• Title/Summary/Keyword: Transformer insulating oil

Search Result 113, Processing Time 0.026 seconds

A Study on the Deterioration Diagnosis Device of Pole Transformer using FFT (FFT를 이용한 주상 변압기의 열화 진단 장치에 관한 연구)

  • 윤용한;김영춘;김재철
    • Journal of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.14 no.3
    • /
    • pp.97-106
    • /
    • 2000
  • This paper proposes on-line based a deterioration diagnosis device for diagnosis pole transformers using tan$\delta$ and FFT(fast Fourier transform). We measured tan$\delta$ and temperature to diagnose pole transformer insulating oil, diagnostic results are processed by FFT. For measuring convenience, we use R/F(radio frequency) wireless data communication module operating by secondary voltage of pole transformer. We have voltage variation test and oil temperature variation test to prove usability of proposed diagnosis device. The result of this paper shows that the proposed device can be used as deterioration diagnosis device of pole transformers.

  • PDF

Analysis of ultrasonic signals through media in transformer (변압기의 전달 매질에 따른 초음파 신호의 특성 분석)

  • Chin, Sang-Bum;Park, Hyun-Soo;Shin, Dong-Seok;Kwak, Hee-Ro;Kweon, Dong-Jin
    • Proceedings of the KIEE Conference
    • /
    • 1999.07e
    • /
    • pp.2057-2059
    • /
    • 1999
  • This paper describes the phenomena of the refraction and reflection when the ultrasonic signals generated by PD(Partial Discharge) in a transformer propagate through the boundary between insulating oil and the tank of the transformer. In this paper, considering the characteristic of the ultrasonic signal and the velocity of the propagation in medium, propagation time from PD source to sensor for incidence angle was calculated. As a result, it was found that the shortest time at specific angle exists. Taking into account the velocity of the propagation in medium, the shortest time with a computer was simulated. It was shown that the simulation was same as experimental result at a real PD source in the transformer.

  • PDF

The Characteristics of RVM by Accelerated Aging in Insulating Materials of the Transformer (경년 열화에 따른 변압기 절연물의 회복전압 특성)

  • Kang, Seok-Young;Han, Sang-Ok;Kim, Jae-Hoon;Kim, Ju-Han;Lee, Sei-Hyun
    • Proceedings of the KIEE Conference
    • /
    • 2005.07e
    • /
    • pp.73-75
    • /
    • 2005
  • In present measurement of moisture contents is used as one of method for estimating degradation of transformer. Most of people use Karl-Fischer titration method for detection moisture contents but this measurement is inconvenient method because we must analyze transformer oil-paper after dismounting transformer and sampling in field. Therefore we don't directly investigate them in field. In this paper we will introduce Recovery Voltage Method(RVM) that is new method for estimating measurement in field though dismounting facility. For measure of moisture contents using RVM in accordance with accelerated thermal aging we have made experimental test cell and aged at a temperature up to 140$^{\circ}C$ for 300 hours. And we have been measured at intervals of 100 hours using RVM 5462 made in fetter company.

  • PDF

Effect of Impurities on Streaming Electrification in Transformer Oil (변압기 절연유의 유동대전현상에 미치는 불순물의 영향)

  • Cho, Moon-Ho;Kweon, Dong-Jin;Kwak, Hee-Ro;Kim, Du-Suck
    • Proceedings of the KIEE Conference
    • /
    • 1992.07b
    • /
    • pp.931-933
    • /
    • 1992
  • The static charges generated at the interface between the insulating oil and the solid materials, can be affected by impurities such as moisture. This paper investigated the charging tendency of clean oil and the oil with moisture in stainless steel pipe. The experimental results show that static electrification of the oil with moisture is smaller than that of the clean oil, and the oil is positively charged.

  • PDF

전기집진기술의 현황과 장래전망(I)

  • 고명삼;이달우
    • The Proceedings of the Korean Institute of Illuminating and Electrical Installation Engineers
    • /
    • v.11 no.1
    • /
    • pp.24-33
    • /
    • 1997
  • In this paper, aging of insulating oil in pole transformer has been studied by performing accelerated thermal aging test. Dissolved gases were extracted by air bubbling method. Concentration of dissolved gases were modified by extraction ratio of each gases in insulting oil. Aging of insulting materials were proceeded by thermal degradation and oxidation reaction. Both of the reactions followed zeroth order kinetics. Formation rate equations for hydrocarbons, carbon oxides, and hydrogen were derived. It was conformed by gas analysis and UV-visible spectrophotometric method that iron core and copper coil in pole transformer act as catalyst during the aging process.

  • PDF

Life Loss of Pole Mounted Transformers by Thermal Aging (열 열화에 의한 주상변압기의 수명 손실)

  • Joung, Jong-Man;Lee, Byeong-Seong;Song, Il-Kewon
    • Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference
    • /
    • 2005.05a
    • /
    • pp.209-213
    • /
    • 2005
  • To enhance the reliability of distribution transformers in service and to reduce the cost of maintaining and replaceing these, the condition and life of those insulating system should be evaluated accurately and the time to replace should be determined economically. Since the transformer failures related to insulation failure indicates that the primary cause is normally mechanical failure of integrity due to loss of mechanical strength as a result of degradation, the tensile strength characteristics of paper during ageing under accelerated conditions in insulating oil and research trends for assessing the life of insulating paper were investigated.

  • PDF

Analysis on the Diagnosis Characteristics of Electrical Insulating Oil for Power Transformer with 3-terminal Capacitive Sensor (3전극형 전기용량 센서를 이용한 변압기 절연유의 열화감지특성 평가)

  • Kim, Ju-Han;Seo, Pan-Seok;Kim, Pil-Hwan;Kim, Myung-Hwan;Park, Hung-Seok;Han, Sang-Ok
    • Proceedings of the KIEE Conference
    • /
    • 2004.11d
    • /
    • pp.89-92
    • /
    • 2004
  • This paper described the capacitive sensor for the diagnosis of deterioration of electrical insulating oils applying guard-ring type the 3-terminal electrodes. To measure stable capacitance of the sensor and to determine the design factors of the sensor, we utilized computational analysis, FEM software. This capacitive sensor discern the extent of deterioration measuring relative permittivity of electrical insulating oils. The result of measuring numerous sample, mineral oils, as serviced year, we confirmed an increase in relative permittivity of oils. Moreover, we confirmed the superior characteristics of the sensor as a species, aged pattern of oils and operating temperature.

  • PDF

Electric Characteristics on the Insulating Paper with Varnish-Impregnant (바니쉬 함침이 절연지에 미치는 영향)

  • Kim, Pil-Hwan;Kim, Ju-Han;Lee, Won-Yeong;Han, Sang-Ok
    • Proceedings of the KIEE Conference
    • /
    • 2004.05b
    • /
    • pp.180-182
    • /
    • 2004
  • We have investigated characteristics of varnish and oil impregnant. When transformers are manufactured with some moisture and varnish impregnant not entirely dried, those should be caused by factors that deteriorate the electrical or mechanical property after installation. Therefore, in this study we experienced moisture content of the new insulating paper and the varnish impregnant paper in the ratio of time for confirming factors that deteriorate the paper characteristics. Besides, we investigated a property study that was experienced the value of dielectric strength and tensile strength as no serviced insulating samples of transformer.

  • PDF

Insulation Properties and Evaluation of Diglycerol Ester Synthesized by Solid Acid Catalysts (고체산 촉매를 이용해 합성한 diglycerol ester의 전기절연 특성 및 평가)

  • Gwon, Miseong;Baek, Jae Ho;Kim, Myung Hwan;Park, Dae-Won;Lee, Man Sig
    • Applied Chemistry for Engineering
    • /
    • v.25 no.3
    • /
    • pp.254-261
    • /
    • 2014
  • The transformer is a static electrical device that transfers energy by inductive coupling. Then, heat is occurred at coils, inner transformer was filled with insulating oils for cooling and insulation. Although mineral oil as insulating oil has been widely used, it does not meet health and current environmental laws because it is not biodegradable. Therefore, in this study, the diglycerol ester was synthesized with diglycerol and fatty acids (oleic acid and caprylic acid) over various catalysts for insulating oil having biodegradability, high flash points and low pour points. The sulfated zirconia ($SO_4{^{2-}}/ZrO_2$) catalyst prepared at different calcination temperature shows the highest conversion of fatty acids at $600^{\circ}C$ due to crystallinity and high density of acid sites per surface area. When the molar ratio of oleic acid and caprylic acid is 1:3, the diglycerol ester shows superior insulation properties that are the flash point of $306^{\circ}C$ and pour point of $-50^{\circ}C$. The insulation properties of synthesized diglycerol ester shows the pour point of $-50^{\circ}C$ and the flash point of over $300^{\circ}C$. Therefore, diglycerol ester is superior to the vegetable oils in insulation properties.

A Study on the Thermal distribution of the 30kVA Pole Transformer Due to the Rated load (30kVA 주상 변압기의 정격부하에 의한 열분포에 관한 연구)

  • Kim, M.K.;Kim, J.T.;Koo, J.Y.;Song, K.D.;Cho, Y.O.;Ha, B.N.
    • Proceedings of the KIEE Conference
    • /
    • 1991.07a
    • /
    • pp.292-295
    • /
    • 1991
  • The life of the transformers is significantly dependent upon the rate of thermal deterioration in the employed insulating materials. Therefore, the study should be based on hot-spot temperature considerations for the life expectancy and possible overload of transformer. We have measured directly temperature of the winding using thermocouples and these test results are compared with those obtained from computer simulation. In this work, our fundamental investigations are well described for the analysis in the thermal distribution of the oil-immersed transformer with the rating of 30kVA.

  • PDF