Behaviors of Impulse Ground Impedances Associated with the Current Injection Point in a Ground Rod (봉상 접지전극에시 전류유입위치에 따른 임펄스 접지임피던스의 특성)

  • Lee, Bok-Hee;Jeong, Dong-Cheol;Lee, Su-Bong
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.19 no.1
    • /
    • pp.94-100
    • /
    • 2005
  • This paper presents the behaviors of transient and effective impulse impedances of a long ground rod associated with the current injection points. The laboratory test for the time domain performance of actual-sized model ground rod subjected to a lightning stroke current has been carried out The transient ground impedances of long ground rods under impulse currents were higher than the ground resistance. Both of the ground resistance and the effective impulse ground impedance decrease with increasing the length of the ground rods. Also, the effective impulse ground impedances are significantly increased in fast rise time ranges. The reduction of the ground resistance is decisive to improve the impulse impedance characteristics of grounding systems. When the test current is injected at the bottom of ground rod, the oscillating pulses with high frequency are included on the wave front of ground rod potential and the effective impulse impedances are higher than any other cases.

Grounding Characteristics Analysis of the Stainless-steel Plate Grounding Electrode for Distribution Poles (배전전주용 스테인리스강판 접지전극의 접지 특성분석)

  • Kim, Kyung-Chul;Lee, Kyu-Jin;Kim, Min-Sung;Jung, Ji-Won
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.24 no.8
    • /
    • pp.94-100
    • /
    • 2010
  • Grounding system insures a reference potential point for electric devices and also provides a low impedance path for fault currents or transient currents in the earth. The ground impedance as function of frequency is necessary for determining its performance since fault currents could contain a wide range of frequencies. In this paper, the grounding resistance, grounding impedance and transient grounding impedance are measured by using 3-point fall-of-potential method in order to analyse grounding characteristics of the stainless-steel plate grounding electrode. An equivalent transfer function model of the grounding impedance and transient grounding impedance are identified from the measured values by using ARMA method and evaluated by comparing conventional grounding impedances.

The Ground Impedance Modeling using pattern Search Method for Neutral Hormonic Analysis (Pattern Search 법을 이용한 중성선 고조파 해석용 접지 임피던스 모델링)

  • 백승현;김경철;최종기;이일무;백남웅
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.18 no.4
    • /
    • pp.181-187
    • /
    • 2004
  • With the proliferation of nonlinear loads, high neutral harmonic currents in three-phase four-wire distribution system have been observed. It has been known that the ground impedance has an effect on the neutral currents of a system which operates with harmonics present. On-site measurements of harmonic currents and voltages according to the fall-of-potential method under case study system were made and the ground impedance modeling using the pattern search method for the harmonic analysis was developed The ground impedance model obtained by the proposed method was compared with the frequency characteristics by field tests and has shown appropriate results, and would be applicable to evaluate the harmonic and transient response characteristics of the ground system.

Transient Grounding Impedance Characteristic Analysis of a Copper Rod-type Grounding Electrode Used for Electric Distribution Systems Using MATLAB Program (MATLAB 프로그램을 이용한 배전계통에 사용되는 동봉 접지전극의 과도 접지임피던스 특성 분석)

  • Kim, Kyung-Chul;Oh, Kyung-Hoon;Lee, Kyu-Jin;Shim, Keun-Bo;Choi, Jong-Kee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.9
    • /
    • pp.40-46
    • /
    • 2009
  • Although a ground resistance is a good index of grounding performance for grounding electrodes, it does not reflect the grounding performance during transient state. A copper rod electrode is the most commonly used grounding electrode in electric distribution systems. In this paper, the grounding impedance of copper rods has been measured in frequency raging from 60[Hz] up to 100[kHz] and an equivalent model of the grounding impedance is identified from the measured values. The grounding impedance under study when a typical lightning surge is injected into the grounding system was simulated numerically and graphically through the use of the MATLAB software program.

Analysis of the Grounding Impedance of a Ground Rod Considering the Frequency-Dependent Resistivity and Relative Permittivity of Soil (토양의 저항률 및 비유전율의 주파수의존성을 고려한 접지봉의 접지임피던스의 해석)

  • Ahn, Chang-Hwan;Choi, Jong-Hyuk;Lee, Bok-Hee
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.26 no.1
    • /
    • pp.54-60
    • /
    • 2012
  • When the transient current with high frequency components such as lightning surges are injected the grounding electrodes, the performance of grounding electrodes should be evaluated as grounding impedance. It is restricted to analyze the grounding impedance by measurement approach since the grounding impedance is very different with the shape and size of grounding electrodes, resistivity and relative permittivity of soil and the frequency component of the injected current. So a variety of simulation approaches have been developed. Typically, the soil resistivity measured with low frequency and relative permittivity between 1 and 80 are used for simulation of the grounding impedance. However, the resistivity and relative permittivity of soil are changed with frequency of injected current. In this paper, the frequency-dependent resistivity and relative permittivity of soil are measured and these parameters are reflected in the simulation of the grounding impedance of a ground rod. The simulated results are compared with the measured results. As a result, the simulated results with frequency-dependent soil parameters show capacitive aspect like measured results in the frequency of lower than 100[kHz] and they are more consistent with the measured results in wide frequency range.

Design and Fabrication of a Surge Impedance Meter (서지임피던스 측정기의 설계 및 제작)

  • Kil, Gyung-Suk;Rhyu, Keel-Soo;Kim, Il-Kwon;Moon, Byung-Doo;Kim, Hwang-Kuk;Park, Chan-Yong
    • Journal of the Korean Society for Railway
    • /
    • v.10 no.6
    • /
    • pp.645-649
    • /
    • 2007
  • Ground systems flow fault currents into the ground, and suppress Ground Potential Rise (GPR) by the current. In this paper, we designed and fabricated a surge impedance meter to analyze the ground impedance in wide frequency ranges. The meter consists of a surge generator, a high speed sample/hold (S/H) circuit and an associated electronics. The surge generator produces surge voltage up to 5kV in ranges of $50\sim500ns$. Field tests were carried out to evaluate the surge impedance meter at a driven-rod ground system. The results showed that surge impedance of ground systems should be measured by various fast surge waveforms, since the impedance increases as the rise time of applied voltage increases.

Development and Application of Pre/Post-processor to EMTP for Sequence Impedance Analysis of Underground Transmission Cables (지중 송전선로 대칭분 임피던스 해석을 위한 EMTP 전후처리기 개발과 활용)

  • Choi, Jong-Kee;Jang, Byung-Tae;An, Yong-Ho;Choi, Sang-Kyu;Lee, Myoung-Hee
    • The Transactions of The Korean Institute of Electrical Engineers
    • /
    • v.63 no.10
    • /
    • pp.1364-1370
    • /
    • 2014
  • Power system fault analysis has been based on symmetrical component method, which describes power system elements by positive, negative and zero sequence impedance. Obtaining accurate line impedances as possible are very important for estimating fault current magnitude and setting distance relay accurately. Especially, accurate calculation of zero sequence impedance is important because most of transmission line faults are line-to-ground faults, not balanced three-phase fault. Since KEPCO has started measuring of transmission line impedance at 2005, it has been revealed that the measured and calculated line impedances are well agreed within reasonable accuracy. In case of underground transmission lines, however, large discrepancies in zero sequence impedance were observed occasionally. Since zero sequence impedance is an important input data for distance relay to locate faulted point correctly, it is urgently required to analyze, detect and consider countermeasures to the source of these discrepancies. In this paper, development of pre/post processor to ATP (Alternative Transient Program) version of EMTP (Electro-Magnetic Transient Program) for sequence impedance calculation was described. With the developed processor ATP-cable, effects of ground resistance and ECC (Earth Continuity Conductor) on sequence impedance were analyzed.

Transient Grounding Impedance Characteristics of a Copper Rod-type Grounding Electrode used for Electric Distribution Systems Using EDSA Program (EDSA 프로그램을 이용한 배전계통에 사용되는 동봉 접지전극의 과도 접지임피던스 특성)

  • Kim, Kyung-Chul;Oh, Kyung-Hoon;Kim, Min-Sung;Choi, Jong-Kee;Kim, Dong-Myung
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.23 no.8
    • /
    • pp.26-32
    • /
    • 2009
  • Grounding insures a reference potential point for electric devices and also provides a law resistance path for fault or transient currents in the earth. The ground impedance as a function of frequency is necessary for determining its performance since fault or transient currents could contain a wide range of frequencies. A copper rod electrode is the most commonly used grounding electrode in electric distribution systems. In this paper, the grounding impedance of copper rods has been measured in frequency raging from 60[Hz] up to 100 [kHz] and an equivalent model of the grounding impedance is identified from the measured values. The grounding impedance under study when a typical lightning surge is injected into the grounding system was simulated numerically and graphically through the use of the EDSA software program.

Effective impulse impedances of a deep-driven ground rod combined with other grounding electrodes (다른 형상의 접지전극에 접속된 심매설 접지전극의 실효임펄스임피던스)

  • Lee, Bok-Hee;Chang, Keun-Chul;Lee, Su-Bong
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.565-569
    • /
    • 2004
  • This paper deals with the characteristics of potential rise and effective impulse impedance of deep-driven ground rods that are used in high resistivity soil or in confined places such as downtown. Also the effects of the impulse and fault currents on the deep-driven ground rods combined with different type grounding electrodes like as mesh grids and counterpoises are described. The $8/20{\mu}s$ impulse current and other wave currents with different rise times are injected into the test ground rod and the effective impedances are examined. The most effective way to obtain the fine transient impedance behaviors of deep-driven ground rods is to reduce the inductive component of grounding electrode systems combined with other ground electrodes.

  • PDF

The Effects of Soil Model in the Grounding System Design (침상 접지전극봉의 접지효과 분석)

  • Lee, Hyung-Soo;Shim, Keon-Bo;Ahn, Chung-Hoon;Kim, Kyu-Sam
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2004.05a
    • /
    • pp.451-455
    • /
    • 2004
  • Although DC ground resistance is a good index of performance for a grounding system, it does not reflect the grounding performance during the transient states. Besides, impulse ground impedance, which is defined by a ratio of the peak value of transient ground potential rise to the peak value of impulse current, cannot be an absolute performance index due to its dependence on impulse current shape. In this paper, a grounding performance of needle-typed ground rod has been compared with simple ground rod.