A Study on A Gas Circuit Breaker Development Using Simplified Synthetic Testing Facility (간이합성시험설비를 이용한 가스차단기 개발에 관한 연구)

  • Chong, Jin-Kyo;Kim, Gyu-Tak
    • Proceedings of the KIEE Conference
    • /
    • 2007.07a
    • /
    • pp.902-904
    • /
    • 2007
  • A $SF_6$ gas circuit breakers are widely used for short circuit current interruption in EHV or UHV power system. During a $SF_6$ gas circuit breaker development, Simplified synthetic testing facility is used. This paper shows how simplified synthetic testing facility is used for a SF6 gas circuit breaker development.

  • PDF

Ground fault circuit interrupter design (누전차단기의 설계와 제작)

  • 설승기
    • 전기의세계
    • /
    • v.29 no.5
    • /
    • pp.303-311
    • /
    • 1980
  • The hazards of electrical shock are well known, but the conventional ground fault circuit breakers did not provide the statis factory safety for human body. Thus this paper considers the standards of performance that they must meet, and describes the new tripping mechanism the operations and the improvements. The experiment at new G.F.C.I. indicates maximum tripping time 25msec minimum sensitive leakage current 25mA and maximum nonaperation leakage current 15mA.

  • PDF

Improvement of Short Circuit Performance in 460[V]/400[A]/85[kA] Molded Case Circuit Breakers (460[V]/400[A]/85[kA] 배선용 차단기의 그리드 및 아크런너 변형을 통한 차단성능 향상)

  • Lee, Seung-Su;Jung, Eui-Hwan;Yoon, Jae-Hun;Kang, Seong-Hwa;Lim, Kee-Joe
    • Proceedings of the KIEE Conference
    • /
    • 2009.07a
    • /
    • pp.1451_1452
    • /
    • 2009
  • Owing to the increasing number of intelligent homes(or called Smart home), the corresponding cost is much higher. Low voltage circuit breakers are widely used in the intelligent homes to interrupt fault current rapidly and to assure the reliability of the power supply. The distribution of magnetic field induced by arc current in the contact system of molded case circuit breaker depends on the shape, arrangement, and kinds of material of grids. This paper is focused on understanding the interrupting capability, more specifically of the grid and the arc runner, based on the shape of the contact system in the current MCCB. The magnetic driving force was calculated by using the flux densities induced by the arc current, which are obtained by three-dimensional finite element method. There is a need to assure that the optimum design required to analyze the electromagnetic forces of the contact system generated by current and the flux density be present. This is paper present our computational analysis on contact system in MCCB.

  • PDF

Interrupting Characteristics of 25.8kV Gas Circuit Breaker Using Thermal-Expansion Principle (열팽창분사원리를 이용한 25,8kV급 가스차단기의 차단특성)

  • Chang, K.C.;Shin, Y.J.;Park, K.P.;Jeong, J.K.;Kim, J.K.;Kim, G.S.
    • Proceedings of the KIEE Conference
    • /
    • 1994.07b
    • /
    • pp.1603-1605
    • /
    • 1994
  • Recently, Gas Circuit Breakers are rapidly replacing Vacuum Circuit Breakers in the medium voltage switchgear. This is due to the improved performance of - GCB in interrupting capability, price, weight, size etc., while the countermeasure to suppress the switching surges of VCB has not been satisfactory. Intensive research works on the GCB have been conducted in the world widely since 1980. Nowadays it is well known that the thermal expansion type GCB can provide- better performance than puffer type in the distribution power system. KERI has conducted researches in the GCB rated at 25.8kV 25kA with Jinkwang Co. using the thermal expantion principle since 1993. In this paper, the calculated results of electric and magnetic fields for the model GCB are presented and analyzed. The effect of permanent magnet used to improve the interruption capabilty at the low current level is also investigated. The design parameters for the interrupter inspected through the short-circuit tests conducted at high power laboratory of KERI.

  • PDF

A Economic feasibility of Superconducting Fault Current Limiter in Korean Power System (초전도한류기의 계통도입을 위한 경제적 타당성 검토)

  • Kim Jong Yul;Lee Seong Ryul;Yoon Jae Young
    • Proceedings of the KIEE Conference
    • /
    • summer
    • /
    • pp.421-423
    • /
    • 2004
  • As power system grows more complex and power demands increase, the fault current tends to gradually increase. In the near future, the fault current will exceed a circuit breaker rating for some substations, which is an especially important issue in the Seoul metropolitan area because of its highly meshed configuration. Currently, the Korean power system is regulated by changing the 154kV system configuration from a loop connection to a radial system, by splitting the bus where load balance can be achieved, and by upgrading the circuit breaker rating. A development project applying 154kV Superconducting Fault Current Limiter(SFCL) to 154kV transmission systems is proceeding with implementation slated for after 2010. In this paper, the expected price of SFCL in order to assure the economic feasibility is evaluated comparing with upgrading cost of ciui.1 breakers. The results show that the SFCL should be developed under seven times of price of circuit breaker to be competitive against upgrading circuit breakers.

  • PDF

Arc-Withstanding Characteristics with respect to the nozzle material for EHV Class Gas Circuit Breakers (초고압 가스차단기용 노즐의 재질에 따른 내아크 특성)

  • Chong, J.K.;Song, K.D.;Park, K.Y.;Song, D.J.
    • Proceedings of the KIEE Conference
    • /
    • 2002.07b
    • /
    • pp.860-863
    • /
    • 2002
  • Recently, main nozzle and inner nozzle for EHV class gas circuit breakers were made by PTFE(Poly Tetra Fluoro Ethylen) for the basic material composite. But, nowadays strengthened PTFE was demanded because the supply of electric power increased. This paper shows the research results for nozzles according to the filler materials.

  • PDF

Failure Mode Analysis of Molded Case Circuit Breakers for the Reliability Assessment (배선용차단기의 신뢰성평가를 위한 고장모드해석)

  • Kim, Min-Kyu;Lee, Jeong-Gi;Jeong, Ju-Young;Kim, Ik-Soo
    • Proceedings of the KIEE Conference
    • /
    • 2004.07c
    • /
    • pp.1994-1996
    • /
    • 2004
  • 본 논문에서는 배전반 또는 분전반에서 널리 이용되고 있는 1000 V 이하의 배선용 차단기, 즉 MCCB(Molded Case Circuit Breakers)의 신뢰성을 평가하기 위한 시험계획 및 시험방법을 검토하기 위한 전단계에서 반드시 필요한 고장모드영향분석(FMEA)의 결과를 서술하고, 또한 고장모드별로 대응되는 스트레스를 이용한 신뢰성평가 방안에 대해서 제시한다.

  • PDF

A Research on Dielectric Characteristics of Small Current Interruption Considering Pre-Condition Test for Puffer Type Circuit Breaker (Pre-Condition 시험을 고려한 Puffer식 차단기의 진상소전류 차단성능에 관한 연구)

  • Ahn, Heui-Sub;Yoon, Jeong-Hoon;Lee, Jong-Chul;Choi, Jong-Ung;Oh, Il-Sung;Lee, Sung-Ho
    • Proceedings of the KIEE Conference
    • /
    • 2003.10b
    • /
    • pp.12-14
    • /
    • 2003
  • This paper presents the small current interruption capability of $SF_6$ puffer circuit breaker considering pre-condition. Firstly, the change of dielectric strength of the 3 breakers was compared with testing breakers as clean contacts and eroded contacts after 3 shots of 760 according to new IEC 62271-100 standard. Also the dielectric strength curve of each model was calculated through flow and electric field simulations. From these results, we could modify the empirical equation, being used to predict the dielectric strength of small current interruption capability, considering the effects of pre-condition.

  • PDF

Investigation on the Commercialization Issues of Resistive Type Superconducting Fault Current Limiters for Electric Networks

  • Park, Tae-Gun;Lee, Sang-Hwa;Lee, Bang-Wook
    • Progress in Superconductivity
    • /
    • v.11 no.1
    • /
    • pp.19-24
    • /
    • 2009
  • Among the various types of fault current limiters, superconducting fault current limiters could be the most preferable choice for high voltage electric power systems owing to the remarkable current limiting characteristics of superconductors. But, there have been no commercial superconducting fault current limiters which were installed into actual electric power systems until these days due to some remained technical and economical problems. Thus, in order to promote the development and application of the superconducting fault current limiters into real field, it is essential to understand the power utilities’ requirements for their networks and also suitable test method and some specifications should be prepared. This paper focuses on the matters of test requirements and standardization issues that should be prepared for commercialization of superconducting fault current limiters. The unique current limiting characteristics of superconducting fault current limiters were investigated and related other standards including circuit breakers, transformers, reactors, power fuse, and fused circuit breakers were compared to setup the basis of novel specification of superconducting fault current limiters. Furthermore, required essential test procedures for superconducting fault current limiters were suggested.

  • PDF

Development of Arc-Fault Detecting Technique through Analysis of Wire Ignition behavior by Series-Arc-Fault Currents (직렬아크고장 전류에 의한 전선 발화 특성 분석을 통한 아크고장 검출 기술의 개발)

  • Lim, Young-Bae;Jeon, Jeong-Chay;Bae, Seok-Myung;Kim, Tae-Kuek
    • Proceedings of the KIEE Conference
    • /
    • 2009.04a
    • /
    • pp.205-207
    • /
    • 2009
  • In 2007, 9,128 fires are attributed to electrical equipments. These fires resulted in 29 deaths and 262 injuries. Arc-faults were one of the major causes of these fires. When an unintended arc-fault occurs, it generates intense heat that can easily ignite surrounding combustibles. Conventional circuit breakers only respond to overloads, short circuits, and leakage currents. Therefore, the breakers do not protect against arcing conditions. This paper presents results obtained in experiments on ignition behavior of wire by series arc fault currents and techniques developed to detect the arc-faults. The developed technique was tested after installation to make sure they are working properly and protecting the circuit. If the developed arc detecting technique is applied, the electrical fires caused by an arc-fault can be reduced.

  • PDF