• Title/Summary/Keyword: Transverse ventilation

Search Result 36, Processing Time 0.025 seconds

A Study on the Effective Fire and Smoke Control in Road-Tunnel with Semi-Transverse Ventilation (도로터널 화재시 대배기구 환기방식에서의 배연 연구)

  • Jeon, Yong-Han;Han, Sang-Cheol;Yoo, Oh-Ji;Kim, Nam-Jin;Seo, Tae-Boem;Kim, Jong-Yoon
    • Proceedings of the SAREK Conference
    • /
    • 2009.06a
    • /
    • pp.1244-1250
    • /
    • 2009
  • In this study it is intended to review the moving characteristics of smoke by performing visualization for the calculation of the optimal smoke exhaust air volume in case a fire occurs in tunnels where transverse ventilation is applied, and to obtain basic data necessary for the design of smoke exhaust systems by deriving optimal smoke exhaust operational conditions under various conditions. As a result of this study, when the critical velocity in the tunnel is 1.75 m/s and 2.5 m/s, the optimal smoke exhaust air volume has to be more than $173\;m^3/s$, $236\;m^3/s$ for the distance of the smoke moving which can limit the distance to 250m. In addition, in case of uniform exhaust the generated smoke is effectively taken away if the two exhaust holes near the fire region are opened at the same time.

  • PDF

Effect of Aspect Ratio and Location of Outlets on Ventilation Performance in a Dry Room (Dry Room에서 종횡비와 배기구 위치가 환기성능에 미치는 영향)

  • 이관수;임광옥;최석호
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.14 no.4
    • /
    • pp.324-331
    • /
    • 2002
  • The characteristics of moisture ventilation in a dry room are studied numerically The behaviors of moisture ventilation are analyzed by varying the aspect ratio of the horizontal plane and for various positions of the outlets in the room. Three different ventilation efficiencies have been used to examine the effect of the longitudinal arrangement of outlets and transverse arrangement of outlets for each aspect ratio on ventilation inside the room. It is shown that the ventilation efficiency in the dry room can be improved by arranging the outlets transversely in the cases that the aspect ratio is less than three and longitudinally in the cases that it is greater than four.

Numerical Study on the Supply and Exhaust Port Size and Fire Management Method in the Semi-transverse Ventilation System for Road Tunnel (도로터널 반횡류환기시스템에서 급배기 포트개도 및 화재시 운영방안에 관한 수치해석적 연구)

  • Ryu, Ji-Oh;Kim, Jin-Su;Rie, Dong-Ho
    • Fire Science and Engineering
    • /
    • v.30 no.2
    • /
    • pp.68-74
    • /
    • 2016
  • In semi-transverse ventilation system applied for road tunnel, adjustment of the port opening ratio is an essential part for uniform airflow rate per unit length over the entire tunnel. However, it has not been considered decently throughout the design process and operating of the tunnel. Therefore, in this study, we developed a program for the calculation of the opening size ratio of supply or exhaust port in transverse ventilation system and carried out the research to present a management plan for the port. In supply duct system, the opening size of the port had a tendency to increase and then decrease later when it gradually becomes closer toward the bulkhead at the beginning of the duct the minimum opening degree is to appeared as 56%. In the exhaust system, port size is the smallest at the beginning of duct as 15%, has shown a tendency to increase towards the bulk head. As results of estimating the air flow rate for 300 m intervals, the exhaust flow rate in the center of tunnel appeared to be extremely low as 8.1% and 12.5% when port size is constant and is adjusted supply type. Thus, even if the normal ventilation efficiency is declines, yet it is highly recommend adjusting the port size in order to obtain a uniform flow rate at fire accidents.

Numerical Simulation of Ventilation Performance in a Dry Room (극저습 공조실의 환기성능에 대한 수치적 모사)

  • Choe, Seok-Ho;Lee, Gwan-Su
    • Transactions of the Korean Society of Mechanical Engineers B
    • /
    • v.26 no.4
    • /
    • pp.594-603
    • /
    • 2002
  • The characteristics of moisture ventilation in a dry room were studied numerically The effect of three important parameters: position of outlets, aspect ratio($\beta$) of horizontal plane and air exchange rate(N), was analyzed by using the scales of ventilation efficiency. The ventilation performance was evaluated by varying the aspect ratio and air exchange rate in the four types of outlet position. It was shown that the ventilation performance was improved by decreasing the aspect ratio in the longitudinal arrangement of outlet. The highest ventilation performance was determined when $\beta$ was 4 in the transverse arrangement of outlet. Regardless of the aspect ratio, the ceiling arrangement of outlet played more dominant effect on the ventilation efficiency than the floor arrangement. In every type and aspect ratio, the increase of air exchange rate to improve ventilation performance was appropriate up to N=60 /h.

Study of the Effective Fire and Smoke Control in Deep Underground Tunnel with Transverse Ventilation (대심도 터널 화재 시 균일배기 환기방식에서의 최적배연 연구)

  • Kim, Jong-Yoon;Lim, Kyung-Bum;Jeon, Yong-Han
    • Journal of the Korea Academia-Industrial cooperation Society
    • /
    • v.16 no.1
    • /
    • pp.21-26
    • /
    • 2015
  • This study represents the effective fire and smoke control in the case of fire in deep underground tunnels, even if the exhaust system can be calculated, the optimal smoke capacity can be determined by establishing technical standards for the transverse ventilation system focusing on the design as a basis for deriving the parameters for utilization. Numerical analyses were performed using the FDS program as a function of the unsteady flow in a deep underground tunnel fire. The analysis results were calculated within 250 m smoke using an inside wind velocity of 0m/s when the capacity of smoke was exhausted, $80m^3/s$, whereas in case of an internal wind velocity of 3m/s, the capacity of smoke exhaust was $197.1m^3/s$, showing an approximately 2.5 fold increase.

A Study on the Effective Fire and Smoke Control in Road-Tunnel with Semi-Transverse Ventilation (도로터널 화재시 반횡류식 균일배기 환기방식에서의 최적배연 연구)

  • Jeon, Yong-Han;Yoo, Ji-Oh;Kim, Nam-Jin;Seo, Tae-Boem;Kim, Jong-Yoon
    • Korean Journal of Air-Conditioning and Refrigeration Engineering
    • /
    • v.21 no.3
    • /
    • pp.186-192
    • /
    • 2009
  • In this study it is intended to review the moving characteristics of smoke by performing visualization for calculation of the optimal smoke exhaust air volume in case a fire occurs in tunnels where transverse ventilation is applied, and to obtain basic data necessary for design of the smoke exhaust systems by deriving optimal smoke exhaust operational conditions under various conditions. As a result of this study, if it was assumed 0 critical velocity in the tunnel, the smoke exhaust air volume was limited within 250 meter in the road-tunnel disaster prevention indicator and the exhaust efficiency was from 55.1% to 95.8% in the result of this study. In case of oversized exhaust ports, the generated smoke is more than the case of uniform exhaust. When the critical velocity in the tunnel is 1.75 m/s and 2.5 m/s, the optimal smoke exhaust air volume has to be more than $173\;m^3/s$, $236\;m^3/s$ for the distance of the moving smoke which can limit the distance to 250 m.

The study of ventilation system during fire in road tunnel with bi-directional or congested unidirectional traffic (교통정체가 심한 도로터널에 대한 화재시 제연방식에 관한 연구)

  • Yoo, Ji-Oh;Shin, Hyun-Jun;Nam, Chang-Ho
    • Proceedings of the SAREK Conference
    • /
    • 2008.06a
    • /
    • pp.474-479
    • /
    • 2008
  • The purpose of this paper is to estimate the fire safety in tunnels with bi-directional and/or congested unidirectional traffic where there may be people on both sides of the fire. Therefore, the spread and movement of smoke are simulated by Fire Dynamic Simulator code under different ventilation systems, longitudinal, semi-transverse, large port exhaust system. And as quantitative risk index, FED (Fractional Effective Dose) for each ventilation system are calculated and compared by existed code developed previous research.

  • PDF

Case Study of the Longest Roadway Tunnel in Korea, Baehuryeong Tunnel (국내 최장대 양방향 도로터널 설계사례-배후령터널)

  • Lee Seon-Bok;Je Hae-Chan
    • Tunnel and Underground Space
    • /
    • v.15 no.6 s.59
    • /
    • pp.432-440
    • /
    • 2005
  • Baehuryeong tunnel connects Chuncheon with Hwacheon in Kangwon, Korea, This tunnel is a single tunnel with 5,057 m long and two bidirectional lanes which will be extended into low lanes in the future. The estimated construction period of Baehuryeong tunnel is approximately 55 months. This tunnel will become the longest bidirectional roadway tunnel in Korea. Compared to a twin tunnel, a bidirectional single tunnel has two major disadvantages with regard to the ventilation system and ease of escape during fire. For these reasons, a service tunnel and the transverse ventilation system are planned first time in Korea. In case of fire, the tunnel ventilation design aims to maintain a smoke free layer for passenger evacuation. The geology of Baehuryeong tunnel site is mainly composed of gneiss and granite. Baehuryeong fault is a mainly large scale fault which stands vertical and parallels with tunnel direction. The influenced zone of this fault is within 70 m. Baehuryeong tunnel was designed that it was separated with the distance of more than 100 m from Baehuryeong fault for its safety.

Scaled model tests for improvement and applicability of the transverse smoke control system on tunnels (횡류식 제·배연 시스템의 개선 및 적용성 분석을 위한 모형실험 연구)

  • Kim, Hyo-Gyu;Baek, Doo-San;Kim, Jae-Hyun;Lee, Seong-Won;Yoo, Ji-Oh
    • Journal of Korean Tunnelling and Underground Space Association
    • /
    • v.22 no.5
    • /
    • pp.563-574
    • /
    • 2020
  • Currently, road tunnels and railroad tunnels are building smoke control systems to emit toxic gases and smoke from fires. Among the various smoke control systems, the transverse smoke control system has the disadvantage that air supply or exhaust is performed on only half of the cross-section, rather than air supply or exhaust on the entire cross-section of the tunnel as air is supplied or exhausted by partitioning the wind path. Therefore, this study analyzed the effect of exhaustion through numerical analysis and scaled model tests on the zoning smoke control system, which improved the limitations of the transverse smoke control system. As a result of the scaled model test, the transverse ventilation system exhibited a 25.6% smoke control rate based on the state where no smoke was controled, and zoning smoke control system showed a smoke control rate of 40.8%. In addition, as a result of numerical analysis, it was found that transverse ventilation system did not control fire smoke spreading from the tunnel and continued to spread. On the other hand, zoning smoke control system was found to be smoke controled within a certain section due to the air curtain effect and the flue gas effect.