DOI QR코드

DOI QR Code

Test Method Using Shield-cup for Evaluating Response Characteristics of Fire Detectors

화재감지기의 응답특성 평가를 위한 Shield-cup이 적용된 시험방법

  • Received : 2020.07.28
  • Accepted : 2020.08.19
  • Published : 2020.08.31

Abstract

It is necessary to predict the activation time of fire detectors accurately to improve the reliability for evaluating the required safe egress time (RSET) in performance-based fire safety design. In this study, problems of the plunge test, which is widely applied in assessing fire detectors, were examined through experiments and numerical simulations. In addition, a new shield-cup test method was proposed to address these problems. A fire detector evaluator (FDE) developed in a previous study was applied to ensure measurement accuracy and reproducibility. During the plunge tests, a significant measurement error was observed in the activation time of the smoke detector because of the rapid flow change when the detector was input. However, during the shield-cup tests, slight changes occurred in the flow inside the FDE when the detector as exposed to smoke. In conclusion, the proposed shield-cup test method is expected to be useful for evaluating the response characteristics of fire detectors more accurately in simulated fire environments.

성능위주 화재안전설계에서 요구 피난시간(Required safe egress time, RSET)의 정확한 평가를 위해서는 화재감지기 작동시간에 대한 정확한 예측이 필수적으로 요구된다. 본 연구에서는 실험 및 수치해석을 통해 화재감지기의 작동시험에 널리 적용되고 있는 Plunge test의 문제점이 검토되었다. 또한 이를 개선시킬 수 있는 새로운 Shield-cup test가 제안되었다. 측정의 정확성 및 재현성 확보를 위하여 개발된 Fire detector evaluator (FDE)가 적용되었다. 주요 결과로서, Plunge test에서는 감지기가 투입되는 순간에 급격한 유동변화로 인하여 연기감지기의 작동시간에 큰 측정오차가 발생되었으며, Shield-cup test에서는 감지기 노출 과정에서 장치 내부의 유동 변화가 거의 확인되지 않았다. 결론적으로 Shield-cup test는 모사된 화재환경에서 화재감지기의 응답특성을 보다 정확히 평가하는데 상당히 유용할 것으로 기대된다.

Keywords

References

  1. J. H. McGuire and G. T. Tamura, "Simple Analysis of Smoke Flow Problems in High Rise Buildings", Fire Technology, Vol. 11, pp. 15-22 (1975). https://doi.org/10.1007/BF02589997
  2. T. Cleary and A. Chernovsky, "Particulate Entry Lag in Spot-Type Smoke Detectors", Proceedings of 6th International Symposium, International Association for Fire Safety Science (IAFSS) (1999).
  3. G. Heskestad and H. F. Smith, "Investigation of a New Sprinkler Sensitivity Approval Test: The Plunge Test", Factory Mutual Research, FMRC Serial No. 22485 RC76-T-50 (1976).
  4. G. Heskestad and R. G. Bill, "Quantification of Thermal Responsiveness of Automatic Sprinklers including Conduction Effects", Fire Safety Journal, Vol. 14, pp. 113-125 (1988). https://doi.org/10.1016/0379-7112(88)90049-5
  5. W. G. Bissel, "An Investigation into the Use of the Factory Mutual Plunge Tunnel and the Resulting RTI for Fixed Temperature Fire Detectors" Master's Thesis, Worchester Polytechnic Institute (1988).
  6. N. C. Tsang, "Study on the Response Time Index of Sprinklers", International Journal on Engineering Performance-Based Fire Codes, Vol. 6, No. 4, pp. 234-241 (2004).
  7. A. Tsui and M. J. Spearpoint, "Variability of Sprinkler Response Time Index and Conduction Factor using the Plunge Test", Building Services Engineering Research and Technology, Vol. 31, No. 2, pp. 163-176, (2010). https://doi.org/10.1177/0143624410363064
  8. R. D. Blevins, "Applied Fluid Dynamics Handbook", New York, Van Nostrand Reinhold Company Inc. (1984).
  9. A. T. Pomeroy, "Analysis of the Effects of Temperature and Velocity on the Response Time Index of Heat Detectors", Master's Thesis, University of Maryland, MA, USA (2010).
  10. J. Grosshandler, "Towards the Development of a Universal Fire Emulator-Detector Evaluator", Fire Safety Journal, Vol. 29, pp. 113-128 (1997). https://doi.org/10.1016/S0379-7112(96)00031-8
  11. T. Cleary, M. Anderson, J. Averill and W. Grosshandler, "Evaluating Multi-Sensor Fire Detectors in the Fire Emulator / Detector Evaluator", INTERFLAM '99, pp. 453-464 (1999).
  12. K. H. Kim and C. H. Hwang, "Measurement of the Device Properties of a Ionization Smoke Detector to Improve Predictive Performance of the Fire Modeling", Journal of Korean Institute of Fire Science & Engineering, Vol. 27, No. 4, pp. 27-34 (2013).
  13. H. W. Park, J. H. Cho, S. Y. Mun, C. H. Park, C. H. Hwang, S. C. Kim and D. G. Nam, "Measurement of Device Properties of Fixed Temperature Heat Detectors for the Fire Modeling", Fire Science and Engineering, Vol. 28, No. 1, pp. 37-43 (2014). https://doi.org/10.7731/KIFSE.2014.28.1.037
  14. J. H. Cho, S. Y. Mun, C. H. Hwang and D. G. Nam, "Measurement of the Device Properties of Photoelectric Smoke Detector for the Fire Modeling", Fire Science and Engineering, Vol. 28, No. 6, pp. 62-68 (2014). https://doi.org/10.7731/KIFSE.2014.28.6.062
  15. H. Y. Jang and C. H. Hwang, "Revision of the Input Parameters for the Prediction Models of Smoke Detectors Based on the FDS", Fire Science and Engineering, Vol. 31, No. 2, pp. 44-51 (2017). https://doi.org/10.7731/KIFSE.2017.31.5.044
  16. G. Y. Yoon, H. S. Han, S. Y. Mun, C. H. Park and C. H. Hwang, "DB Construction of Activation Temperature and Response Time Index for Domestic Fixed-temperature Heat Detectors in Ceiling Jet Flow", Fire Science and Engineering, Vol. 34, No. 3, pp. 35-42 (2020). https://doi.org/10.7731/KIFSE.103eea8f
  17. C. H. Hwang, B. H. Yoo and C. E. Lee et al., "An Experimental Study of Smoke Movement in Tunnel Fire with Natural and Forced Ventilations", Transactions of Korean Society of Mechanical Engineers B, Vol. 29, No. 6, pp. 711-721 (2005). https://doi.org/10.3795/KSME-B.2005.29.6.711
  18. Y. Kametani, K. Fukagata, R. Orlu and P. Schlatter, "Effect of Uniform Blowing/Suction in a Turbulent Boundary Layer at Moderate Reynolds Number", International Journal of Heat and Fluid Flow, Vol. 55, pp. 132-142 (2015). https://doi.org/10.1016/j.ijheatfluidflow.2015.05.019
  19. B. J. Kim, J. H. Cho, C. H. Hwang and S. H. Park, "A Study on the Development of a Low-cost Device for Measuring the Optical Smoke Density", Fire Science and Engineering, Vol. 29, No. 4, pp. 81-88 (2015). https://doi.org/10.7731/KIFSE.2015.29.4.081
  20. National Standards of the Republic of Korea, "Detailed Regulations for Model Approval & Inspection Technical Standards for Fire Detectors", Korea Fire Institute (KFI), National Fire Agency, Republic of Korea, p. 23 (2019).
  21. S. S. Krishnan, K. C. Lin and G. M. Faeth, "Extinction and Scattering Properties of Soot Emitted from Buoyant Turbulent Diffusion Flames", Journal of Heat Transfer, Vol. 123, pp. 331-339 (2001). https://doi.org/10.1115/1.1350823
  22. S. Singh, M. N. Fiddler and S. Bililign, "Measurement of Side-dependent Single Scattering Albedo of Fresh Biomass Burning Aerosols usng the Extinction-Minus-scattering Technique with a Combination of Cavity Ring-down Spectroscopy and Nephelometry", Atmospheric Chemistry and Physics, Vol. 16, pp. 13491-13507 (2016). https://doi.org/10.5194/acp-16-13491-2016
  23. W. P. Arnott, H. Moosmuller and J. W. Walker, "Nitrogen Dioxide and Kerosene-Flame Soot Calibration of Photoacoustic Instruments for Measurement of Light Absorption by Aerosols", Review of Scientific Instruments, Vol. 71, No. 12, pp. 4545-4552 (2000). https://doi.org/10.1063/1.1322585
  24. K. McGrattan, S. Hostikka, R. McDermott, J. Floyd, C. Weinschenk and K. Overholt, "Fire Dynamics Simulator User's Guide", NIST Speical Publication 1019 (Sixth Edition), National Instiutue of Standards and Technology, Gaithersburg, MD (2015).
  25. U.S. NRC and EPRI, "Nuclear Power Plant Fire Modeling Analysis Guiderlines", NUREG-1934 and EPRI 1023259, Finial Report (2012).
  26. G. Heskestad, "Generalized Characterization of Smoke Entry and Response for Products of Combustion Detectors", Proceedings of the Fire Detection for Life Safety Symposium (1975).
  27. J. Dinenno, D. Drysdale, L. Craig, W. Douglas, P. Custer, J. Hall, J. Watts, "SFPE Handbook of Fire Protection Engineering", 3rd ed., National Fire Protection Association, Fosston, USA, pp. 560, 645 (2002).
  28. G. W. Mulholland and C. Croarkin, "Specific Extinction Coefficient of Flame Generated Smoke", Fire and Materials, Vol. 24, pp. 227-230 (2000). https://doi.org/10.1002/1099-1018(200009/10)24:5<227::AID-FAM742>3.0.CO;2-9
  29. H. Y. Jang, S. Y. Mun and C. H. Hwang, "Sensitivity Analysis of Input Parameters for Prediction Models of Smoke Detectors based on FDS", Proceedings of 2017 Spring Annual Conference, Korean Institute of Fire Science & Engineering, pp. 133-134 (2017).