• Title/Summary/Keyword: arc simulation

Search Result 422, Processing Time 0.024 seconds

Development of Fault Detector for Series Arc Fault in Low Voltage DC Distribution System using Wavelet Singular Value Decomposition and State Diagram

  • Oh, Yun-Sik;Han, Joon;Gwon, Gi-Hyeon;Kim, Doo-Ung;Kim, Chul-Hwan
    • Journal of Electrical Engineering and Technology
    • /
    • v.10 no.3
    • /
    • pp.766-776
    • /
    • 2015
  • It is well known that series arc faults in Low Voltage DC (LVDC) distribution system occur at unintended points of discontinuity within an electrical circuit. These faults can make circuit breakers not respond timely due to low fault current. It, therefore, is needed to detect the series fault for protecting circuits from electrical fires. This paper proposes a novel scheme to detect the series arc fault using Wavelet Singular Value Decomposition (WSVD) and state diagram. In this paper, the fault detector developed is designed by using three criterion factors based on the RMS value of Singular value of Approximation (SA), Sum of the absolute value of Detail (SD), and state diagram. LVDC distribution system including AC/DC and DC/DC converter is modeled to verify the proposed scheme using ElectroMagnetic Transient Program (EMTP) software. EMTP/MODELS is also utilized to implement the series arc model and WSVD. Simulation results according to various conditions clearly show the effectiveness of the proposed scheme.

Reliability Estimation by Simulation Using Total Hazard (시뮬레이션에서 Total Hazard 를 이용한 신뢰도 추정)

  • 전치혁
    • Journal of the Korean Operations Research and Management Science Society
    • /
    • v.16 no.1
    • /
    • pp.59-67
    • /
    • 1991
  • The hazard estimator is proposed for estimating system failure probability of a general network where all minimal cut sets are given. Theoretical variance of the hazard estimator is derived in a bridge system. It is demonstrated that variance of the hazard estimator is much smaller than that of the raw simulation estimator particularly for small arc failure probability.

  • PDF

A Study on Power Factor Correction of CO2 Arc Welder Using Three Phase Switch Mode Converter (3상 AC/DC 스위치 모드 승압형 컨버터를 이용한 CO2 아크 용접기 역률개선에 관한 연구)

  • 이정훈;김재문;안정준;이상석;원충연;김세찬
    • Proceedings of the KIPE Conference
    • /
    • 1998.07a
    • /
    • pp.149-153
    • /
    • 1998
  • In this paper A switched mode AC/DC three phase boost converter with high power factor and sinusoidal input current waveform is analyzed and simulated. The proposed converter retain high power factor and sinusoidal input current waveform even under electric arc welder load. It is shown that experimental result and simulation waveform yield a sinusoidal input current waveform at high power factor.

  • PDF

Influence of twisting angle between fixed contact and movable contact on arc driving force in 3petal spiral type vacuum interrupter (3petal spiral type vacuum interrupter에서 가동접점전극과 고정접점전극간의 마주보는 각도의 변화가 아크구동력에 미치는 영향)

  • Kim, Byoung-Chul;Yun, Jae-Hun;Lee, Seung-Soo;Kang, Seong-Hwa;Lim, Kee-Joe
    • Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference
    • /
    • 2008.06a
    • /
    • pp.480-480
    • /
    • 2008
  • Vacuum circuit breaker(VCB) is now emerging as an alternative of gas circuit breaker(GCB) which uses SF6 gas as insulating material whose dielectric strength is outstanding. But we have to reduce SF6 gas because SF6 gas is one of greenhouse gas and efforts to reduce greenhouse gas are now trend of the world. Therefore, we can say VCB is the optimal alternative of GCB because vacuum is environmentally friendly. The vacuum interrupter is the core part of VCB to interrupt arcing current. There are mainly two methods to extinguish arc. One is radial magnetic field (RMF) method and the other is axial magnetic field (AMF) method. We deals with RMF method in this paper. Compared with AMP, RMF arc quenching method has different principle to extinguish arc. In case of RMF method, pinch effect is much larger than AMF method. Because of pinch effect RMF type contact electrodes have the single large spot which is severly damaged and melted while AMF type contact electrodes have small and multiple spots which are slightly damaged and melted. To prevent contact electrode being damaged and melted from high temperature-arc, RMF method uses Lorentz force to move arc. In this paper we calculated and compared the arc driving force of two cases and we analyzed the force acting on each part of arc by means of commercial finite element method software Maxwell 3D. They have 3petals and we considered two cases. One is the case when fixed(upper) and movable(lower) contacts are in mirror arrangement (Case 1). The other is the case when one of two contacts (movable contact) is revolved at maximum angle as possible as it can be (Case 2). And at each case above, we analyzed arc driving force at two positions, position 1 is the closest to the center of contact and position 2 is near the edge of petal on fixed contact. As a result we could find that Case 2 generated stronger arc driving force than Case 1 at position 1. But at position 2 Case 1 generated stronger arc driving force than Case 2. This simulation method can contribute to optimizing spiral-type electrode designs in a view of arc driving force.

  • PDF

A Study on the Detection Technique of the Flame and Series arc by Poor Contact (접촉 불량에 의한 불꽃 및 직렬아크의 검출 기법에 관한 연구)

  • Woo, Kim Hyun;Hyun, Baek Dong
    • Fire Science and Engineering
    • /
    • v.26 no.6
    • /
    • pp.24-30
    • /
    • 2012
  • This study is on the method of the detection for flame and series arc which can be happened at poor contact point added a vibration in part of contact point of low voltage line. In general, the causes of electric fire are over current, short circuit, poor contact, ect. The over-current or short circuit among those causes is detected by measuring a instant current value, but poor contact is difficult to detect by measuring a excessive value of the voltage and current and a distortion of waveforms. And therefore, in this paper, it is studied on the optimal technique of the arc judgement using fuzzy logic and MDET (Multi Dimension Estimation Technique). And it carries out the simulation for arc detection and the experiment for controller and load test. In result, the controller and detection algoristhm, is classified with normal wave and abnormal arc wave without relation with each loads and so the controller can detect a series arc successfully.

A Comparison of Operation Characteristics for $3\Phi$Boost/Buck Converter to Inverter Arc Welding Machine (인버터 아크용접기를 위한 3상 승압/강압형 컨버터의 운전특성비교)

  • 최해룡;구영모;채영민;최규하;목형수;김규식;원충연
    • Proceedings of the KIPE Conference
    • /
    • 1998.07a
    • /
    • pp.260-264
    • /
    • 1998
  • Three phase Boost/Buck converter which have economical merits and simple control scheme, are analyzed and evaluated through comparative methods and digital simulation for equivalent load. Those play a part of voltage boost/buck as well as power factor correction with single switch. Controller operating in constant and variable frequency is used for rapid output response and stable system condition respectively. Moreover low THD property of single switched converters is available for inverter arc welding machine known as high power and low power factor. So, in this paper a comparison of the characteristics in boost and buck converter is described and then simulation results conforms the merits from point of view of power factor and voltage regulator.

  • PDF

Secondary Arc Modeling for Single-Pole Switching on Transmission Lines (단상재폐로 송전선로에 대한 2차 아크 모델링)

  • Park, Pyung-Chul;Lee, Uk-Hwa;Shin, Joong-Rin
    • Proceedings of the KIEE Conference
    • /
    • 1996.11a
    • /
    • pp.157-159
    • /
    • 1996
  • The secondary arcing phenomenon can be hardly modeled for computer simulation due to its particularly nonlinear characteristics. This paper describes a new computer modeling technique for the secondary arc which can be implemented with the EMTDC. The computer model proposed is based on realistic are conduction behaviors through both FIT and variable resistor modules which is supported in the EMTDC. Simulation results using the proposed technique are compared with some previous studies.

  • PDF

Applying a GIS to Solid and Hazardous Waste Disposal Site Selection (쓰레기매립장 부지선정을 위한 GIS 활용연구)

  • 김윤종;김원영;유일현;백종학;이현우;류중희
    • Korean Journal of Remote Sensing
    • /
    • v.6 no.2
    • /
    • pp.135-151
    • /
    • 1990
  • Solid and hazardous waste disposal site selection by using GIS(Geographic Information System) is the purpose of this study. The criteria of site selection are usually defined in accordance with geological, cultural and social characteristics. Unadequate adaptation of these criteria in a site selection may cause serious problem of water and soil pollution. The environmental information for extraction of these criteria consist of a lot of data : geology, geomorphology, hydrogeology, engineering geology, cultural and social information.... GIS could be easily applied to construct of this environmental information data base, and carry out cartography simulation using overlay mapping technique(polygon overlay). ARC/INFO(GIS system) was used for these studies, and AML(ARC/INFO Macro Language) in this system provided more variable and effective methods for cartography simulation. TM(Thematic Mapper) images were used for the evaluation of land cover/use in the studied area, by using ERDAS image processing system.

Characteristics of Pre-Post Contacts of DC Consent-Plug (직류용 콘센트-플러그의 초기-후기접점 특성)

  • Na, Jaeho;Wang, Yongpeel;Kim, Hyosung
    • The Transactions of the Korean Institute of Power Electronics
    • /
    • v.21 no.4
    • /
    • pp.290-295
    • /
    • 2016
  • Socket-outlets and plugs are essential devices that supply electric power into user appliances. During plug-out operation of an engaged plug from the socket-outlet, the consistent arc between the plug and the socket-outlet could develop into heavy fires in DC systems but only a small spark in AC systems. This paper proposes a pre-/post-electrode method to prevent plugs and socket-outlets from melting by sustaining arc energy. To implement the proposed pre-/post-electrodes, an experimental plug is manufactured with two electrodes, in which a post resistance Rs is connected in between. This paper investigates the function of the post resistance Rs, in which the best value of the post resistance Rs is obtained through simulation and experiment.