• Title/Summary/Keyword: 섬락

Search Result 84, Processing Time 0.031 seconds

Switching Surge Flashover Characteristics of 765 kV Transmission Towers (765 kV 송전철탑 개폐섬락 특성)

  • Shim, J.W.;Chang, S.C.;Kwak, J.S.;Kim, J.B.
    • Proceedings of the KIEE Conference
    • /
    • 1996.11a
    • /
    • pp.276-278
    • /
    • 1996
  • The breakdown Process in large gaps is greatly influenced by the gap geometry. Therefor full scale test are essential for the economical and reliable air insulation design. For switching surge design of 765 kV double circuit transmission line KEPRI is carrying the verifying tests using impulse voltage generator at Gochang test site. In this paper, the intermediate results of verifying tests are presented and the switching surge design criteria of 765 kV transmission tower flashover paths are discussed.

  • PDF

A Flashover Characteristics Due to Flames (화염으로 인한 전기적 섬락특성 변화)

  • Sohn, H.K.;Lee, H.K.;Han, H.J.;Park, I.P.;Oh, H.H.;Min, B.W.
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.703-704
    • /
    • 2007
  • Most of the transmission lines in Korea pass through a mountains. The forest fire occurred in around the transmission lines make an accident such as flashover and faults in the power transmission lines. In spite of that risk, there are no research on the flashover characteristics by fires in electric discharge engineering in our country. This paper was mentioned about the relation between the flame and flashover characteristics. We were carried out simple test by using artificial flame generator and rod-plane or conductor-plane gaps. And we were summarized test results.

  • PDF

Series-Gap Characteristics of Transmission Line Arrester with Switching and Lightning Impulse Flashover Test (개폐서지 및 뇌충격 섬락시험에 따른 송전 피뢰기의 직렬공극 특성)

  • Cho, Han-Goo;Yoo, Dae-Hoon
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.11a
    • /
    • pp.484-485
    • /
    • 2007
  • This paper describes the series-gap characteristics of transmission line arrester with switching and lightning impulse flashover test. The transmission line arrester exhibited external gap because it is must not flashover with switching impulse on the other hand it is must flashover with lightning impulse. In accordance, minimum and maximum length of series-gap was determinated with these tests. As gap length is increased flashover voltage was increased in the range of 315.4 kV~496.3 kV and negative polarity exhibited a high voltage. As a result, It was thought tat the series-gap length of transmission line arrester exhibited in the range of 580 mm~1100 mm.

  • PDF

A Study on the Flashover Properties of Insulators with Artifitial Pollution (오손조건에 따른 애자의 섬락 특성에 관한 연구)

  • 송치훈;조성인;국연호;남궁도;한상옥
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2000.07a
    • /
    • pp.679-682
    • /
    • 2000
  • This paper present the result of the flashover properties of inulators due to artifitial pollution. For this study, a mini fog chamber has been fabricated with transparent acryl which has the merit in observasion and electrical insulation. All the experiment was carried in mini fog chamber. Though non-souble contaminant do not distribute on the electric conductivity of contaminant and contaminated insulator, that influence on the flashover characteristics of insulators. with the result, we assume phenomenon caused with the hygroscopic property of non-soluble contaminant.

  • PDF

Multi-aging Test for Estimating Long Time Performance of Polymer Insulators for Transmission line (송전용 폴리마 런자의 장기성능을 위한 복합열화시험)

  • 조한구;한세원;이운용;윤문수
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 1999.11a
    • /
    • pp.640-643
    • /
    • 1999
  • This paper presents the results of multi-stress chamber experiments done to examine the tracking and erosion performance of polymer insulator. Multi-stress testing is able to demonstrate deficiencies of polymer insulator materials and designs, including the nature of interfaces in insulation design. Therefore, multi-stress testing is believed to a suitable test for evaluating the aging performance of polymer insulator designs. We have nvestigated IEC 61109 Annex C for estimating long time performance of polymer insulator.

  • PDF

Influence of Combustion Flame on Breakdown Characteristics of Vertical-Model Power Lines (수직배열 모델 전력선의 절연파괴 특성에 미치는 화염의 영향)

  • Park, Kwang-Seo;Kim, In-Sik
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.4
    • /
    • pp.85-92
    • /
    • 2008
  • Occurring forest fire or burning bushes beneath overhead transmission lines have caused breakdown disturbances of the system in many countries. In this study, experiments for flashover characteristics in the simulated condition of vertical power lines were conducted so as to investigate the reduction in insulation strength caused by combustion flame. As the results of an experimental investigation, it is demonstrated that flame can reduce breakdown voltages of the model lines according to height(h) of flame. The breakdown voltages were decreased with decreasing the height(h) of flame it can be seen that the average reduction of flashover levels, in comparison with the no-flame case, are 46.2[%] for h=9[cm] and 62.5[%] for h=3[cm] when ac voltage is applied.

STUDY ON SAFETY OF SPIRAL INSULATING & FLEXIBLE JUMPER PROTECTOR COVER (소용돌이형 점퍼선방호관의 안전성에 관한 연구)

  • Ji, Yong-Heon;Choi, Myeong-Ho;Lee, Jae-Young;Kim, Dong-Sik;Kwak, Sang-Young;Kim, Young-Chan;Kim, Nam-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 2008.04b
    • /
    • pp.211-213
    • /
    • 2008
  • 배전선로는 항상 각종 공작물과 아주 가까운 상태에서 존재하고 있어 배전선로 근접 작업 시 전력선에 근접으로 인한 섬락 또는 접촉으로 작업원이 감전 재해를 입을 수 있으며 또는 비, 바람, 조류 등에 의한 이물 접촉으로 설비 고장을 유발 시킬 수 있다. 이러한 감전재해 및 설비고장을 예방하기 위하여 22.9kV-y 전력선의 직선부분에 사용할 수 있는 직선형 방호관을 개발하여 건설현장 주변의 전력선에 방호조치 함으로서 전력선 근접 작업 시 작업종사자의 안전 확보에 이바지함은 물론 정전사고방지에도 크게 기여하여 왔다. 그러나 22.9kV-y 배전선로의 점퍼선부분과 변압기의 인상선 등 곡선으로 되었거나 구불구불한 형상으로 된 부위는 직선형 방호관으로는 방호조치가 불가능하여 산업안전보건법이 정한 산업안전기준에 관한 규칙 제327조 제2호에 의한 방호조치를 취하지 않고 근접작업이 진행되어 감전재해와 정전사고가 발생되어 왔었다. 한전에서 협력업체와 공동으로 연구개발한 소용돌이형 점퍼선방호관을 그동안 방호조치를 취하지 못한 점퍼선이나 구불구불한 전력선부위에 방호조치를 함으로서 감전재해의 예방과 정전사고 발생을 획기적으로 감소시킬 것으로 기대된다.

  • PDF

Leakage Current Pulse analysis of Porcelain Insulator at 154kV Transmission Line by use of Pulse Current Method (Pulse current method를 이용한 154kV급 송전용 자기 애자의 누설 전류의 펄스 분석)

  • Lee, Seul-Ki;Ryu, Cheol-Hwi;Lee, Bang-Wook;Choi, Gwang-Beom;Koo, Ja-Yoon
    • Proceedings of the KIEE Conference
    • /
    • 2008.05a
    • /
    • pp.129-130
    • /
    • 2008
  • 송전선로에 설취된 애자들은 지속적인 전기적 기계적 스트레스에 노출되어 있기 때문에 여러 환경적 요인으로 인해 애자 표변의 열화가 가속된다. 이와 같은 애자의 표면 열화는 dryband를 형성하게 되고 지속적인 애자 표면상의 dryband와 누설 전류 증가의 상호 작용은 애자의 섬락를 일으키는 원인이 된다.[1][2] 이러한 연구의 결과 고전압용 애자로 유입되는 누설 전류는 애자 열화의 정도를 평가할 수 있는 매우 중요한 parameter임을 알 수 있다. 따라서 고전압용 애자의 누설전류를 분석하고 취득하여 애자의 열화 평가 및 이로 인해 발생할 수 있는 결함 애자의 검출에 대한 연구가 절실히 요구되고 있다, 본 논문에서는 고전압용 애자 중 자기애자의 누설전류 특성을 조사하기 위해 자체 제작한 실험 챔버, AC 내전압기, 전류센서r, 오실로스코프, PC등으로 구성된 실험 시스템을 구축하였고, 데이터 분석을 위한 S/W로서 LabView를 사용하였다. 그에 따른 실험 결과로서 정상 애자련과 결함 애자를 포함한 애자련의 누설전류 데이터를 취득하여 본 연구에서 제시한 알고리즘을 통해 분석함으로써 정상 애자 내의 결함 애자 포함 여부를 판별할 수 있었다.

  • PDF

Influence of Conducting Particle on the Breakdown Phenomena of $SF_6$ gas in Gas Insulated System ([$SF_6$] 가스 절연기기내에 도전성 금속이물 존재시 섬락전압에 미치는 영향)

  • Lee, B.W.;Ham, G.H.;Kim, I.S.;Koo, J.Y.
    • Proceedings of the KIEE Conference
    • /
    • 1998.07e
    • /
    • pp.1687-1689
    • /
    • 1998
  • In this work, the behaviours of conducting wire type particles within the coaxial electrode gap energized with high ac voltage have been systematically investigated using charge simulation method. For this, spheroidal charge is adopted as a image charge for the CSM analysis in order to calculate the acquired charge of the particles which are erected on the surface of the outer electrode. For this purpose, the effects of the lengths and diameters of Cu, Al particles in gas insulated system have been studied by a numerical computation and particle lifting voltage, lifting field, breakdown voltage, acquired charge and travelling distance have been considered. From this, we understand that the particle behaviours have different characteristics according to the particle lengths and diameters. And a possible countermeasure, based on the proposed simulation, has been provided with a view to estimating the flashover voltage of $SF_6$ gas under the 1 atm.

  • PDF

Surface and Electrical Properties on EPDM/Silicone Composite Insulator (EPDM/Silicone 복합 절연체의 표면특성과 전기적 특성)

  • Shim, Dae-Sup;Park, Sung-Gyun;Kim, Bum-Jin
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2001.05c
    • /
    • pp.92-95
    • /
    • 2001
  • 고분자 복합체 절연재료는 porcelain 이나 glass 같은 세라믹 소재의 재료와 비교하여 옥외사용 시간의 관점에서 더 뛰어난 특정을 발휘한다. 그러나 노화되었을 때, 이들 옥외용 절연재료의 성질은 발수성이나 흡수성등과 같은 절연재료의 표면특성에 의해 변화한다. 이러한 표면특성의 변화는 누설전류에 의한 트래킹 (tracking), 침식 (erosion) 및 섬락현상(flashover) 등의 유전체 파괴에 이르게 한다. 본 연구에서는 고분자 복합체 절연재료로 널리 이용되고 있는 EPDM의 발수특성을 향상시키기 위해 기존에 이용되던 무기물 첨가제인 alumina hydrate(ATH)이외에 발수성이 뛰어난 실리콘 고무를 상용화제를 이용하여 블렌드하고, 각종 유기 첨가제 및 무기물 보강제를 이용하여 EPDM/Silicone 복합체를 제조하였다. EPDM/Silicone 복합체의 인장강도 및 유전강도는 실리콘의 함량이 증가할수록 낮아졌으며, 촉진 노화시험을 실시한 결과 $120^{\circ}C$까지 인장강도 및 신율을 유지하였다. 유전강도의 측정결과 복합체의 접촉각과 표면에너지 측정결과 Silicone 고무의 함량이 증가할수록 접촉각은 증가하고, 표면에너지는 낮아졌다. 경사평판법에의한 내트래킹성 측정결과 실리콘 함량이 증가할수록 내트래킹성은 우수하였으며, 실리콘 함량이 30%인 복합체에서는 트래킹 및 침식이 진행되지 않았다.

  • PDF