• Title/Summary/Keyword: impulse current

Search Result 371, Processing Time 0.025 seconds

Change of Electrical Characteristics of ZnO Arrester Blocks by Lightning Impulse Current (뇌충격전류에 의한 산화아연형 피뢰기 소자의 전기적 특성변화)

  • Gil, Gyeong-Seok;Han, Ju-Seop;Park, Yeong-Ho
    • The Transactions of the Korean Institute of Electrical Engineers C
    • /
    • v.48 no.7
    • /
    • pp.550-555
    • /
    • 1999
  • This paper deals with the effect of lightning impulse current on electrical characteristics of ZnO blocks used in distribution lightning arrester. The electrical characteristics of ZnO blocks are degraded by overtime impulse current, and the degraded ZnO block is brought to a thermal runaway and finally destroyed. It is therefore important to estimate the change of electrical characteristics of ZnO blocks. In this study, an impulse current generator which can produce 8/20$[\mus]$, 3[㎄] and 4/10$[\mus]$, 5[㎄] waveform is designed and fabricated to simulate the lightning impulse current of power systems. Total energy applied to the ZnO blocks at each time is 739[J] in 8/20$[\mus]$, and 523[J] in 4/10$[\mus]$, impulse current, respectively. From the experimental results, the 3rd harmonic of the leakage current increases continuously with the number of applied impulse current, but no significant changes in residual voltage and in reference voltage are observed until the ZnO block is destroyed. Also, it is confirmed that the main factor on degradation of ZnO blocks is rather the total energy applied to ZnO blocks than the peak value of the impulse current.

  • PDF

Characteristics of Lightning Impulse Current of Zno Block for Transmission Line Arrester with External Gap (송전선로에 사용되는 갭형 피뢰기 소자의 뇌임펄스 전류특성)

  • Cho, Han-Goo;Yoo, Dae-Hoon
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.04b
    • /
    • pp.61-62
    • /
    • 2009
  • This paper describes the characteristics of lightning impulse current of ZnO block for transmission line arrester with external gap. The ageing parameters of lightning arresters ate impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by impulse current. Total energy applied to the ZnO arrester each time is $4/10{\mu}s$, 30kA and $2/20{\mu}s$, 10kA impulse current. Before and After the test, the residual voltage variation of varistors passed was below 5%. According to the test, it is thought that the ZnO arrester shows good stability with impulse current test.

  • PDF

Characteristics of Lightning Impulse Current of ZnO Block for Transmission Line Arrester with External Gap (송전선로에 사용되는 갭형 피뢰기 소자의 뇌임펄스 전류특성)

  • Cho, Han-Goo;Yoo, Dae-Hoon
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2007.06a
    • /
    • pp.458-459
    • /
    • 2007
  • This paper describes the characteristics of lightning impulse current of ZnO block for transmission line arrester with external gap. The ageing parameters of lightning arresters are impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by impulse current. Total energy applied to the ZnO arrester each time is $4/10{\mu}s$, 30kA and $2/20{\mu}s$, 10kA impulse current. Before and After the test, the residual voltage variation of varistors passed was below 5%. According to the test, it is thought that the ZnO arrester shows good stability with impulse current test.

  • PDF

Design & characteristics of impulse current test system for station class(up to class 5) (송변전급(up to class 5) Impulse current test system의 설계 및 특성)

  • Kim, Seok-Sou;Choi, Ike-Sun;Kang, Young-Sik;Park, Byung-Rak;Park, Tae-Gon
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2004.07b
    • /
    • pp.1146-1149
    • /
    • 2004
  • A new developed impulse current test system(100kV, 250kJ)is presented, which can carry out all impulse current and performance tests on surge arrester sections with rated voltage up to 12kV according to IEC 60099-4(2001). The maximum achievable peak value is 200kA for the impulse current $4/10{\mu}s$ and 60kA for the $30/80{\mu}s$ and $8/20{\mu}s$. The long duration current impulse is realized from class 1 to class 5. The digital transient recorder(4 channels 60MS/S 10bit) is used for measuring AC voltage, impulse current, reference voltage and leakage current. The complex control, measuring, evaluation and data storage system is controlled by one industrial PC system.

  • PDF

Changes of Electrical Characteristic of ZnO Varistors by a Lightning Impulse Current (뇌충격전류에 의한 산화아연형 바리스터의 전기적 특성변화)

  • 이종혁;손원진;김명진;길경석
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • 2000.10a
    • /
    • pp.581-584
    • /
    • 2000
  • This paper describes the effect of lightning impulse current on ZnO varistors(390 V, 6.5 kA) used in low-voltage AC mains as a protective device against transient overvoltages. A lightning impulse current standardized in IEC 61000-4-5 is applied to the varistors, and the energy applied to the varistor at each time is about 12 J. In the experiment, various Parameters such as leakage current, reference voltage are measured with the number of applied impulse current. Also, micro-structure changes of the varistors after applying the lightning impulse current of 200 times are compared. The electrical characteristics of the varistors are degraded by overtime impulse current, showing increase in leakage current and decrease in reference voltage.

  • PDF

Change of the Characteristics of ZnO Arrester Blocks by Lightning Impulse Current (산화아연형 피뢰기 소자의 뇌충격전류에 의한 특성 변화)

  • Han, Joo-Sup;Song, Jae-Yong;Kil, Gyung-Suk
    • Proceedings of the KIEE Conference
    • /
    • 1998.11c
    • /
    • pp.907-909
    • /
    • 1998
  • This paper describes the effect of impulse current on degradation of ZnO blocks. In this study, an impulse current generator which can produce 8/20 [${\mu}s$], 3 [kA] and 4/10 [${\mu}s$], 5 [kA] waveform is designed and fabricated to simulate the lightning impulse current. The residual voltage, reference voltage, and leakage current flowing to the ZnO blocks are observed. The experimental results show that the leakage current increases continuously with the number of applied impulse current, but no significant changes in residual voltage and in operating voltage are observed until the ZnO block is destroyed. Also, it is confirmed that the main factor on degradation of ZnO blocks is rather the total energy applied to ZnO blocks than the peak value of the impulse current.

  • PDF

Investigation of Large-scale Transmission Tower Grounding Grid with High Amplitude and Uniform Flowing Impulse Current

  • Yang, Shuai;Huang, Jiarui;Wei, Shaodong;Zhou, Wenjun
    • Journal of Electrical Engineering and Technology
    • /
    • v.13 no.5
    • /
    • pp.2050-2058
    • /
    • 2018
  • Impulse characteristic of transmission tower grounding grid is needed for lightning protection of transmission line. This paper describes an outdoor experimental test facility established for large-scale grounding grid of transmission tower, made up of four impulse current generators and a circle current return electrode. The amplitude of impulse current is up to 100 kA. The results of the CDEGS simulation and GPR measurement reveal the uniform current distribution in the test arrangement. An impulse test for a square electrode with extended conductors is carried out in condition of three current waveforms with different amplitude. Based on the electrical network model and iterative algorithm method, a calculation model is proposed to simulate the impulse characteristic of large-scale grounding grid considering soil ionization. The curve of impulse resistance against the current amplitude shows the soil ionization both from the simulation and test. Deviation between the simulation and test result is less than 15%.

A Study on the microstructure and Surge Characteristics of ZnO varistors for distribution Arrester (배전급 피뢰기용 ZnO 바리스터 소자의 미세구조 및 서지 특성에 관한 연구)

  • 김석수;조한구;박태곤;박춘현;정세영;김병규
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.15 no.2
    • /
    • pp.190-197
    • /
    • 2002
  • In this thesis, ZnO varistors with various formulation, such as A∼E, were fabricated according to ceramic fabrication method. The microstructure, electrical properties, and surge characteristics of ZnO varistors were investigated according to ZnO varistors with various formulation. In the microstructure, A∼E\`s ZnO varistor ceramics sintered at 1130$\^{C}$ was consisted of ZnO grain(ZnO), spinel phase (Zn$\_$2.33/Sb$\_$0.67/O$\_$4/), Bi-rich phase(Bi$_2$O$_3$) and intergranuler phase, wholly. Lightning impulse residual voltage of A, B, C and E\`s ZnO varistors suited standard characteristics, below 12kV at current of 5kA. On the contrary, D\`s ZnO varistor exhibited high residual voltage as high reference voltage. In the accelerated aging test, leakage current and watt loss of B, C and D\`s ZnO varistors increases abruptly with stress time under the first a.c. stress(115$\^{C}$/3.213kV/300h). Consequently, C varistor exhibited a thermal run away. On the contrary, leakage current and watt loss of A and C\`s ZnO varistors which show low initial leakage current exhibited constant characteristics. After high current impulse test, A\`s ZnO varistor has broken the side of varistor but impulse current flowed. On the contrary, E\`s ZnO Varistor exhibited good discharge characteristics which the appearance of varistor was not wrong such as puncture, flashover, creaking and other significant damage. After long duration impulse current test, E\`s ZnO varistor exhibited good discharge characteristics which the appearance of varistor was not wrong such as puncture, flashover, creaking and other significant damage. After high current impulse test and long duration impulse current test, E\`s ZnO varistor exhibited very good characteristics which variation rate of residual voltage is 1.4% before and after test.

HY 1600kV/70kA Impulse Voltage/Current Test Facility (한양대학교 1600kV/70kA 충격 전압/전류 시험설비 구축)

  • Chang, Yong-Moo;Kim, Cheol-Ho;Hwang, Ryul;Lee, Bang-Wook;Koo, Ja-Yoon
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2009.11a
    • /
    • pp.229-229
    • /
    • 2009
  • This Impulse Voltage and Current Test System is designed for performing of impulse voltage tests with Lightning impulse voltage 1.2/50(LI) up to 1520kV peak value and switching impulse voltages 250/2500(SI) up to 1120kV peak valu acc. to IEC 60060-1, and furthermore for impulse current test, e.g. testing of arrester sections($U_{res}$=95kV)with current impulses 4/10 and 8/20 up to 70kA peak value.

  • PDF

Degradation Characteristics of Pr/Co/Cr/Er Co-doped Zinc Oxide Varistors by Impulse Current Stress

  • Nahm, Choon-Woo
    • Transactions on Electrical and Electronic Materials
    • /
    • v.15 no.6
    • /
    • pp.348-352
    • /
    • 2014
  • In light of the sure protection function, the most important factors of a varistor are the clamping voltage ratio and degradation characteristics. The degradation characteristics of Pr/Co/Cr/Er co-doped zinc oxide varistors were investigated by impulse currents (0.4~2.1 kA) stress for the specified content of $Er_2O_3$ (0.5 and 2.0 mol%). The varistor doped with 2.0 mol% $Er_2O_3$ exhibited the best clamp characteristics, with the clamp voltage ratio (K) in the range of K = 1.63~1.88 at the impulse currents of 5-50 A. However, the varistor doped with 0.5 mol% exhibited excellent electrical stability, with variation rates for the breakdown field, for the nonlinear coefficient, and for the leakage current density of -6.9%, -12.6%, and -14.3%, respectively, after application of an impulse current of 2.1 kA. In contrast, the varistor doped with 2.0 mol% was destroyed after application of an impulse current of 1.2 kA.