• Title/Summary/Keyword: 이복희

Search Result 459, Processing Time 0.025 seconds

Measurement and Analysis of Transient Grounding Resistance with the Pulse Generator (펄스발생기에 의한 과도접지저항의 측정과 분석)

  • Park, J.S.;Yang, J.J.;Lee, K.O.;Lee, B.H.;Lee, B.K.;Ohk, Y.H.
    • Proceedings of the KIEE Conference
    • /
    • 1996.07c
    • /
    • pp.1864-1866
    • /
    • 1996
  • Grounding is the art of making an electrical connection to the earth. In order to protect man, electrical and/or electric equipments from the lightning strokes, all the energy of lightning strokes must be diverted via a safe path to earth. It is essential to the transient grounding resistance against lightning strokes. In this paper, measurements and analyses of grounding surge impedance have been investigated. For measurements of grounding surge impedance the pulse generator was designed and fabricated. The pulse generator has rise time of 22.4 ns and pulse duration of $8\;{\mu}s$. The transient grounding resistance has been measuring by injecting low power and step current between the earthing system under test and a remote reference earth and measuring the potential rise caused by this current. As a result, the transient grounding resistance against lightning surge in the short time domain is much higher than steady state grounding resistance.

  • PDF

A Study on the Analysis of Harmonics on Low-voltage AC Lines (저압 전원선의 고조파 분석)

  • Lee, B.H.;Baek, Y.H.
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1885-1887
    • /
    • 2004
  • This paper presents the aspect and distribution of voltage and current harmonics being made at low voltage power systems. The voltage and current harmonics in power systems supplying various loads were monitored and analyzed. We have examined the results compared to advanced countries' harmonics control standards. As a result, the current harmonics were significantly greater than the voltage harmonics. In particular, the harmonics of currents flowing through loads with power switching electronics was pronounced. Also, the contents of current harmonics of street lamp circuits was about 30%, and it was decreased to 12.3% with the installation of scries reactor. On the whole, The measured results of voltage and current harmonics exceeds the regulation limits recommended by IEEE std 519-1992.

  • PDF

Statistical Characteristics of the Electromagnetic Pulses Radiated from Intracloud Discharges (운방전에 의한 뇌전자장 펄스의 특성)

  • Lee, B.H.;Lee, D.M.;Jeong, D.C.;Lee, S.C.;Ahn, C.H.
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1882-1884
    • /
    • 2004
  • In this paper, the waveform parameters of electromagnetic pulses radiated from intracloud discharges were presented. The zero-crossing times and the full pulse widths of the large bipolar electromagnetic pulses due to intracloud discharges are gradually decreased as the stroke proceeds. Also, the electromagnetic pulses tend to be bipolar, with narrow and fast leader pulses superimposed on the initial half cycle. The mean numbers of leader pulses superimposed on the initial half cycle were 1.61${\pm}$0.74 and 1.75${\pm}$0.73 for the positive and negative polarities, respectively.

  • PDF

Theoretical analysis and measurement of Ground impedance of Ground rods (봉상전극 접지임피던스의 측정과 이론적 분석)

  • Lee, Bok-Hee;Lee, Tae-Hyung;Lee, Su-Bong;Eom, Ju-Hong
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1876-1878
    • /
    • 2004
  • A systematic approach of measurement, modeling and analysis of grounding system impedance is presented. The measurement and analysis system of ground impedance is based on a computer aided technique. The ground impedances of the ground rod are considerably dependent on the frequency. The ground impedance is mainly resistive in the frequency range of 3-20 kHz. At higher frequencies, the reactive components of the ground impedances are no longer negligible and the inductance of the ground rod was found to be the core factor deciding the ground impedance. As a consequence, the equivalent circuit model based on the measured data was proposed, and the calculated results were in approximately agreement with the measured data.

  • PDF

The characteristics of the luminous events caused between the ZnO arrester block and electrode (산화아연(ZnO) 피뢰기 소자와 전극사이에서 발생하는 방전광 특성)

  • Lee, B.H.;Pak, K.Y.;Kang, S.M.
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1869-1871
    • /
    • 2004
  • The primary role of ZnO arresters is to protect transmission and distribution equipments against lightning surges. The extremely nonlinear V-I characteristics of the ZnO arrester obviates the need for isolation gaps and consequently it is continuously connected to line voltage. For this reason, ZnO arresters are degraded with increasing with time in actual power systems. In this work, the characteristics of the luminous events between the ZnO block and electrodes were investigated. As a result, the luminous events were effected by the impulse and the near polarity of the luminous event was intense near the grounded electrode. Also the luminous event may cause the degradation of ZnO arrester block.

  • PDF

Measurement of the Induced Voltages and Magnetic Fields Produced by Multiple Lightning Discharges (뇌방전에 의한 유도전압과 자장의 측정)

  • Lee, B.H.;Cho, S.C.;Lee, W.C.;Shim, E.B.;Woo, J.W.
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1866-1868
    • /
    • 2004
  • This paper deals with the device for measuring the time-varying magnetic fields and induced voltages caused by lightning discharges. The system consists of two loop antennas for the measuring the magnetic flux density and induced voltages caused by the lightning current, an integrator a data acquisition and a personal computer with a software package that was developed for the analysis of the measurements.

  • PDF

Characteristics of lightning impulse breakdowns in inhomogeneous $SF_6$ gas gap (불평등전장에서 $SF_6$ 기체의 뇌임펄스 절연파괴특성)

  • Lee, B.H.;Choi, H.S.;Oh, S.K.;Li, F.
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1921-1923
    • /
    • 2004
  • V-p characteristics and the discharge luminous characteristics in inhomogeneous $SF_6$ gas gap under the positive and negative lightning impulse voltages are presented. The test gap was composed of the plane-to-plane with a needle-shaped protrusion. The applied voltage and the predischarge current were measured by the electric field sensor and the shunt of 50 ${\Omega}$, respectively. The light emission signals were observed by a photomultiplier tube, and a high-speed camera. In a consequence, the dielectric strengths of $SF_6$ gas gap under positive lightning impulse voltages were independent of the gas pressure. In the presence of the positive polarity, the branches of discharge channel were created and the directions of the discharge paths were random. On the other hands, the discharge paths of the negative polarity were more thicker and brighter.

  • PDF

Measurement and Analysis of Magnetic Field Waveform Generated by Operating Fluorescent Lamp (형광등의 사용중에 발생되는 자계파형의 측정과 해석)

  • 이복희;전덕규;길경석
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.8 no.4
    • /
    • pp.22-29
    • /
    • 1994
  • 본 논문에서는 시변자계측정을 위한 센서와 형광등의 점등에 의하여 발생되는 자계의 특성에 대하여 기술하였다. 자계측정계는 동축케이블을 사용한 자기적분형 자계센서와 증폭기, 적분기로 구성하였으며 교정실험 결과, 주파수대역은 약 40Hz∼100kHz이었다. 수동점등식, 고주파점등식과 글로우점등식 등 여러 가지 점등방식의 형광등에 의하여 발생되는 자계의 파형을 측정하고, 측정된 자계의 주파수성분을 고속푸리에변환(fast Fourier transformation: FFT)기법으로 해석하였다. 형광등의 점등중에 발생되는 자계성분은 주로 기수고주파 성분이 많이 포함되어 있으며, 인덕션칵에 의하여 점등순간에는 급변성의 과도성분이 나타났다. 전자회로나 제어기기의 보호를 위한 자계차폐장치를 설계할 때에는 반드시 자계의 기수고조파성분을 고려하여야 됨이 확인되었다.

  • PDF

Numerical Calculation of Longitudinal Current Distribution in Grounding Electrode for Analyzing the Grounding Impedance (접지임피던스 분석을 위한 접지전극의 전류분포 수치계산)

  • Cho, Sung-Chul;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.1
    • /
    • pp.46-52
    • /
    • 2013
  • The current distribution passing through grounding electrode is required for calculating an impedance of grounding electrode using the electromagnetic field model. In this paper the numerical calculation for currents passing through a grounding electrode as a function of frequency was given. The proposed approach is based on the wire antenna model(AM) in the frequency domain. The Pocklington's equation driven from the wire antenna theory was numerically calculated by the Galerkin's method. The triangle function was applied to both the basis function and the weighting function. The current distribution of a horizontal ground electrode was simulated in MATLAB. Also these results were compared with the data obtained from the CDEGS HIFREQ calculation.