• 제목/요약/키워드: arc driving force

검색결과 22건 처리시간 0.031초

Simple Analysis Method for the Interrupting Capability of a Contact System in a Molded Case Circuit Breaker

  • Choi, Young-Kil;Jee, Seung-Wook
    • Journal of Electrical Engineering and Technology
    • /
    • 제12권3호
    • /
    • pp.1257-1261
    • /
    • 2017
  • This paper focuses on understanding the interrupting capability of an arc contact system in a molded case circuit breaker (hereafter MCCB). We selected four types of MCCBs and analyzed the magnetic flux density distributions in the contact systems caused by the fault currents. We ascertained that the magnetic flux density profile varies according to the shape of the contact system and was asymmetric at both the ends of an arc, perpendicular to the arc column because of the magnetic grid installed in the contact system. The asymmetric difference creates a magnetic force that pushes the arc current outwards and provides an interrupting capability. We have introduced a simple analysis method for determining the interrupting capability of the contact system for an MCCB by the arc-driving magnetic flux density.

철도 차량용 직류 고속도 차단기의 그리드 특성 해석 (Effects of Grid Characteristics on High Speed Circuit Breaker for Railway Vehicle)

  • 박지원;정주영;최진일
    • 한국철도학회논문집
    • /
    • 제19권2호
    • /
    • pp.117-123
    • /
    • 2016
  • 철도차량용 직류 고속도 차단기(HSCB)는 주 회로에 흐르고 있는 전류를 정상 차단시 아크 슈트 내부에서 발생아크를 소호하여 접지사고를 방지하는 기능으로 사용되고 있다. 선로에 사용되는 접촉기의 개방시에 발생하는 아크를 연구하기 위하여 아크 구현, 외부자계 등에 의한 효과적인 아크 소호의 방식 정립 및 아크 자기 구동력의 해석이 필요하다. 본 논문은 전자접촉기의 정상 차단시 발생하는 아크를 자속밀도 차와 로렌츠력을 통하여 소호능력을 예측하였다. 아크 슈트 내부의 그리드 개수와 형상은 내부 자계 형성에 영향을 미치므로, 유한 요소법을 이용하여 그리드의 변화에 따른 아크 소호능력을 연구하였으며 정격전압에 따른 그리드의 소호능력 평가와 그리드 형상 특성을 해석하였다.

열파퍼식 가스차단기에서 발생하는 아크 플라즈마에 의한 열유동 특성 (Thermal Flow Characteristics Driven by Arc Plasmas in a Thermal Puffer Type GCB)

  • 이종철;김윤제
    • 대한전기학회논문지:전기기기및에너지변환시스템부문B
    • /
    • 제54권11호
    • /
    • pp.527-532
    • /
    • 2005
  • During the last ten years the new interruption techniques, which use the arc energy itself to increase the pressure inside a chamber by the PTFE nozzle ablation, have displaced the puffer circuit breakers due to reduced driving forces and better maintainability. In this paper, we have investigated the thermal flow characteristics inside a thermal puffer type gas circuit breaker by solving the Wavier-Stokes equations coupled with Maxwell's equations for considering all instabilities effects such as turbulence and Lorentz forces by transient arc plasmas. These relative inexpensive computer simulations might help the engineer research and design the new interrupter in order to downscale and uprating the GIS integral.

460[V]/400[A]/85[kA] 배선용 차단기의 아크런너 변형을 통한 차단성능 향상 (Improvement of Short Circuit Performance in 460[V]/400{A]/85(kA] Molded Case Circuit Breakers)

  • 이승수;허준;윤재훈;강성화;임기조
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2009년도 하계학술대회 논문집
    • /
    • pp.394-394
    • /
    • 2009
  • Owing to the increasing number of intelligent homes(or called Smart home), the corresponding cost is much higher. Low voltage circuit breakers are widely used in the intelligent homes to interrupt fault current rapidly and to assure the reliability of the power supply. The distribution of magnetic field induced by arc current in the contact system of molded case circuit breaker(hereafter MCCB) depends on the shape, arrangement, and kinds of material of arc runner. This paper is focused on understanding the interrupting capability, more specifically of the arc runner, based on the shape of the contact system in the current MCCB. The magnetic driving force was calculated by using the flux densities induced by the arc current, which are obtained by three-dimensional finite element method. There is a need to assure that the optimum design required to analyze the electromagnetic forces of the contact system generated by current and the flux density be present. This is paper present our computational analysis on contact system in MCCB.

  • PDF

MEASUREMENT OF SURFACE TENSION OF MOLTEN METALS IN ARC WELDING

  • Shinobu Satonaka;Shigeo Akiyoshi;Inoue, Rin-taro;Kim, Kwang-Ryul
    • 대한용접접합학회:학술대회논문집
    • /
    • 대한용접접합학회 2002년도 Proceedings of the International Welding/Joining Conference-Korea
    • /
    • pp.757-762
    • /
    • 2002
  • Many reports have been shown that the buoyancy, electromagnetic force, surface tension, and gas shear stress are the driving forces of weld pool circulation in arc welding. Among them, the surface tension of molten metal plays an important role in the flow in weld pool, which are clarified by the specially designed experiments with small particles as well as the numerical simulations. The surface tension is also related to the penetration in arc welding. Therefore, a quantitative evaluation of surface tension is demanded for the development of materials and arc process control. However, there are few available data published on the surface tension of molten metals, since it depends on the temperature and the composition of materials. In this study, a new method was proposed for the evaluation of surface tension and its temperature dependence, in which it is evaluated by the equilibrium condition of acting forces under a given surface geometry, especially back surface. When this method was applied to the water pool and to the back surface of molten pool in the stationary gas tungsten arc welding of thin plate, following results were obtained. In the evaluation of surface tension of water, it was shown that the back surface geometry was very sensitive to the evaluation of surface tension and the evaluated value coincided with the surface tension of water. In the measurement of molten pool in the stationary gas tungsten arc welding, it was also shown that the comparison between the surface tension and temperature distribution across the back surface gave the temperature dependent surface tension. Applying this method to the mild steel and stainless steel plates, the surface tension with negative gradient for temperature is obtained. The evaluated values are well matched with ones in the published papers.

  • PDF

460[V]/400[A]/85[kA] 배선용 차단기의 그리드 및 아크런너 변형을 통한 차단성능 향상 (Improvement of Short Circuit Performance in 460[V]/400[A]/85[kA] Molded Case Circuit Breakers)

  • 이승수;정의환;윤재훈;강성화;임기조
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2009년도 제40회 하계학술대회
    • /
    • pp.1451_1452
    • /
    • 2009
  • Owing to the increasing number of intelligent homes(or called Smart home), the corresponding cost is much higher. Low voltage circuit breakers are widely used in the intelligent homes to interrupt fault current rapidly and to assure the reliability of the power supply. The distribution of magnetic field induced by arc current in the contact system of molded case circuit breaker depends on the shape, arrangement, and kinds of material of grids. This paper is focused on understanding the interrupting capability, more specifically of the grid and the arc runner, based on the shape of the contact system in the current MCCB. The magnetic driving force was calculated by using the flux densities induced by the arc current, which are obtained by three-dimensional finite element method. There is a need to assure that the optimum design required to analyze the electromagnetic forces of the contact system generated by current and the flux density be present. This is paper present our computational analysis on contact system in MCCB.

  • PDF

225[AF]/200[A]/50[kA] 배선용 차단기 고정자 변화를 통한 차단용량 향상

  • 이승수;윤재훈;정의환;임기조;강성화
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 2009년도 추계학술대회 논문집
    • /
    • pp.221-221
    • /
    • 2009
  • This paper is focused on understanding the interrupting capability, more specifically of the fix contact, based on the shape of the contact system in the current MCCB. The magnetic driving force was calculated by using the flux densities induced by the arc current, which are obtained by three-dimensional finite element method. There is a need to assure that the optimum design required to analyze the electromagnetic forces of the contact system generated by current and the flux density be present. This is paper present our computational analysis on contact system in MCCB.

  • PDF

DC 고속도 차단기의 아크 구동력 향상을 위한 구동부 형상 시뮬레이션 연구 (Simulation Study of Arc Driving Force of DC High Speed Circuit Breaker)

  • 임성우;이종건;;이방욱
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 2015년도 제46회 하계학술대회
    • /
    • pp.594-595
    • /
    • 2015
  • 본 논문에서는 직류차단기 내부 아크 러너 구조에 따라 아크에 작용하는 구동력 차이에 대한 연구를 수행하였다. 컴퓨터 시뮬레이션을 통해 아크 러너 기울기를 변화에 따라 아크 구동력을 계산하였으며, 결과 값들에 대한 비교 분석을 통해 아크 구동력 차이의 발생을 확인하였다. 구동력 차이의 발생 원리를 알아보고 아크구동력 향상 방안에 대해 연구하였으며, 결과 방안을 차단시간 단축 요소로써 활용할 수 있을 것으로 기대한다.

  • PDF

미래 기후 시나리오를 고려한 도시 유역 홍수 피해 저감을 위한 투수성 포장 시설 대상 유역 우선순위 선정 (Prioritizing the target watersheds for permeable pavement to reduce flood damage in urban watersheds considering future climate scenarios)

  • 채승택;송영훈;이주원;정은성
    • 한국수자원학회논문집
    • /
    • 제55권2호
    • /
    • pp.159-170
    • /
    • 2022
  • 기후변화로 인한 도시유역의 물 관련 재해의 심각성이 증가함에 따라 미래 기후 환경에서 도시 유역의 홍수피해를 줄이는 것은 중요한 문제 중 하나이다. 본 연구는 다기준의사결정기법을 이용하여 미래 기후 환경에서 도시 유역의 홍수 피해 저감 효율을 극대화하기 위해 투수성 포장 시설을 설치하기 위한 지역의 우선순위를 선정한다. 과거에 비해 도시화가 많이 진행된 목감천 유역을 대상유역으로 선정하였으며, 목감천 유역의 27개 소유역을 투수성 포장 시설의 설치 가능지역으로 하였다. 2개의 Shared Socioeconomic Pathway (SSP) 시나리오에 따른 Coupled Model Intercomparison Project 6(CMIP6)의 6개 전지구모형(General Circulation Model, GCM)을 사용하여 연구대상지의 미래 월 강수 자료를 추정했다. 투수성 포장의 우선순위를 결정하기 위한 수량 평가 기준은 Driving force-Pressure-State-Impact-Response (DPSIR) 체계를 토대로 선정하였으며, 평가 기준별 투수성 포장 시설의 평가값은 국가통계자료와 Storm Water Management Model의 모의 값을 사용했다. 최종적으로 Fuzzy TOPSIS 및 Minimax regret 방법을 사용하여 투수성 시설을 설치하기 위한 지역의 우선순위를 선정했다. 결국 우선순위가 높은 지역은 목감천 유역의 상류 유역에 비해 도시화가 많이 진행되었고 인구밀도가 높은 하류유역에 집중되었다.

Generic studies on thermo-solutal convection of mercurous chloride system of ${Hg_2}{Cl_2}$ and Ne during physical vapor transport

  • Choi, Jeong-Gil;Lee, Kyong-Hwan;Kim, Geug-Tae
    • 한국결정성장학회지
    • /
    • 제19권1호
    • /
    • pp.39-47
    • /
    • 2009
  • The effects of thermo-solutal convection on mercurous chloride system of ${Hg_2}{Cl_2}$, and Ne during physical vapor transport are numerically investigated for further understanding and insight into essence of transport phenomena, For $10\;K{\le}{\Delta}T{\le}30\;K$, the growth rate slowly increases and, then is decreased gradually until ${\Delta}T$=50 K, The occurrence of this critical point near at ${\Delta}T$=30 K is likely to be due to the effects of thermo-physical properties stronger than the temperature gradient corresponding to driving force for thermal convection. For the range of $10\;Torr{\le}P_B{\le}300\;Torr$, the rate is second order-exponentially decayed with partial pressures of component B, $P_B$. For the range of $5{\le}M_B{\le}200$, the rate is second order-exponentially decayed with a function of molecular weight of component B, $M_B$. Like the case of a partial pressure of component B, the effects of a molecular weight arc: reflected through the binary diffusivity coefficients, which are intimately related with suppressing the convection flow inside the growth enclosure, i,e., transition from convection to diffusion-dominant flow mode as the molecular weight of B increases. The convective mode is near at a ground level, i,e., on earth (1 $g_0$), and the convection is switched to the diffusion mode for $0.1\;g_0{\le}g{\le}10^{-2}g_0$, whereas the diffusion region ranges from $10^{-2}g_0$ up to $10^{-5}g_0$.