$ measuring error and it can not measure the exact value when the current is over 1[A]. In addition it is very difficult to use the fall-of-potential method in distribution system. In this paper we propose the new measurement method using ground current of distribution system as the current source.

  • PDF

Analysis of Ground Resistance Reduction Effect by Common use of Ground Poles (접지극의 공용화를 통한 접지저항 저감효과 분석)

  • Hong Sung Taek;Lee Eun Chun;Shin Gang Wook
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.440-442
    • /
    • 2004
  • The ground resistance of middle scale ground pole was measured by using the 'fall of potential method' suggested by IEEE However, the measured resistance value was lower than the minimum value required To solve this problem. ground pole was set to be used commonly. In this research. ground resistance was measured using the newly suggested method and the results were analyzed to see if they satisfied the domestic regulation The results of this research will be applied to the management works as well as the establishment of new plan.

  • PDF

Trust Analysis of Ground Resistance Measurements by the Substitute Auxiliary Electrode (대체 보조전극을 이용한 접지저항 측정 신뢰성 분석)

  • Lee, Sang-Ick;Yoo, Jae-Geun;Jeon, Jeong-Chay;Jeon, Hyun-Jae
    • The Transactions of the Korean Institute of Electrical Engineers P
    • /
    • v.56 no.2
    • /
    • pp.109-114
    • /
    • 2007
  • This paper summarize about the auxiliary electrode measured a ground resistance. The method to measure a ground resistance is the fall-of-potential method to using an auxiliary electrode. And an auxiliary electrode must be set up on the ground. Today it is so difficult to set up the auxiliary electrode on the ground because of many concrete building and many paved roads. So this paper is regarding a trust analysis of the ground resistance measurement by the substitute auxiliary electrode. It substituted a iron structure around the building, a neutral line multiplex ground to earth, a wire net for auxiliary electrode. This information is confirmed bv compared with the measurement value.

Comparison of Ground Resistance Measurement Value by the Substitute Auxiliary Electrode (대체 보조전극을 이용한 접지저항 측정값 비교)

  • Lee, Snag-Ick;Yoo, Jae-Geun;Jeon, Jeong-Chay;Jeon, Hyun-Jae
    • Proceedings of the KIEE Conference
    • /
    • 2007.04b
    • /
    • pp.85-87
    • /
    • 2007
  • This paper summarize about the auxiliary electrode measured a ground resistance The method to measure a ground resistance is the fall-of-potential method to using an auxiliary electrode. And an auxiliary electrode must be set up on the ground. Today it is so difficult to set up the auxiliary electrode on the ground because of many concrete building and many paved roads. So this paper is regarding of the ground resistance measurement by the substitute auxiliary electrode. It substituted a iron structure around the building, a wire net for auxiliary electrode. This information is confirmed by compared with the measurement value.

  • PDF

A Study on Prevention of Construction Opening Fall Accidents Introducing Image Processing (이미지 프로세싱을 활용한 개구부 추락 사고예방에 관한 연구)

  • Hong, Sung-Moon;Kim, Buyng-Chun;Kwon, Tae-Whan;Kim, Ju-Hyung;Kim, Jae-Jun
    • Journal of KIBIM
    • /
    • v.6 no.2
    • /
    • pp.39-46
    • /
    • 2016
  • While institutional matters such as improvement on Basic Guidelines for Construction Safety are greatly concerned to reduce falling accidents at construction sites, there are short of studies on how to practically predict accident signs at construction sites and to preemptively prevent them. As one of existing accident prevention methods, it was attempted to build the early warning system based on standardized accident scenarios to control the situations. However, the investment cost was too high depending on the site situation, and it did not help construction workers directly since it was developed to mainly provide support operational work support to safety managers. In the long run, it would be possible to develop the augmented reality based accident prevention method from the worker perspective by extracting product information from BIM, visually rendering it along with site installation materials term and comparing it with the site situation. However, to make this method effective, the BIM model should be implemented first and the technology that can promptly process site situations should be introduced. Accordingly, it is necessary to identify risk signs through lightweight image processing to promptly respond only with currently available resources. In this study, it was intended to propose the system concept that identified potential risk factors of falling accidents by histogram equalization, which was known as the fastest image processing method presently, used visual words, which could enhance model classification by wording image records, to determine the risk factors and notified them to the work manager.

Minimized Distance of the Current Electrode in the Measurement of Ground Resistance (접지저항 측정에 있어서 전류전극의 최소 이격거리)

  • Lee, Sang-Mu;Kang, Young-Heung;Yang, Jun-Gyu
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.10
    • /
    • pp.68-73
    • /
    • 2006
  • As in the measurement of ground resistance by using the 3 point fall-of-potential method, it is known that the distance of current electrode should be at the point of showing the plateu on the potential curve. But the problem is that it my be practically impossible to meet the condition in actual sites. For solving such a situation, this paper provides the least distance of current electrode according to the analysis for the test-field measurement showing that it is feasible to measure the ground resistance in the two in current electrode distance as the length of driven-rod type electrode and the some district length of mesh electrode.

Effective Impulse Impedances of Deeply Driven Grounding Electrodes

  • Lee, Bok-Hee;Jeong, Dong-Cheol;Lee, Su-Bong;Chang, Keun-Chul
    • KIEE International Transactions on Electrophysics and Applications
    • /
    • v.4C no.5
    • /
    • pp.207-214
    • /
    • 2004
  • This paper presents the characteristics of transient and effective impulse impedances for deeply driven grounding electrodes used in soil with high resistivity or in downtown areas. The laboratory test associated with the time domain performance of grounding piles subjected to a lightning stroke current has been carried out using an actual-sized model grounding system. The ground impedances of the deeply driven ground rods and grounding pile under impulse currents showed inductive characteristics, and the effective impulse ground impedance owing to the inductive component is higher than the power frequency ground impedance. Both power frequency ground impedance and effective impulse ground impedance decrease upon increasing the length of the model grounding electrodes. Furthermore, the effective impulse ground impedances of the deeply driven grounding electrodes are significantly amplified in impulse currents with a rapid rise time. The reduction of the power frequency ground impedance is decisive to improve the impulse impedance characteristics of grounding systems.