지하주차장 공기환경 개선을 위한 이오나이저의 적용효과 검토

Air Cleaning Performance of an Ionizer for Underground Parking Facilities

  • 투고 : 2012.08.16
  • 발행 : 2012.11.25

초록

The main objective of this study was to verify a possibility of indoor air environment enhancement via actual operation of ionizer device. Two pollutants, benzene and toluene, were used as indicators for evaluating the air cleaning performance of ionizers. The test results show that negative air ions may provide the air cleaning effect which can be acquired by supplying 0.058-0.100($m^3/hr$), 0.035-0.070($m^3/hr$) ventilation. Another indicator of this test result, air cleaning factor(ACF) was also indicated that the impact of negative air ions is consistently maintained during the ionizer operation. In addition, according to experimental results, it was also found that removal efficiency of benzene was 2.1 times higher than that of toluene. From this research and existing literature, one can conclude that additional indoor air quality improvement can be expected by applying ionizers in ventilation system for underground parking facilities.

키워드

과제정보

연구 과제 주관 기관 : 한국연구재단, 정보통신산업진흥원

참고문헌

  1. 박동일 (2009), Lenard Effect Water Catch 환기시스템 적용에 관한 연구, 경원대학교 환경대학원 석사논문
  2. 이진희, 윤평섭 (2003), 실내조경식물의 음이온 방출효과를 이용한 실내오염제거 기작과 효율, 한국식물.인간.환경학회지, 6(4) 81-92.
  3. 한충수, 강훈, 이해철, 최태섭 (2004), 음이온환경이 인체에 미치는 영향, 한일원적외선 심포지움 학술발표자료
  4. Angus Shiue, Shih-Cheng Hu, Mao-Lin Tu (2011), Particles Removal by Negative ionic Air Purifier in Cleanroom, Aerosol and Air Quality Research, 11: 179-186.
  5. Byung Uk Lee, Mikhail Yermakov, Sergey A. Grinshpun (2004), Removal of fine and ultrafine particles from indoor air environments by the unipolar ion emission, Atmospheric Environment 38, 4815-4823. https://doi.org/10.1016/j.atmosenv.2004.06.010
  6. Charles J. Weschler, Helen C. Shields (2004), Potential reactions among indoor pollutants, Atmospheric Environment Vol.31, No.21, pp 3487-3495.
  7. Chen-Fa Wu, Chun-Hsien Lai, Hone-Jay Chu, Wen-Huang Lin (2011), Evaluating and Mapping of Spatial Air Ion Quality Patterns in a Residential Garden Using a Geistatistic Method, Int J. Environ. Res. Public Health, 8, 2304-2319. https://doi.org/10.3390/ijerph8062304
  8. Chih Cheng Wu, Grace W.M. Lee (2004), Oxidation of volatile organic compounds by negative air ions, Atmospheric Environment 38, 6278-6295.
  9. Chih Cheng Wu, Grace W.M. Lee, Pojen Cheng, Shinhao Yang, Kuo Pin Yu (2006), Effect of wall surface materials on deposition of particles with the aid of negative air ions, Aerosol Scienc 37, 616-630. https://doi.org/10.1016/j.jaerosci.2005.05.018
  10. J.L. Liu, T.C.W. Tung, J. Burnett (2001), Quantification of dust removal and ozone emission of ionizer air cleaners by chamber testing, Journal of Electrostatics 51-52, 20-24 https://doi.org/10.1016/S0304-3886(01)00118-8
  11. K. Charles, R.J Magee, D. Won, E. Lusztyk (2005), Indoor Air Quality Guidelines and Standards, National Research Council Canada. Final Report5.1-CMEIAQ-II: Consortium for Material Emission and IAQ Modelling II.
  12. Karlberg, A., Magnusson, K. and Nilsson, U (1992) Air oxidation of d-limonene (the citrus solvent) creates potential allergens. Contact Dermatitis 26, 332-340. https://doi.org/10.1111/j.1600-0536.1992.tb00129.x
  13. Koichi Hirota, Teruyuki Hakoda, Hidehiko Arai, Shoji Hashimoto (2002), Electron-beam decomposition of vaporized VOCs in air, Radiation Physics and Chemistry 65 415-421. https://doi.org/10.1016/S0969-806X(02)00353-5
  14. M Bohgard, P. Eklund (1998), Effect of an ionizer on sub-micron particles in indoor air, J. Aerosol Sci. Vol. 29, Suppl. 1, pp. S1313-S1314. https://doi.org/10.1016/S0021-8502(98)90839-4
  15. M. Joshi, B.K. Sapra, A. Khan, P. Kothalkar, Y.S. Mayya (2010), Thoron (220Rn) decay products removal in poorly ventilated environments using unipolar ionizers: Dosimetric implications, Science of the Total Environment 408, 5701-5706. https://doi.org/10.1016/j.scitotenv.2010.08.011
  16. Neil E. Klepeis, William C. Nelson, Wayne R. Ott, John P. Robinson, Andy M. Tsang, Paul Switzer, Joseph V. Behar, Stephen C. Hern, William H. Engelmann (2001), The National human activity pattern survey (NHAPS): A resource for assessing exposure to environmental pollutants, Journal of Exposure Analysis and Environmental Epidemiology 11, 231-252. https://doi.org/10.1038/sj.jea.7500165
  17. S.A. Grinshpun, G. Mainelis, M. Trunov, A. Adhikari, T. Reponen, K. Willeke (2005), Evaluation of ionic air purifiers for reducing aerosol exposure in confined indoor spaces, Indoor Air 15: 235-245. https://doi.org/10.1111/j.1600-0668.2005.00364.x
  18. Stacy L. Daniels (2001), Applications of Air Ionization for Control of VOCs and PMx, Paper#918, in Proc.94th Annu. Conf. Exhibition Air and Waste Management Assoc., Orlando, FL, June 24-28.
  19. Stacy L. Daniels (2002), "On the Ionization of Air for Removal of Noxious Effluvia"(Air Ionization of Indoor Environments for Control of Volatile and Particulate Contaminants With Nonthermal Plasmas Generated by Dielectric-Barrier Discharge), IEEE TRANSACTIONS ON PLASMA SCIENCE, VOL. 30, NO. 4, AUGUST.
  20. Zygmunt Grabarczyk (2001), Effectiveness of indoor air cleaning with corona ionizers, Journal of Electrostatics 51-52, 278-283. https://doi.org/10.1016/S0304-3886(01)00058-4