• Title/Summary/Keyword: high-current impulse test

Search Result 44, Processing Time 0.035 seconds

A Study on the Improvement of ZnO Varistor for Distribution Class Surge Arrester(18kV, 5kA) (배전급 피뢰기(18kV, 5kA)용 산화아연바리스타의 성능향상에 관한 연구)

  • Yoo, Deok-Son;Yoon, Han-Soo;Kim, Suk-Soo;Choi, Yeon-Gyu;Jang, Sung-Do
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2003.07b
    • /
    • pp.744-746
    • /
    • 2003
  • A ZnO varistor with reference voltage 250V/mm was fabricated through the control of particle size in slurry and the variation of sintering conditions. It was found that to measure the flatness of the V-I characteristic curve in the small-current region and the flatness of the V-I characteristic curve in a large-current region was improved nonlinearity of the fabricated ZnO varistor. According to the IEC 60099-4 was measured the accelerated aging test and high current test of the distribution class surge varistor which is excellent in respect to the property of ZnO varistor.

  • PDF

Dead Operation Characteristics of Earth Leakage Circuit Breaker Caused by Impulse Voltages (임펄스전압에 대한 누전차단기의 부동작 특성)

  • Lee, Bok-Hee;Chang, Sug-Hun;Lee, Seung-Chil
    • Proceedings of the KIEE Conference
    • /
    • 1997.07e
    • /
    • pp.1715-1717
    • /
    • 1997
  • This paper deals with the dead operation characteristics of the earth leakage circuit breaker(ELB) caused by impulse voltages. The surge protective devices for electronic circuit and AC power lines are becoming more widely used. It is possible to give rise to the malfunction of ELB due to the operation of surge protective devices, and the interruption of AC power lines brings about several disadvantages such as low reliability of electronic and informational systems, economical loss, and etc. The dead operation characteristics of the ELB from impulse voltages were measured under the conditions of KS C 4613 and the test circuit with a varistor. As a result, the peak current value of the zero-phase sequence circuit of the ELB is increased as the surge voltage and stray capacitance increase. All of the ELBs used in this work were satisfied with the lightning impulse dead operation test condition defined in KS C 4613. However one specimen only did not cause dead operation in the condition of the test circuit with a varistor. There is high possibility that a large portion of the ELBs connected with the AC power lines having the surge protective devices bring about the dead operation.

  • PDF

Electrical Characteristics and Performance Evaluation with Manufacturing Process of Zinc Oxide Varistors (산화아연소자의 성형공정에 따른 전기적 특성과 성능평가)

  • Cho, Han-Goo;Yoon, Han-Soo;Kim, Suk-Soo;Choi, In-Hyuk
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.19 no.11
    • /
    • pp.1061-1066
    • /
    • 2006
  • This paper presents the electrical characteristics with manufacturing process and performance evaluation of high performance zinc oxide varistors. ZnO varistors were fabricated with typical ceramic production methods with different thickness and the structural and electrical characteristics of ZnO varistors were investigated. All varistors exhibited high density, which was in the range of $5.41{\sim}5.49g/cm^3$. In the electrical properties, the reference voltage increased in the range of $4.410{\sim}5.250kV$ with increasing their thickness and the residual voltage exhibited the same trends as the reference voltage. In the long duration current impulse withstand test, E-2 and F-1 samples failed at the two and four shots of impulse current, respectively, but E-1 and F-2 samples survived 18 shots during the test. Before and after this test, the variation ratio of residual voltage of E-1 and F-2 samples were -0.34 % and 0.05 %, respectively, which were in the acceptance range of 5 %. According to the results of tests, it is thought that if the fabrication process such as insulating coating, sintering condition, and soldering method is improved, these ZnO varistors would be possible to apply to the station class arresters in the near future.

Effective impulse impedances of a deep-driven ground rod combined with other grounding electrodes (다른 형상의 접지전극에 접속된 심매설 접지전극의 실효임펄스임피던스)

  • Lee, Bok-Hee;Chang, Keun-Chul;Lee, Su-Bong
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.565-569
    • /
    • 2004
  • This paper deals with the characteristics of potential rise and effective impulse impedance of deep-driven ground rods that are used in high resistivity soil or in confined places such as downtown. Also the effects of the impulse and fault currents on the deep-driven ground rods combined with different type grounding electrodes like as mesh grids and counterpoises are described. The $8/20{\mu}s$ impulse current and other wave currents with different rise times are injected into the test ground rod and the effective impedances are examined. The most effective way to obtain the fine transient impedance behaviors of deep-driven ground rods is to reduce the inductive component of grounding electrode systems combined with other ground electrodes.

  • PDF

Analysis of Soil Ionization Behaviors under Impulse Currents

  • Lee, Bok-Hee;Park, Geon-Hun;Kim, Hoe-Gu;Lee, Kyu-Sun
    • Journal of Electrical Engineering and Technology
    • /
    • v.4 no.1
    • /
    • pp.98-105
    • /
    • 2009
  • This paper presents the characteristics of soil ionization for different water contents, and the parameters associated with the dynamic properties of a simple model grounding system subject to lightning impulse currents. The laboratory experiments for this study were carried out based on factors affecting the soil resistivities. The soil resistivities are adjusted with water contents in the range from 2 to 8% by weight. A test cell with a spherical electrode buried in the middle of the hemispherical container was used. As a result, the electric field intensity $E_c$ initiating ionization is decreased with the reduction of soil resistivities. Also, as the water content increased, the pre-ionization resistance $R_1$ and the post-ionization resistance $R_2$ became lower with increasing current amplitude. The time-lag to ionization $t_1$ and the time-lag to the second current peak $t_2$ at high applied voltages were significantly shorter than those of low applied voltages. It was found that the soil ionization behaviors are highly dependent on the water content and the applied voltage amplitude.

Characteristics of lightning impulse breakdowns in inhomogeneous $SF_6$ gas gap (불평등전장에서 $SF_6$ 기체의 뇌임펄스 절연파괴특성)

  • Lee, B.H.;Choi, H.S.;Oh, S.K.;Li, F.
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1921-1923
    • /
    • 2004
  • V-p characteristics and the discharge luminous characteristics in inhomogeneous $SF_6$ gas gap under the positive and negative lightning impulse voltages are presented. The test gap was composed of the plane-to-plane with a needle-shaped protrusion. The applied voltage and the predischarge current were measured by the electric field sensor and the shunt of 50 ${\Omega}$, respectively. The light emission signals were observed by a photomultiplier tube, and a high-speed camera. In a consequence, the dielectric strengths of $SF_6$ gas gap under positive lightning impulse voltages were independent of the gas pressure. In the presence of the positive polarity, the branches of discharge channel were created and the directions of the discharge paths were random. On the other hands, the discharge paths of the negative polarity were more thicker and brighter.

  • PDF

Contruction and Performance Evaluation of the Surge Arrester for Transmission Class (송전급 피뢰기의 구조와 성능평가)

  • Kim, S.S.;Choi, I.S.;Cho, H.G.
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2002.07b
    • /
    • pp.890-893
    • /
    • 2002
  • Since 1970s, varistors using metal-oxide resistors have been applied to Gapless surge arresters for power system. In the paper, the structure of metal-oxide surge arresters without gaps for 362kV GIS which is developed the first in korea has been introduced. And the main evaluation items for the metal-oxide resistors which are reference voltage test, residual voltage test, long duration current impulse withstand test and operating duty test is tested and evaluated.

  • PDF

The Dielectric Characteristics of Turn-to-Turn Insulation for DC Reactor Type HTSFCL (DC reactor type 고온호전도 한류기의 턴간 절연 특성)

  • 백승명;정종만;이창화;류엔반둥;김상현
    • Journal of the Korean Institute of Electrical and Electronic Material Engineers
    • /
    • v.16 no.12S
    • /
    • pp.1299-1304
    • /
    • 2003
  • Fault current limiters (FCL) are extensively needed to suppress fault currents, especially for trunk power systems heavily connected to high voltage/large current transmission lines. Due to its ideal electrical behavior, high-temperature superconductor fault current limiter (HTSFCL) becomes one of the most important developing trends of limiters in power system. This paper describes the result of an investigation of the dielectric characteristics of turn-to-turn insulation for pancake and solenoid type reactor coil in liquid nitrogen. The influence of thickness in a variety length, on AC, DC and impulse surface flashover has been investigated. Also, the relationships between the number of turn and breakdown characteristics were clarified. The information gathered in this test series should be helpful in the design of liquid nitrogen filled DC reactor type HTSFCL.

Insulation Design for a 13.2kV/630A High-Tc Superconducting Fault Current Limiter (13.2kV/630A급 고온초전도 한류기의 절연설계)

  • Kang, Hyoung-Ku;Lee, Chan-Joo;Ko, Tae-Kuk;Seok, Bok-Yeol
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.941-942
    • /
    • 2007
  • The superconducting fault current limiter (SFCL) consists of superconducting coil for limiting the fault current and cryogenic cooling system for keeping the coil in superconducting condition. The study on the insulation design for superconducting coil and cryogenic cooling system should be elaborately performed to develop a high voltage SFCL. In this paper, insulation design of solenoid coil for 13.2kV/630A SFCL is performed through the AC dielectric breakdown test and lightning impulse dielectric strength test. The dependence of dielectric characteristics on the magnitude of liquid nitrogen pressure is also investigated. Through the investigation, it is verified that dielectric characteristics of sub-cooled nitrogen are strongly enhanced by the pressurization. The electrical insulation design of 13.2kV/630A SFCL is performed by applying the experimental results. The successful insulation design for development of 13.2kV/630A SFCL is confirmed by AC dielectric breakdown tests.

  • PDF

Transient Impedance Characteristics of Grounding Rods (봉상접지극의 과도임피던스 특성)

  • 김일권;김점식;송재용;길경석
    • Proceedings of the Korean Institute of Information and Commucation Sciences Conference
    • /
    • 2000.10a
    • /
    • pp.568-572
    • /
    • 2000
  • This paper describes the experimental results of a transient impedance characteristics of grounding rods to a square pulse and standard lightning impulse current. The test were performed on single grounding rod($\phi$ 10mm, 1m) and triple-grounding rods( $\phi$ 10mm, 1m) of equilateral triangles with 5m spacing. For measurements of transient impedance, a pulse generator which can produce square wave of 30ns rise time and 20U Pulse duration was designed and fabricated. In the experiment, transient impedance of the grounding systems have been investigated from the recorded potential and current waveforms. The results showed that the value of the transient impedance is quite higher than the stationary resistance, and provide useful information for the value of a grounding system considered transient characteristics under a high frequency condition such as lightning stokes and ground-fault.

  • PDF