• Title/Summary/Keyword: Conventional grounding impedance

Search Result 22, Processing Time 0.02 seconds

Characteristics of Grounding Impedances of Carbon Compound Grounding Electrodes (탄소혼합물 접지전극의 접지임피던스의 특성)

  • Lee, Kang-Soo;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.5
    • /
    • pp.54-60
    • /
    • 2011
  • This paper presents characteristics of frequency-dependent grounding impedance and transient grounding impedance for the carbon compound grounding electrode used in the installation of computerized electronic equipment and lightning protection system. The frequency-dependent grounding impedances were measured by applying sinusoidal currents in the frequency range from 100 [Hz] to 10[MHz], and the transient grounding impedances were examined by subjecting the impulse current with the front-time between 1~80[${\mu}s$]. As a result, the ground resistance of the carbon compound grounding electrode is less than that of another type grounding electrodes. The transient grounding impedance is relatively low and the conventional grounding impedance is rather lower than the ground resistance. The frequency-dependent grounding impedance of the carbon compound grounding electrode is capacitive and the grounding impedance is decreased with increasing the frequency of injected currents. Therefore in the case that the carbon compound grounding electrode is jointly used with large-scaled grounding electrodes, it is possible to reduce the high frequency grounding impedance of the integrated grounding electrode system.

Analysis for the conventional impedance of counterpoise using EMTP (EMTP를 이용한 매설지선의 규약접지임피던스 해석)

  • Kim, Jong-Ho;Joe, Jeong-Hyeon;Beak, Young-Hwan;Lee, Gang-Su;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2009.10a
    • /
    • pp.47-50
    • /
    • 2009
  • When the lightning currents flow through the ground electrode, the grounding system should be evaluated by the grounding impedance rather than the ground resistance because a grounding system shows the transient impedance characteristic by the inductance of the ground electrode and the capacitance of the soil. The ratio of the peak values of electric potential and currents is the conventional impedance that shows the transient characteristic about impulse currents of the grounding system in a roundabout way. The grounding system having low conventional impedance is a fine grounding system with low electric potential when the lightning currents flow. In this paper the conventional impedance of the counterpoise is calculated by using the distributed parameter circuit model and embodied the distributed parameter circuit model by using the EMTP program The adequacy of the distributed parameter model is examined by comparing the simulated and the measured results. The conventional impedance of the counterpoise is analyzed for first short stroke and subsequent short stroke currents.

  • PDF

Critical Length Estimation of Counterpoise Subjected to Lightning Stroke Currents

  • Lee, Bok-Hee;Yoo, Yang-Woo;Kim, Jong-Ho
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.8
    • /
    • pp.106-113
    • /
    • 2011
  • The conventional grounding impedance of a counterpoise is calculated as a function of the length of the counterpoise by use of the distributed parameter circuit model with an application of the EMTP(Electromagnetic Transient Program). The adequacy of the distributed parameter circuit model is examined and verified by comparison of the simulated and the measured results. The conventional grounding impedance of the counterpoise is analyzed for the first short stroke and subsequent short stroke currents. As a result, the simulated results show that the minimum conventional grounding impedance gives at a specified length of the counterpoise. The shorter the time taken to reach the peak of injected currents, the shorter the length of the counterpoise having the minimum conventional grounding impedance. We also present the critical lengths of the counterpoise for short stroke currents as a function of soil resistivity. Based on these results, it is necessary to compute the length of the counterpoise in a specified soil resistivity which satisfies both the low conventional grounding impedance requirement whilst also providing a suitable ground resistance in order to obtain an economical design and installation of the counterpoise.

Grounding Characteristics Analysis of the Rod-Type Grounding Electrodes used for Electric Distribution Systems (배전계통에 사용되는 봉형 접지전극의 접지 특성 분석)

  • Kim, Kyung-Chul;Jung, Ji-Won
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.25 no.6
    • /
    • pp.49-56
    • /
    • 2011
  • Grounding system insures a reference potential point for electric devices and also provides a low impedance path for fault currents or transient currents in the earth. The ground impedance as function of frequency is necessary for determining its performance since fault currents could contain a wide range of frequencies. In this paper, the grounding resistance, grounding impedance and transient grounding impedance are measured by using 3-point fall-of-potential method in order to analyse grounding characteristics of the copper and concrete rod grounding electrodes. An equivalent transfer function model of the ground impedance and transient grounding impedance are identified from the measured values by using ARMA method and evaluated by comparing the conventional grounding impedance.

Grounding Impedance Behaviors Associated with the Current Injection Point and the Length of Counterpoise (매설지선의 길이와 전류인가점에 따른 접지임피던스특성)

  • Li, Feng;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.6
    • /
    • pp.66-71
    • /
    • 2009
  • This paper presents the grounding impedance behaviors of counterpoise exposed to impulse currents. The transient and conventional grounding impedances of three counterpoises having the length of 10, 30 and 50[m] were measured and analyzed as a function of the injection point of impulse currents. As a result, the trend of the conventional grounding impedances measured as a function of injection of impulse current is similar to the transient grounding impedance of counterpoise. The injection point of impulse current has great influence on the transient grounding impedance characteristics of counterpoise. The transient grounding impedance characteristics in a short time range are strongly dependent on the length of counterpoise. The transient characteristics of grounding impedance of 10[m] counterpoise subjected to the impulse current was capacitive behavior, on the other hand, those of 30[m] and 50[m] counterpoises were inductive behavior. It is found that the grounding conductor should be connected to the central point of counterpoise.

Transient Grounding Impedance Behaviors of Deeply-driven Ground Rods According to the Injection Point of Impulse Currents (임펄스전류의 인가위치에 따른 심매실 봉상 접지전극의 과도접지임피던스 특선)

  • Lee, Su-Bong;Li, Feng;Lee, Seung-Ju;Jeon, Byung-Wook;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.10
    • /
    • pp.62-68
    • /
    • 2008
  • This paper presents the transient and conventional grounding impedance behaviors of deeply-driven ground rods associated with the injection point of impulse currents. The transient grounding impedance strongly depends on the length of deeply-driven ground rod and the rise time and injection point of impulse currents, and the intrinsic inductance of ground rod has a significant affect on the transient grounding impedance of grounding system in fast rise time ranges. The reduction of inductance is decisive to improve the impulse impedance behaviors of deeply-driven ground rods. It is effective that grounding conductor is connected to the top of the ground rod as short as possible.

The transient grounding impedance measurment of large grid grounding electrodes (대규모 그리드 접지전극의 과도접지임피던스의 측정)

  • Jeon, Byung-Wook;Lee, Su-Bong;Li, Feng;Lee, Seung-Ju;Jung, Dong-Cheol;Lee, Bok-Hee
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2008.10a
    • /
    • pp.69-72
    • /
    • 2008
  • This paper presents the transient and conventional grounding impedance behaviors of large grid grounding system associated with the injection point of impulse current The measurement methods consider two possible errors in the grounding-system impedances: (1) ground mutual resistance due to current flow through ground from the ground electrode to be measured to the current auxiliary, (2) ac mutual coupling between the current test lead and the potential test lead The test circuit was set to reduce the error factors. The transient grounding impedance depends on the rise time and injection point of impulse current It is effective that grounding conductor is connected to the center of the large grid grounding system.

  • PDF

Grounding Characteristics Analysis of the Stainless-steel Plate Grounding Electrode for Distribution Poles (배전전주용 스테인리스강판 접지전극의 접지 특성분석)

  • Kim, Kyung-Chul;Lee, Kyu-Jin;Kim, Min-Sung;Jung, Ji-Won
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.8
    • /
    • pp.94-100
    • /
    • 2010
  • Grounding system insures a reference potential point for electric devices and also provides a low impedance path for fault currents or transient currents in the earth. The ground impedance as function of frequency is necessary for determining its performance since fault currents could contain a wide range of frequencies. In this paper, the grounding resistance, grounding impedance and transient grounding impedance are measured by using 3-point fall-of-potential method in order to analyse grounding characteristics of the stainless-steel plate grounding electrode. An equivalent transfer function model of the grounding impedance and transient grounding impedance are identified from the measured values by using ARMA method and evaluated by comparing conventional grounding impedances.

Transient Grounding Impedance Characteristic Analysis of a Copper Rod-type Grounding Electrode Used for Electric Distribution Systems Using MATLAB Program (MATLAB 프로그램을 이용한 배전계통에 사용되는 동봉 접지전극의 과도 접지임피던스 특성 분석)

  • Kim, Kyung-Chul;Oh, Kyung-Hoon;Lee, Kyu-Jin;Shim, Keun-Bo;Choi, Jong-Kee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.9
    • /
    • pp.40-46
    • /
    • 2009
  • Although a ground resistance is a good index of grounding performance for grounding electrodes, it does not reflect the grounding performance during transient state. A copper rod electrode is the most commonly used grounding electrode in electric distribution systems. In this paper, the grounding impedance of copper rods has been measured in frequency raging from 60[Hz] up to 100[kHz] and an equivalent model of the grounding impedance is identified from the measured values. The grounding impedance under study when a typical lightning surge is injected into the grounding system was simulated numerically and graphically through the use of the MATLAB software program.

Simulated Analysis for the Transient Impedance Behaviors of Counterpoises Subjected to the Impulsive Currents (임펄스전류에 의한 매설지선의 과도임피던스특성에 대한 모의해석)

  • Joe, Jeong-Hyeon;Lee, Bok-Hee
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.58 no.10
    • /
    • pp.1861-1868
    • /
    • 2009
  • A ground electrode subjected to lightning surge current shows the transient impedance behaviors. The ground electrode for protection against lightning should be evaluated in view of the transient grounding impedance and conventional grounding impedance, not ground resistance. The transient impedance characteristics of ground electrodes are influenced by the shape of ground electrode and the soil characteristics, as well as the waveform of lightning surge current. In order to propose a simulation method of analyzing the transient impedance characteristics of the grounding system in practical use, this paper suggests a theoretical analysis method of distributed parameter circuit model to simulate the transient impedance characteristics of counterpoise subjected to lightning surge current. EMTP and Matlab programs were employed to compute the transient grounding impedances of three counterpoises with different lengths. As a consequence, the simulated results using the proposed distributed parameter circuit model are in good agreement with the measured results.