• Title/Summary/Keyword: lightning surge current

Search Result 119, Processing Time 0.025 seconds

Frequency Dependance of Ground Impedances of the Counterpoises (매설지선 접지임피던스의 주파수 의존성)

  • Choi, Young-Chul;Choi, Jong-Hyuk;Kim, Dong-Kyu;Lee, Gyu-Sun;Yang, Soon-Man;Lee, Su-Bong;Lee, Bok-Hee;Ahn, Chang-Hwan
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.1489_1490
    • /
    • 2009
  • Ground impedance is changed according to frequency of the current injected into the grounding system. Because the lightning surge gives a broad frequency spectrum from some ten Hz to a few MHz, frequency dependance of ground impedance must be evaluated. In this paper, we have constructed 10m, 30m, 50m counterpoise and evaluated frequency dependance of ground impedance. Also we have evaluated frequency dependance of ground impedance according to current injection point. As a result, long counterpoises have low ground resistance, but ground impedances of those are significantly increased in the range of high frequency. In the case that currents are injected into the center of counterpoise, the ground impedance is most lower than any other injection point. Also, additory ground rod of 1.8m long affect ground impedance decrease.

  • PDF

Evaluation of Electrical Characteristics of Metal Oxide Varistors for Surge Arresters (초고압용 피뢰기 산화아연소자의 전기적 특성 평가)

  • Cho, Han-Goo;Yoon, Han-Soo;Kim, Suk-Soo;Han, Se-won
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2005.05b
    • /
    • pp.46-49
    • /
    • 2005
  • This paper presents the electrical characteristics of metal oxide varistors for lightning surge arresters. ZnO varistors were fabricated with typical ceramic production methods and two types of varistors were also prepared to be compared. The nominal discharge current and line discharge class of those varistors are $10kA(8/20{\mu}s)$ and class 3, respectively. The diameter of varistors manufactured and prepared were in the range of 61.6~65.0mm and the thickness of those were in the range of 27~42.52mm. The reference and residual voltage were tested and reference and residual voltage per 1mm and the ratio of reference and residual voltage were calculated. The reference voltage per 1mm of varistors manufactured was about 175V/mm but that of A's and B's varistors was nearly 200V/mm. The residual voltage exhibited the same trends as the reference voltage, so the reference and residual voltage per 1mm of domestic varistors should be increased. According to the results of tests, it is thought that if the reference and residual voltage per 1mm were increased to 200V/mm and 330V/mm, domestic ZnO varistors would be possible to apply to the station class arresters in the near future.

  • PDF

Computation of Critical Length for Linear Grounding Electrodes (직선형 접지전극의 임계길이의 산정)

  • Kim, Ki-Bok;Lee, Bok-Hee;Joe, Jeong-Hyeon
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.9
    • /
    • pp.67-74
    • /
    • 2009
  • For the surge currents like lightning currents containing high frequency components and the abnormal currents having high frequencies which cause the EMI(Electromagnetic interference) problems for the electronic devices and communication instruments, the linear grounding electrodes have the significantly composite impedance characteristics which are dependent on the frequency of the applied current. The impedance of a grounding electrode is not lowered by expanding the dimension of the grounding electrode, and the length of grounding electrode having the minimum value of the grounding impedance for each condition of frequency and soil characteristics is existent, and it is defined as Critical length. In this paper, the critical lengths for the vertically and horizontally-buried grounding electrodes are calculated by using the distributed parameter circuit model. The propriety of the simulations has been confirmed by comparing the simulated results with the measured results.

Transient Ground Impedances According to Shapes of Grounding Electrodes (접지전극의 형상에 따른 과도접지임피던스)

  • Lee, Bok-Hee;Lee, Su-Bong;Lee, Tae-Hyung;Jung, Hyun-Uk;Jeong, Dong-Cheol
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.20 no.1
    • /
    • pp.65-70
    • /
    • 2006
  • This paper presents the transient behaviors of grounding system impedance against lightning impulse currents. The dynamic characteristics of the deeply driven ground rod and grounding grid subjected to the impulse current were investigated. The transient ground impedance strongly depends on the configuration and size of grounding electrodes and the shapes of impulse currents, and the inductance of grounding electrodes has a significant affect on the transient ground impedance of grounding system Also, the deeply-driven ground rod was effective to reduce the transient ground impedance in time domain of miceroseconds.

Analysis of the Ground Impedance of Ground Grids Combined with the Carbon Ground Electrodes (탄소접지극이 병설된 접지그리드의 접지임피던스의 해석)

  • Lee, Bok-Hee;Um, Sang-Hyun;Kim, You-Ha;Lee, Kang-Soo;Jeon, Byung-Wook;Choi, Jong-Hyuk
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.27 no.3
    • /
    • pp.36-42
    • /
    • 2013
  • This paper deals with the frequency-dependent ground impedance of ground grids combined with the carbon ground electrodes. Ground grids are generally valid for multipurpose grounding systems as well as lightning protection systems. The carbon ground electrodes may be supplementarily used to reduce the high frequency ground impedance and to improve the transient response to surge currents. The frequency-dependent ground impedances of ground grids combined with or without the carbon ground electrodes were measured and their simulations with due regard to frequency-dependent soil resistivity were implemented by using EMTP program and Matlab modeling. As a consequence, the ground impedance of ground grids combined with the carbon ground electrodes is significantly reduced when the test current is injected at the terminal of the carbon ground electrode. The measured and simulated data for the test ground grids fairly agree with each other. It was found that the proposed method of simulating the frequency-dependent ground impedance is distinguished. The simulation techniques of predicting accurately the ground impedances without actual measurements can be used in the design of grounding systems based on ground grids and the carbon ground electrodes.

Transient Impedance Characteristics of Grounding Rods (봉상접지극의 과도임피던스 특성)

  • 김일권;송재용;길경석;권장우
    • Journal of the Korea Institute of Information and Communication Engineering
    • /
    • v.5 no.1
    • /
    • pp.133-143
    • /
    • 2001
  • This paper describes the correlation of the transient impedance and its parameters with the stationary resistance of a grounding system to a square pulse current and a lightning impulse current. In the experiment, the grounding system consists of a single grounding rod$(\Psi10[mm], 1[m])$and/or a triple-grounding rods of equilateral triangles with 5[m] spacing for operation. To analyze the transient impedance characteristics of the grounding system, a pulse generator which can produce square wave of a 30[ns] rise-time and a $20[\mus] $pulse duration is designed and fabricated. The injected content in the grounding system and the developed potential were recorded, and the time variation of the transient impedance were calculated as the ratio of the potential rising to the injected current at each time. The transient impedance and the effective surge impedance Z3 which defines economic protection level in power system were quite higher than the stationary resistance. The grounding impedance is decreased by the application of the triple-rods grounding system, and its effect is decreased as the frequency of the current is increased due to the inductance of the grounding leads.

  • PDF

The Protection methods of Telecommunication Network from Electrical Transient Phenomena (전기적 과도현상으로부터 통신망의 보호대책)

  • Choi, Man-Ho;Kim, Hyun-Duk;Kim, Byung-Cheul
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • v.9 no.2
    • /
    • pp.693-696
    • /
    • 2005
  • Parallel and cross of the electrical power and telecommunication network is become accelerated, because telecommunication equipments are constructed according to road for efficient maintenance of domestic telecommunication network. The electrical power network can generate an electrostatic induction, and is itself transmission medium from electrical transient phenomenon such as lighting. So, transient phenomenon of lightning surge is induced to telecommunication network, and then it is damaged by connecting between electrical ground of electrical power network and telecommunication network. In this study, we found that cut-off of return path current by separate distance between electrical ground of electrical power network and telecommunication network, and cut-off of electrostatic induction voltage by grounding unused leads of both terminals of the electrical and telecommunication network have good effect as the protection methods of telecommunications network from electrical transient phenomena.

  • PDF

Frequency Dependence of Impedance of the Grounding Grid (접지그리드의 접지임피던스의 주파수 의존성)

  • 이복희;이동문;엄주홍;김교운
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.17 no.5
    • /
    • pp.22-28
    • /
    • 2003
  • This paper describes the frequency dependence of the grounding impedance. In order to propose the evaluation method of the transient response of powered grounding systems, the grounding impedances were measured with varying the frequency of incoming currents by way of the variable frequency inverter and band pass filter. The magnitude and phase of the grounding impedance were analyzed in the frequency range of 20 [Hz]∼2.1[kHz]. The grounding impedance were increased with increasing the frequency of the test current. The grounding impedance at the frequency of 2[kHz] in the actual 22.9[kV] substation grounding system was approximately 3 times as large as the 60[Hz] grounding impedance. It was found that the frequency dependence of the grounding impedance is mainly subject to the inductive reactance of the grounding conductors. As a result, it is critical to determine the shape and size of grounding grid reducing the resultant inductance in grounding systems for lightning surge protection.

Impulse breakdown Characteristics in SF6/N2, Gas Mixtures with a Temperature Variation (온도변화에 따른 SF6/N2 혼합가스의 임펄스 절연파괴특성)

  • Li, Feng;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.22 no.12
    • /
    • pp.79-86
    • /
    • 2008
  • This paper presents the experimental results of impulse breakdown characteristics in $SF_6/N_2$ gas mixtures under a highly non-uniform electric field with a change in temperature. The test temperature ranges from -25[$^{\circ}C$] to 25[$^{\circ}C$]. The processes of impulse preliminary breakdown developments were analyzed by the measurements of current pulse and luminous signals. As a result, the temperature dependance of breakdown voltage for the negative polarity was much stronger than that for the positive polarity. When increasing the temperature, The leader stepping time for the negative polarity was shown to be longer than that for the positive polarity. The results presented in this paper can be used as a useful information in designing the gas insulation lines with prominent ability for lightning surge.