• Title/Summary/Keyword: fire performance test

Search Result 618, Processing Time 0.03 seconds

Development of Arm Fire Device for Solid Rocket (고체 추진기관 점화안전장치 개발)

  • Jang Seung-Gyo;Jung Jin-Suk;Kim In-Suk
    • Proceedings of the Korean Society of Propulsion Engineers Conference
    • /
    • 2005.11a
    • /
    • pp.169-172
    • /
    • 2005
  • The performance test result of the Arm Fire Device(Ignition Safety Device) for solid rocket which prevents accidental ignition was described. The results of the closed bomb test and the igniter test of the classical mechanical arm fire device and the advanced electro-mechanical arm fire device were presented, and according to the igniter test result it was realized that the electro-mechanical arm fire device has an advantage in aspect of the action time.

  • PDF

Thermal Characteristics of Fire-Protection Foams Exposed to Radiant Heating (복사열에 노출된 소방용 폼 약제의 열적 특성 연구)

  • Kim, H.S.;Hwang, I.J.;Kim, Youn-J.
    • Proceedings of the KSME Conference
    • /
    • 2004.04a
    • /
    • pp.1570-1575
    • /
    • 2004
  • In order to evaluate the performance of fire-fighting agents used to protect structures from heat and fire damages, the thermal characteristics of fire-protection foams are experimentally investigated. The current research focuses on the destruction of a fire-fighting foam subjected to heat radiation. A simple repeatable test for fire-protection foams subjected to fire radiation is developed. This test involves foam generation equipment, a fire source for heat generation, repeatable test procedures, and data acquisition techniques. Results of the experimental procedure indicated that each thermocouple within the foam responded in a similar manner and gradually to a temperature of $15^{\circ}C{\sim}20^{\circ}C$. At this point, each trace generally rises to a temperature of approximately $90^{\circ}C$. The temperature gradient in the foam as time passes increases with increased foam expansion ratio. In addition, it is determined that the temperature gradient along the foam for depth decreases with increased foam expansion ratio.

  • PDF

Test Method Using Shield-cup for Evaluating Response Characteristics of Fire Detectors (화재감지기의 응답특성 평가를 위한 Shield-cup이 적용된 시험방법)

  • Jang, Hyo-Yeon;Hwang, Cheol-Hong
    • Fire Science and Engineering
    • /
    • v.34 no.4
    • /
    • pp.36-44
    • /
    • 2020
  • It is necessary to predict the activation time of fire detectors accurately to improve the reliability for evaluating the required safe egress time (RSET) in performance-based fire safety design. In this study, problems of the plunge test, which is widely applied in assessing fire detectors, were examined through experiments and numerical simulations. In addition, a new shield-cup test method was proposed to address these problems. A fire detector evaluator (FDE) developed in a previous study was applied to ensure measurement accuracy and reproducibility. During the plunge tests, a significant measurement error was observed in the activation time of the smoke detector because of the rapid flow change when the detector was input. However, during the shield-cup tests, slight changes occurred in the flow inside the FDE when the detector as exposed to smoke. In conclusion, the proposed shield-cup test method is expected to be useful for evaluating the response characteristics of fire detectors more accurately in simulated fire environments.

Properties of Fire Resistance of Concrete with Contents of Polypropylene Fiber and Specimens Size (폴리프로필렌 섬유의 혼입률 및 부재크기 변화에 따른 콘크리트의 내화 특성)

  • 전선천;황인성;이병열;양성환;한천구
    • Proceedings of the Korea Concrete Institute Conference
    • /
    • 2001.05a
    • /
    • pp.463-468
    • /
    • 2001
  • A lot of considerations on the spatting by fire of high performance concrete should be taken into for fire resistance of the concrete structures. In this paper, fire resistance of high performance concrete is described using polypropylene fiber, which is known to be contributed to fire resistance. Strength level and member size are varied with. According to test results, spatting by fire takes place more easily, as W/C increases and member size decreases. It shows that concrete containing polypropylene fiber has good effects on preventing spatting by fire. In case high performance concrete does not contain polypropylene fiber, residual strength shows to be decreased remarkably compared :o that of normal concrete. Whereas, in case 0.1% of polypropylene fiber contents, high performance concrete shows higher residual strength than that of normal concrete. As member size is smaller, residual strength shows to be decreased.

  • PDF

An Experimental Study on the Various Factors affect the Explosive Spalling of High Performance Concrete (고성능 콘크리트의 폭열에 미치는 각종 요인에 관한 실험적 연구)

  • Na, Chul-Sung;Shin, Kwan-Soo;Lee, Eui-Bae;Kwon, Young-Jin;Kim, Gyu-Yong;Kim, Moo-Han
    • Proceedings of the Korea Institute of Fire Science and Engineering Conference
    • /
    • 2006.04a
    • /
    • pp.172-175
    • /
    • 2006
  • Recently, fire resistance of high performance concrete for explosive spatting was issued as high performance concrete was vulnerable to the explosive spatting in initial fire. Therefore, This study is willing to propose fundamental data for quick and accurate diagnosis of deteriorated concrete structure by fire damage with making variable concrete test specimen, exposing high temperature environment, observing the explosive spatting and examining engineering property.

  • PDF

Evaluation for fire resistance performance of high strength CFT with loading (재하하중에 따른 고강도 CFT의 내화성능 평가)

  • Hong, Seok-Beom;Yoo, Jo-hyeong;Kim, Woo-Jae;Lee, Ji-Hwan
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2013.11a
    • /
    • pp.184-185
    • /
    • 2013
  • Concrete filled steel Tube(CFT) columns have great strength but also fire resistance performance due to the heat storage effect of concrete. In this research, we focus on the fire performance of CFT using 100 MPa concrete without fire protection. We use steel fiber and nylon fiber for fire resistance. We perform the fire test of CFT specimen with loading 200, 300 and 400 ton. To investigate the effect of loading to fire resistance, we compare the fire resistance time according to the loading.

  • PDF

A Study for the Fire Retardant-Characteristics of Expandable Graphite Composite Materials (팽창흑연을 사용한 복합재료의 난연 특성에 관한 연구)

  • Chun, Kwan-Ok;Rie, Dong-Ho
    • Journal of the Korean Society of Safety
    • /
    • v.32 no.3
    • /
    • pp.28-33
    • /
    • 2017
  • In this study, the composite material of expandable graphite was made to the material development for improving such as a composite material of the sandwich panels or material properties of a fire door and was tested by the ISO 1182, ISO 5660-1(Cone calorimeter Method). For the test, the composite material of expandable graphite, what the expandable graphite ratio was increased by respectively 0g~30g, was classified A1,A2, A3, A4, and made to the test specimens. Through cone calorimeter test, peak heat release rate(HRR) and total heat release(THR), expanded thickness and expansion rate of each composite material of expandable graphite, and fire prone crack and mass loss rate after burning was measured. Thus, the effect of the addition of the expandable graphite and whether is suitable for reference as a fire retardant, was analyzed. Consequently the correlation of THR and fire retardant performance rate was confirmed.

An experimental study on the fireproof performance of fire damper in accordance with insulation conditions on the coaming and blade (코밍 방열 두께 및 블레이드 방열 유무에 따른 방화 댐퍼의 내화성능에 관한 실험적 연구)

  • Choi, Tai-Jin;Kim, Joung-Sik;Choi, Kyeong-Kwan;Lim, Young-Soo;Kim, You-Taek
    • Journal of Advanced Marine Engineering and Technology
    • /
    • v.37 no.4
    • /
    • pp.431-437
    • /
    • 2013
  • In this paper, Fire resistance test was carried out to obtain class H-120 thermal insulation of fire dampers according to a hydrocarbon fire conditions. Specimens were fabricated three different types according to the change of the insulation system applied to damper blade and coaming which were measured surface temperature by performing the fire resistance test. As a test result, specimen-1, 2 of an uninsulated damper blade were exceeded thermal insulation acceptance criteria at 21 minutes, 46 minutes respectively, but specimen-3 of an insulated damper blade was satisfied thermal insulation acceptance criteria during 120 minutes. The test results showed that the insulation of the damper blade is an important factor in the fireproof performance of fire dampers concerning the coaming length minimum 500 mm on the unexposed side as specified test standard.

Comparison of the Fire Resistance Performance of Firestop Systems on Non-Metallic Pipes, Based on the Type of Through-Penetration Sleeve Used (비금속관 설비관통부의 슬리브 종류에 따른 내화성능 비교)

  • Jeong, A-Yeong;Choi, Hong-Beom;Park, Jin-O;Lee, Hyung-Do
    • Proceedings of the Korean Institute of Building Construction Conference
    • /
    • 2023.05a
    • /
    • pp.301-302
    • /
    • 2023
  • In this study, we aimed to identify changes in fire resistance according to the type of sleeves used for pipe penetrations and to examine their accreditation of fire resistance performance and use them as basic data. The test results of fire resistance according to the type of sleeve used in non-metallic pipe facilities showed that the temperature on the support side was higher for sleeves with higher thermal conductivity. For the temperature on the surface of the pipes, in the case of galvanized steel plates, steel pipes, and structures without sleeves, the highest temperature was observed after the expansion of the firestop material for 46 to 53 minutes and then decreased. PVC sleeves showed a steady increase in temperature until 53 minutes, after which the temperature did not increase further. In addition, for non-metallic pipes, the effect of the type of sleeve on fire resistance is considered to be insignificant because the lower part (heating direction of the furnace) under the support structure is cut off to block the heat during the two-hour fire resistance test.

  • PDF