Abstract
This paper analyzes impedance convergence characteristics and harmonics of electric locomotives operation and fault condition. To simulate the various fault and operation condition, AT feeding system and various locomotives are modeled using PSCAD/EMTDC. Analysis shows that impedance are converged into protection area in the case of short fault between catenary and rail or catenary and feeder line but in the case of disconnection fault, impedance is rater bigger so protective relay can't detect the fault. Therefore more analysis of overload and high impedance fault caused disconnection fault is needed.