Standard weather data for Seoul has been developed for use in computer calculations for energy requirements, and the 8760 sequential hourly values for seven weather elements have been placed in magnetic tape and cards. Applying the method determining average month, developed by Japanese Society of Heating, Air-Conditioning and Sanitary Engineers, the standard year data have been selected from the monthly average values for three weather elements during the 10year period of 1971 through 1980. The followings are obtained. 1. The Test Reference Year, consisting of 12 months chosen from different calendar years, has been determined, and TRY tape which contains seven weather elements has been prepared. 2. The Typical Weather Year, which means a year close to the average value, is the year of 1978 during the above 10 year period. 3. During the period, Winter Season needs the maximum heating load is from Dec. 1976 to Mar. 1977 and Summer Season needs the maximum cool ins load is from Jun. to Sep, 1978.