• 제목/요약/키워드: 배전피뢰기

검색결과 67건 처리시간 0.025초

복합 가속열화를 통한 배전용 고분자 피뢰기의 장기 열화특성 예측 (Longterm Aging Characteristics of Distribution Polymer Housed Surge Arresters by Multistress Accelerated Aging)

  • 김주용;권태호;박철배;김준일
    • 한국전기전자재료학회논문지
    • /
    • 제20권8호
    • /
    • pp.691-696
    • /
    • 2007
  • In this study accelerated aging test equipment was developed to simulate domestic weather condition for accelerated aging test of polymer housed distribution surge arresters. Polymer arresters were aged for 3,000 hours by this test equipment and chemical and electrical characteristics analysis of surge arresters were conducted after aging test. In addition, performance assessment of outdoor installed arresters for 3 years was conducted to compare aging effect between accelerated aging test and natural aging. Through this experiment it is verified that the capability of the proposed aging test for simulating natural aging and the housing material and disconnector of domestic polymer arresters can be deteriorated by the long time field operation.

2회선 배전계통에서 가공지선 접지 및 피뢰기 설치환경에 따른 뇌과전압 해석 (Analysis of Lightning Overvoltage with Earth of Overhead Grounding Wire and Installation Types of Arrester in Double Circuits Distribution Systems)

  • 정채균;김상국;이종범;정영호
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2003년도 하계학술대회 논문집 A
    • /
    • pp.497-499
    • /
    • 2003
  • This paper analyses the lightning overvoltage with earth of grounding wire and installation types of arresters in double circuits distribution systems. First, the model for analysis is selected severer case between upper line and lower line when the direct lightning surge strikes on the overhead grounding wire. The lightning overvoltage is variously calculated with earth distance between overhead grounding wires. This paper also analyses the effect of the installation distance between arrestors and the earth resistance of overhead grounding wire. From these results, authors examine the rationality of BIL that is applied in distribution system.

  • PDF

배전용 피뢰기의 가속열화시험 (Accelerating aging test of distribution lightning arresters)

  • 김주용;송일근;김찬영;이병성;문재덕
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 하계학술대회 논문집
    • /
    • pp.596-598
    • /
    • 2000
  • This paper presents a new accelerating aging test facility for distribution lightning arresters. Aging parameters of lightning arrester are moisture ingress, electrical stress and surge absorption and so on. In this system, we applied 13.2kV to 6 samples and controled temperature and humidity of chamber and measured leakage currents of the all samples. Also we developed accelerating aging cycle which consists of -35$^{\circ}C$∼90$^{\circ}C$ temperature and 40%∼90% humidity. Through the aging test we found out the leakage current of aged sample increases rapidly according to the temperature rising. Hereafter we can determine the replacement guide of leakage current for field operating arresters and condition assessment of aged samples through this aging test.

  • PDF

배전용 피뢰기의 인공오손에 의한 누설전류의 고조파 분석 (Harmonics Analysis of Leakage Current due to Artificial Contamination of Distribution Arresters)

  • 박재준
    • 전기학회논문지
    • /
    • 제61권9호
    • /
    • pp.1306-1313
    • /
    • 2012
  • This paper reports the contamination performance of two distribution arresters (new and used ones) tested under three different contaminant conditions - clean fog, ESDD (equivalent salt deposit density) level (A, B, C, and D), and kaolin contamination conditions, and their leakage current, total leakage current, and component of the resistive leakage current were measured in order to diagnose arrester deterioration. The 3rd harmonics was larger than 5th and 7th ones for the arrester under the clean fog, and as the ESDD contamination level was applied, 5th one became relatively larger than 3rd one. Therefore, these results indicated that the resistive leakage current could be used for the diagnosis of the arresters.

배전급 저압피뢰기 임펄스 특성 연구 (The Study on the Impulse Characteristic of Secondary Arresters in Power Distribution System)

  • 강문호;박상만;박영근;장상옥;이흥호
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 춘계학술대회 논문집
    • /
    • pp.295-297
    • /
    • 2004
  • The overvoltage generated by the lightning strokes has been doing considerable damage to the distribution network as well as the consumer facility until now. Because most of the lightning strokes are accompanied by a storm, the aftermath of damage to the consumer is so serious. Therefore it is very important to survey the optimal operation plan by the field test of distribution lightning facilities. In this paper we have accomplished the field test to verify the impulse characteristic of Secondary Arrester(SA), and analyzed the effect of the SA in power distribution system.

  • PDF

배전용 폴리머 피뢰기의 전기적 특성시험 (Electrical Characteristics Test of Distribution Polymer Lightening Arresters)

  • 권태호;이병성;송일근;김동명;윤태상;정상봉
    • 한국조명전기설비학회:학술대회논문집
    • /
    • 한국조명전기설비학회 2004년도 춘계학술대회 논문집
    • /
    • pp.546-549
    • /
    • 2004
  • This paper describes the electrical characteristics of the polymer lightning arresters(L.As) used to protect distribution lines and power facilities from surge. For the relative comparison, the characteristics assessment was done for 2 states of L.As before and after water immersion treatment. The L.As for the comparative test were immersed with water of $95[^{\circ}C]$ considered a severe condition. After the immersion treatment, the assessment was carried out for material analyses in chemical structure(FTIR : fourier transform infrared spectrophotometer). Electrical performance measured insulation resistance measurement, leakage current measurement, critical operation voltage measurement etc.. In addition to, the results were compared with those for the L.As deteriorated in the field. Thus, the accelerative deterioration degree of polymer materials by immersion treatment was evaluated, by which the structural defects of the polymer L.As could be inferred.

  • PDF

배전급 피뢰기의 신뢰성 평가에 관한 기술 동향 (A Technical Trend on New Distribution Class Arrester Ground Lead Disconnector Design)

  • 김선빈;김인희;홍현욱;오용;황종선;최용성;이경섭
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2007년도 제38회 하계학술대회
    • /
    • pp.1980-1981
    • /
    • 2007
  • This paper introduces performance characteristics of existing distribution class arrester ground lead disconnecting devices. The paper also introduces a new distribution class ground lead disconnector design that not only extends the claimable detonation range well below the 20 amps specified in industry standards, but is very durable when exposed to severe arrester durability tests. Finally, this paper shows how this next generation disconnector interacts with the connected arrester to improve the overvoltage withstand capability of the arrester assembly.

  • PDF

현장 고장난 배전용 피뢰기의 특성분석 (Characteristic Analysis of Distribution Lighten ins Arrester Failed in the Field)

  • 김찬영;김주용;송일근;이병성;한재홍;윤태상
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 하계학술대회 논문집
    • /
    • pp.687-690
    • /
    • 2000
  • This paper provides the result of the analysis of the lightening arresters which were disconnected from the power line due to the overvoltage having high current. The effect of thermal runaway on the microstructures of lightening arrester's block was intensively investigated. The chance of the microstructures of the blocks was limited only on the breakdown paths and near them. Also even though a disconnector was disconnected from the arrester, some of the lightening arrester were showed normal characteristics.

  • PDF

열화정도에 따른 배전용 피뢰기의 열화특성 분석 (Analysis of degradation of distribution lightning arresters as degradation degree)

  • 장동욱;박동배;박영국;이용희;강성화;임기조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2000년도 하계학술대회 논문집
    • /
    • pp.140-143
    • /
    • 2000
  • The primary function of ZnO lightning arrester is to protect transmission and distribution equipment from overvoltages and to absorb electrical energy resulting from lightning or switching surges and form temporary overvoltage. However, ZnO lightning arrester are known to exhibit an increases in resistive current with time, the rate of increase being exacerbated with increasing applied voltage and ambient temperature. So, it is important to the leakage current measurement of ZnO lightning arrester. In addition, since the resistive leakage current caused by deterioration of ZnO lightning arrester mainly caused an increase of the third harmonic component, thereby it is possible the arrester degradation diagnosis by measuring the third harmonic component in the total leakage current. The leakage current and third harmonic component are measured and used to investigate the degradation diagnosis of ZnO element of arrester. Also the SEM photography is used to investigate the change of crystal structure of ZnO element with degradation.

  • PDF

RF Sputtering으로 제작한 $SiO_2 $$SiO_2/TiN$ 박막의 R-V 특성 (The R-V Characteristics of $SiO_2 $ & $SiO_2/TiN$ Thin Film Fabricated by RF Sputtering)

  • 김창석;하충기;김병인
    • 한국전기전자재료학회논문지
    • /
    • 제11권10호
    • /
    • pp.826-832
    • /
    • 1998
  • In this study the thin films with the structure of Si+SiO$_2$+TiN are made by RF supttering method. TiN, which has small diffusion coefficient and low resistivity, is evaporated between SiO$_2$ and Al layers. It investigates the V-R characteristics depending on the thickness of SiO$_2$ which is used as insulation layer and researches its effects on voltage stability of thin film and varistor. These films show very small resistance valus in negative(-) voltage and large and large value in positive voltage band, and with the increase of voltage, resistance value is rapidly reduced and the satisfactory characteristic of varistor is shown at +1[V]. It is found that resistance value of TiN thin film is small and also TiN thin film has more current than the thin film which is not evaporated by TiN thin film. When Al electrode is evaporated of SiO$_2$ thin film, spiking occurs, but the spiking can be prevented with evaporation of TiN between SiO$_2$ and Al layers and this thin films in made easily because of its good attachment. With the increase of voltage, the resistance is changed into non-linear pattern and the bidirectional varistor characteristic is shown and then its theory can be verified by this experiment. Accordingly, when TiN is evaporated of Si Wafer(n-100), it obtains better voltage-resistance than thin film which is not evaporated and also when varistor character is used electrically to automatic control element such as elimination of flame, power distribution arrestor and constant voltage compensation, satisfactory reproducibilities are expected.