• Title/Summary/Keyword: catenary feeding system

Search Result 26, Processing Time 0.027 seconds

A Study on a Catenary Impedance Estimation Technique using Boosting Current Compensation Based on Current Division Characteristics of an AT Feeding System

  • Jung, Hosung;Kim, Hyungchul;Chang, Sang-Hoon;Kim, Joorak;Min, Myung-Hwan;An, Tae-Pung;Kwon, Sung-Il
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.3
    • /
    • pp.1370-1376
    • /
    • 2015
  • Generally, an autotransformer(AT) feeding system consists of double tracks, up and down, with the trolley wire and feeder wire of the up and down tracks connected in the sectioning post(SP). Consequently, load current or fault current flows on two tracks based on catenary impedance characteristics, making it difficult to estimate catenary impedance accurately. This paper presents a technique for the estimation of catenary impedance using boosting current compensation based on the current division characteristics of an AT feeding system to improve the operation performance of impedance relay. To verify the technique, we model an AT feeding system through a power analysis program (PSCAD/EMTDC) and simulate various operation and fault conditions. Through the simulation, we confirmed that the proposed technique has estimated catenary impedance with a similar degree of accuracy to the actual catenary impedance

Analysis of Catenary impedance characteristics in the extended power feeding conditions of AC traction system (교류급전방식에서의 연장급전에 따른 선로임피던스 특성 분석)

  • Jung, Hosung;Kim, Joorak;Chang, Sanghoon
    • Proceedings of the KIEE Conference
    • /
    • 2015.07a
    • /
    • pp.1617-1618
    • /
    • 2015
  • This paper analyzed catenary impedance characteristics of relays installed in substation and sectioning post to protect power feeding circuit in the extended power feeding conditions. For this, we modelled AT feeding system using PSCAD/EMTDC and calculated catenary impedance. The relay installed in substation calculated catenary impedance of the extended power feeding area adding catenary impedance of self protection zone. But, the relay installed in sectioning post calculated catenary impedance of the only protection area. Therefore, we confirmed that the more reliable protection way can be utilized using the relay installed in sectioning post.

  • PDF

A Study on Real Time Catenary Impedance Estimation Technique using the Synchronized Measuring Data between Substation and Train (변전소와 차량간의 동기화를 통한 실시간 전차선로 임피던스 예측 기법 연구)

  • Jung, Hosung
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.62 no.10
    • /
    • pp.1458-1464
    • /
    • 2013
  • This paper proposed a new real time catenary impedance estimation technique using synchronized power data from the measured data of operating vehicle and substation for catenary protective relay and fault locator setting. This paper presented estimation equation of catenary impedance using synchronized power data between substation and vehicle of AT feeding system for the performance verification of the proposed technique. Also AC feeding system is modeled through power analysis program and performance was verified through simulation according to various load changes. We verified that average 2.38%(distance equivalent 23.8 m) error appeared between the proposed estimation equation of catenary impedance and power analysis program simulation output in no connection double track system between up track and down track. Furthermore, We confirmed that estimation error is bigger depending on the increasing the distance from substation and vehicle impedance using only using vehicle current when calculating vehicle impedance in connection double track system between up track and down track. But, We confirmed that the proposed technique estimated accurately catenary impedance regardless of vehicle impedance and distance from substation.

Analysis for Catenary Voltage of The ATs-Fed AC Electric Railroad System (단권변압기 교류전기철도 급전시스템의 전차선 전압해석)

  • 정현수;이승혁;김진오
    • The Transactions of the Korean Institute of Electrical Engineers A
    • /
    • v.52 no.9
    • /
    • pp.493-499
    • /
    • 2003
  • This paper presents exact Autotransformers(ATs)-fed AC electric Railroad system modeling using constant current mode for locomotives. An AC electric railroad system is rapidly changing single-phase load, and at a feeding substation, 3-phase electric power is transferred to paired directional single-phase electric power. As the train moves along a section of line between two adjacent ATs. The proposed AC electric railroad system modeling method considers the line self-impedances and mutual-impedances. The constant current mode model objectives are to calculate the catenary and rail voltages with the loop equation. When there are more than one train in the AC electric railroad system, the principle of superposition applies and the only difference between the system analyses for one train. Filially, this paper shows the general equation of an AC electric railroad system, and that equation has no relation with trains number, trains position, and feeding distance.

Modeling and Simulation Reactive Power Compensator using Multi-port Network Algorithm in Electrified Railway (다단자망 알고리즘을 이용한 급전시스템의 무효전력 보상 모델링 및 시뮬레이션)

  • Kim, Joorak
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.65 no.5
    • /
    • pp.883-887
    • /
    • 2016
  • The power supply system in Korean electrified railway has adopted AT feeding. If a fault occurs in some substation for any reason, the vicinity substation must feed electric power on the outage substation through catenary. So, the feeding distance grows twice of the normal state at extended feeding condition. If substation's feeding distance is longer than normal condition, the catenary impedance and train to supply electric power from the substation. Therefore, the severe voltage drop can occur and power supply shall be not allowed. This paper presents the model of compensator against voltage drop using multi-port network algorithm. Whole traction power supply system can be analyzed with this model. Computer simulation including this model is performed based on real train schedule and increased schedule in case studies.

Analysis of fault characteristics in Catenary system for protection of AC feeding system (교류 급전시스템 보호를 위한 전차선로 고장특성 분석)

  • Jung, Ho-Sung;Park, Young;Kim, Joo-Rak;Kwon, Sam-Young;Park, Hyun-June
    • Proceedings of the KIEE Conference
    • /
    • 2006.07b
    • /
    • pp.1089-1090
    • /
    • 2006
  • This paper analyzes impedance convergence characteristics and harmonics of electric locomotives operation and fault condition. To simulate the various fault and operation condition, AT feeding system and various locomotives are modeled using PSCAD/EMTDC. Analysis shows that impedance are converged into protection area in the case of short fault between catenary and rail or catenary and feeder line but in the case of disconnection fault, impedance is rater bigger so protective relay can't detect the fault. Therefore more analysis of overload and high impedance fault caused disconnection fault is needed.

  • PDF

A Study on Fault Location Estimation Technique Using the distribution Ratio of Catenary Current in AC Feeding System (전차선 전류 분류비를 이용한 교류전기철도 고장점 표정기법에 관한 연구)

  • Jung, Ho-Sung;Park, Young;Kim, Hyeng-Chul;Min, Myung-Hwan;Shin, Myong-Chul
    • Journal of the Korean Society for Railway
    • /
    • v.14 no.5
    • /
    • pp.404-410
    • /
    • 2011
  • In AC feeding system, the fault location is calculated by using ratio of current absorbed in the neutral point of AT(Automatic Transformer) or by measuring reactance. In this way, however, an estimation error can be happened due to the many reasons. In addition, for measuring currents in the neutral point of AT, other measuring devices and communication equipments are additionally required. In order to solve the disadvantages, this paper suggests a novel technique using the distribution ratio of catenary current. The proposed technique uses existing protective relays and measures catenary current. With the measured data, we can calculate the distribution ratio of catenary current and determine fault location. Through the simulated results, we derived the correlation between current ratio and fault location. Using this technique, additional equipments and expenses can be reduced. Besides, fault location can be determined more correctly.

Practical diagnostic technique for catenary surge arrester in electric railway (전차선로용 피뢰기 진단기법 적용 연구)

  • Han, Moon-Seob;Jang, Dong-Uk;Jung, Ho-Sung;Kil, Gyung-Suk
    • Proceedings of the KIEE Conference
    • /
    • 2005.07b
    • /
    • pp.1631-1633
    • /
    • 2005
  • This paper describes the measurement result of leakage current flowing arrestors connected in catenary line to propose an optimal management methods. 27 arrestors set in 7 locations were tested. The leakage currents are included a harmonics of electric train during the operation of electric train in feeding section and in case of feeding earthing system.

  • PDF

Analysis for Catenary Voltage of The ATs-Fed AC Electric Railroad System (교류전기철도 급전시스템의 전차선 전압해석)

  • 이승혁;정현수;김진오
    • Proceedings of the KSR Conference
    • /
    • 2002.10a
    • /
    • pp.490-496
    • /
    • 2002
  • This paper presents exact Autotransformers(ATs)-fed AC electric Railroad system modeling using constant current mode far locomotives. An AC electric railroad system is rapidly changing single-phase load, and at a feeding substation, 3-phase electric power is transferred to paired directional single-phase electric power. As the train moves along a section of line between two adjacent ATs. The proposed AC electric railroad system modeling method considers the line self-impedances and mutual-impedances. The constant current mode model objectives are to calculate the catenary and rail voltages with the loop equation. When there are more than one train in the AC electric railroad system, the principle of superposition applies and the only difference between the system analyses for one train. Finally, this paper shows the general equation of an AC electric railroad system, and that equation has no relation with trains number, trains position, and feeding distance.

  • PDF

Analysis of AT Feeding Systems considering the Voltage Constraint Conditions of the Catenary. (전차선 전압제약조건을 고려한 AT 급전계통 해석)

  • Kim B.;Chung K. W.
    • Proceedings of the KSR Conference
    • /
    • 2005.05a
    • /
    • pp.27-33
    • /
    • 2005
  • Constant load model is generally used for an electric train to perform the static analysis of AT feeding systems. In this model, the train will be considered as a constant load model when it drives or as a constant source model when it applies regenerative brake. However there must be some voltage constraints on the catenary in actual operations. These constraints are established for the reason of protecting the feeding facilities from excessive rise of regenerative braking voltage or guaranteeing the minimum traction power of train. In normal operating situation, the pantagraph voltage of the train should be maintained within these limits. Keeping these facts in minds, we suggest new methods of analyzing AT feeding systems using the constant power models with the conditions of voltage constraints. The simulation results from a sample system using the proposed method illustrate both the states of system variables and the supply-demand relation of power among the trains and the systems very clearly, so it is believed that the proposed method yields more accurate results than conventional methods do. The proposed methods are believed to contribute to the assessment of TCR-TSC for compensating reactive powers too.

  • PDF