Minimized Distance of the Current Electrode in the Measurement of Ground Resistance

접지저항 측정에 있어서 전류전극의 최소 이격거리

  • 이상무 (한국전자통신연구원 표준연구센터 기술기준연구팀) ;
  • 강영흥 (군산대학교 전자정보공학부) ;
  • 양준규 (군산대학교 정보통신공학과)
  • Published : 2006.12.31

Abstract

As in the measurement of ground resistance by using the 3 point fall-of-potential method, it is known that the distance of current electrode should be at the point of showing the plateu on the potential curve. But the problem is that it my be practically impossible to meet the condition in actual sites. For solving such a situation, this paper provides the least distance of current electrode according to the analysis for the test-field measurement showing that it is feasible to measure the ground resistance in the two in current electrode distance as the length of driven-rod type electrode and the some district length of mesh electrode.

접지저항을 측정하는데 있어서 전류전극의 이격거리는 일반적으로 접지전극으로부터 전류전극에 이르기까지의 직선 구간상에서의 전압강하의 변화 곡선에 소위 평탄 구간이 존재하도록 이격하는 것으로 알려져 있다. 그러나 이러한 전류전극 이격 기준의 문제점은 그와 같은 조건을 만족하기에는 현실적으로 곤란한 측정 현장이 있다는 것이다. 이러한 문제의 보완을 위하여 본 논문은 실험적 측정 데이터를 활용, 분석하여 전류전극 이격거리의 최소 규격을 제시하였다. 분석 결과에 의하면 봉상접지에 대하여는 봉 길이의 2배 이상을, 메쉬접지에 대하여는 한 변 길이의 2배 이상 이격하여야 함을 알 수 있다.

Keywords

References

  1. IEEE, IEEE Guide for Safety in AC Substation Grounding, IEEE Std 80-2000, Jan. 30, 2000, pp.115-116
  2. IEEE, IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System, IEEE Std 81-1983, Sep. 17, 1981, p.21
  3. IEEE, IEEE Guide for Measurement of Impedance and Safety Characteristics of Large, Extended or interconnected Grounding Systems, IEEE Std 81.2-1991, Dec. 5, 1991, p.6, p.12
  4. F. Dawalibi, D. Mukhedkar, 'Resistance Measurment of Large Grounding Systems', IEEE Transactions on Power Apparatus and Systems, Vol. PAS-98, No.6, 1979.11/12, pp.2348-2354 https://doi.org/10.1109/TPAS.1979.319434