• 제목/요약/키워드: Tan delta

검색결과 521건 처리시간 0.022초

Tan Delta 측정을 이용한 유침 절연지의 열화특성 분석 (Analysis of Degradation Characteristics for Oil-Paper Insulation using Tan Delta Measurement)

  • 김정태;김우빈
    • 전기학회논문지
    • /
    • 제65권9호
    • /
    • pp.1518-1523
    • /
    • 2016
  • In this study, in order to understand the degradation characteristics of oil-paper insulation for power transformers and OF cables, tan delta was measured using cable model specimens with long-term accelerated thermal and electrical aging. In addition, to find out the degradation level due to the accelerated aging, tensile strengths of aged papers were measured. As a result, tan ${\delta}$ showed the characteristics of slight decrease at the first stage and then increase with the aging time, which could be analyzed due to the evaporation of remaining moisture and the change of aging rate with time. Also, the trend of tensile strengths with aging temperature and time was appeared to be exponentially decreased and by use of these data equivalent calculated lifetimes and accelerated aging factors were derived for each aging temperatures. After then, tan ${\delta}$ was analyzed with the equivalent operating years. For all different aging temperatures, the aged data were very well fit to the equivalent operating years and it is shown that tan ${\delta}$ was increased with the decrease of tensile strength.

가스량, Tan $\delta$, 수분량, 전산가에 의한 유침 전력 변압기의 열화현상에 관한 연구 (The degradation of insulation oil in power transformers by the evolution of gases, Tan $\delta$, moisture and total acid number)

  • 최종갑;한민구;권태원;윤용범
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1989년도 추계학술대회 논문집 학회본부
    • /
    • pp.159-163
    • /
    • 1989
  • The various degradation phenomena, such as the evolution of gases, tan $\delta$, moisture content and total acid number in power transformer insulation oil, have been measured and analyzed. Mineral oil has been degraded at laboratory by the forced thermal stress of $60^{\circ}C$ and $90^{\circ}C$ respectively. Thermal aging oil has been degraded about 17, 34, 72 days. Also, we extracted insulation oil from working transformers. We measured gases dissolved in samples, tan $\delta$, moisture content, total acid number. Activation energy and resistivity is calculated from them. It is found that gases and tan $\delta$ increases as partial discharge and total acid number increases and that conductivity of the sample increases as activation energy increases.

  • PDF

Mini-model 초전도 케이블의 유전손실 특성 (The Dielectric loss Properties of Mini-model Superconducting Cable)

  • 김영석;곽동순;한철수;김해종;김동욱;김상현
    • 한국전기전자재료학회논문지
    • /
    • 제16권10호
    • /
    • pp.946-951
    • /
    • 2003
  • A high-Tc superconducting cable(HTS cable) is expected as an underground power line supplying the electrical power the densely populated city in future. The electrical insulation is very important for develop HTS cable system because it is operated a high voltage and in cryogenic temperature. We manufactured a mini-model cable and measured a tan$\delta$ of cable using schering bridge. The tan$\delta$ of PPLP was lower than that of Tyvek and Kraft at a given temperature, the tan$\delta$ of PPLP was 1.16${\times}$10-3. According to the increase of electric stress the tan$\delta$ increased because partial discharge occurred inside butt gap of mini-model cable. However, the tan$\delta$ decreased by increase of liquid nitrogen pressure. This reason is thought by decrease of part discharge between butt gap by increase of liquid nitrogen pressure.

대용량 터빈발전기 고정자 권선의 절연상태 평가 (Assessment of Insulation Condition in Large Turbine Generator Stator Windings)

  • 김희동;이영준;박덕현
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2093-2096
    • /
    • 1999
  • This paper describes to access the insulation deterioration condition of the stator windings in three large turbine generators. Nondestructive tests have been carried out on stand-still generators which have been in service for 2 to 30 years. In most cases these tests include ac current increase rate($\Delta$I), delta tan delta( ${\Delta}tan{\delta}$), and maximum partial discharge(Qm). Gen. 2 show that the $tan{\delta}$ is higher than other two generators in the $tan{\delta}$-voltage curve. Partial discharge(PD) patterns were observed internal, corona and treeing discharges in large turbine generators. The PD tests were confirmed the correlation between discharge patterns and the kinds of defects.

  • PDF

XLPE 절연케이블의 열화진단 정확도 향상을 위한 VLF tanδ 판정기준 개선 (An Amendment of the VLF tanδ Criteria to Improve the Diagnostic Accuracy of the XLPE-insulated Power Cables)

  • 이재봉;정연하
    • 전기학회논문지
    • /
    • 제59권9호
    • /
    • pp.1644-1651
    • /
    • 2010
  • VLF $tan{\delta}$ diagnosis technology is introduced in IEEE Std 400 and proposed as evaluation criterion in an effective way of detecting water tree which mainly causes the failure of XLPE insulated cables. In order to inspect the accuracy of the VLF $tan{\delta}$ method for XLPE insulated power cables in Korean distribution system, diagnosis for 41 cables which were being serviced in the fields has been carried out and they were removed for AC breakdown voltage test after. Regarding the 41 cables, it was hard to confirm any relation between the VLF $tan{\delta}$ values and AC breakdown voltages and also water tree in the insulation was not detected. However, the other cables were failed several days after the diagnosis of the 41 cables. Water trees were found and their VLF $tan{\delta}$ values were also much higher than the criterion of IEEE standard. It has been ascertained that we need to change the IEEE criteria in order to improve the accuracy of detecting water trees by additional analyzing of field examples of failure and case studies from overseas countries and therefore amended VLF $tan{\delta}$ test voltage and evaluation criteria have been proposed.

회전기 고정자 권선에서 절연재료의 특성 (Properties of Insulation System in Rotating Machine Stator Windings)

  • 박종정;김희동;김희곤;강도열;한상옥
    • 한국전기전자재료학회:학술대회논문집
    • /
    • 한국전기전자재료학회 1997년도 춘계학술대회 논문집
    • /
    • pp.326-329
    • /
    • 1997
  • The surface of mica/epoxy paper(130${\mu}{\textrm}{m}$) is investigated with SEM(scanning electron microscope). SEM micrographs revealed that thermal aging has a strong influence on aged specimens. The mica/epoxy paper was exposed at 187$^{\circ}C$ in an ordinary electrical oven for 72hour. Stater windings from two generators were measured by tan delta(tan $\delta$)and maximum partial discharge(Qm). The values of tan $\delta$and Qm were fecund to be higher for new generator than old one. The insulation condition of mica/epoxy paper were measured by ac current and tan $\delta$. Test results are observed that the sound specimens are higher than those aged. Model bar coils subjected to various accelerated agings were evaluated by Qm.

  • PDF

플라즈마 중합 MMA의 유전특성 개선에 관한 연구 (A Study on the Improvement of the Dielectric Properties of Plasma Polymerized Methyl Methacrylate)

  • 이덕출;박구범
    • E2M - 전기 전자와 첨단 소재
    • /
    • 제3권2호
    • /
    • pp.115-122
    • /
    • 1990
  • 플라즈마중합 에틸메타아크릴레이트(PPMMA) 박막의 유전특성인 유전정접(tan .delta.)과 정전용량(C)을 관측하고 산화와 열처리 및 플라즈마처리로 인한 PPMMA의 tan .delta.와 C의 변화에 대하여 연구하였다. 측정온도 25.deg.C, 측정주파수 1KHz에서 1MHz의 범위에서 PPMMA 박막은 CO와 -OH같은 산화물의 생성으로 인하여 tan .delta. 와 C는 증가하고 tan .delta.는 측정주파수 내에서 피이크를 형성한다. 이는 PPMMA내에 잔류하는 저분자량 성분과 자유라디칼의 존재와 공기중에서의 산화가 그 원인이라 할 수 있다. 본연구에서는 PPMMA박마그이 열처리 및 플라즈마처리를 하여 저분자량 성분과 라디칼을 제거하고 산화를 방지하여 박막의 유전특성을 개선하였다.

  • PDF

유기화 클레이의 첨가가 실리카 및 카본블랙를 함유한 SBR 복합체의 동적 특성에 미치는 영향 (Effect of organoclay on the dynamic properties of SBR compound reinforced with carbon black and silica)

  • 손민진;김원호
    • Elastomers and Composites
    • /
    • 제41권4호
    • /
    • pp.260-267
    • /
    • 2006
  • 유기화 클레이(organically modified layered silicates)가 보강된 SBR 나노 복합체를 라텍스법(latex method)에 의해서 제조하였다. 유기화 MMT는 dodecylamine으로 유기화한 DA-MMT와 dimethyldodecylamine으로 유기화한 DDA-MMT의 두 가지를 제조하였다. 유기화 클레이의 층간거리와 분산도를 확인하기 위하여 XRD와 TEM촬영을 하였다 Na-MMT, DA-MMT, DDA-MMT의 XRD 회절 패턴을 분석한 결과 Na-MMT는 $2{\theta}=7.2^{\circ}$로써 층간거리가 $12.3{\AA}$, DA-MMT는 $2{\theta}=5.1^{\circ}$로 층간거리가 $17{\AA}$를 나타내었으며, DDA-MMT의 경우, 회절 피크는 $2{\theta}=4.8^{\circ}$로써. 층간거리는 $18.4{\AA}$으로 나타났다. 이는 DDA-MMT와 DA-MMT가 각각 5 phr 첨가된 SBR 나노 복합체의 TEM 결과에서도 확인할 수 있었다. SBR 나노 복합체에 filler system (carbon black/silica/OLS)을 적용 후 시편을 제조하였다. 제조된 시편의 동적 점탄성 평가 (DMTA)는 $-20^{\circ}C{\sim}80^{\circ}C$ 사이에서 이루어졌으며, loss factor (tan $\delta$)의 거동을 확인하였다. 그 결과, 타이어 트래드용 컴파운드를 대상으로 할 경우, 카본블랙과 실리카의 혼용비가 35:25일 때, 빗길 제동특성과 연비특성을 대변하는 $0^{\circ}C$$50{\sim}60^{\circ}C$에서의 tan $\delta$가 가장 우수함을 알 수 있었다. 또한 이 시스템에 실리카의 일정 부분을 DDA-MMT($0{\sim}10phr$)로 대체할 경우, $0^{\circ}C$의 tan $\delta$값은 높아지는 반면, $50{\sim}60^{\circ}C$의 tan $\delta$값은 감소하였다.

고압전동기 고정자 권선의 절연상태 평가 (Assessment of Insulation Condition in High Voltage Motor Stator Windings)

  • 김희동;박의갑;박완조
    • 대한전기학회:학술대회논문집
    • /
    • 대한전기학회 1999년도 하계학술대회 논문집 E
    • /
    • pp.2392-2395
    • /
    • 1999
  • This paper describes to access the insulation deterioration condition of the stator windings in six high voltage motors. Nondestructive tests have been carried out on stand-still motors. These tests include ac current increase rate($\Delta$I), delta tan delta(${\Delta}tan{\delta}$), and maximum partial discharge(PD). AC current and $tan{\delta}$ were measured by Schering bridge. The measurement of PD patterns were conducted using digital partial discharge detector. PD patterns were observed treeing and internal discharges in Motor 1 and 2. The stator windings of two motors were found to be in a poor condition and their were recommended to rewind. The stator. windings of four motors were judged to be in serviceable condition.

  • PDF

루타일이 삽입된 유전체 공진기의 두 공진 모드를 이용한 루타일의 유전손실과 $YBa_2Cu_3O_{7-{\delta}}$ 박막의 마이크로파 표면저항 측정 (Simultaneous Measurements of the Loss Tangent of Rutile ($TiO_2$) and the Microwave Surface Resistance of $YBa_2Cu_3O_{7-{\delta}}$ Films using Two Resonant Modes of Rutile -loaded cavity Resonator)

  • 임준;이재훈;김민정;허정;이상영
    • Progress in Superconductivity
    • /
    • 제4권2호
    • /
    • pp.137-143
    • /
    • 2003
  • In measuring the microwave surface resistance of high-Tc superconductor (HTS) films using the dielectric-loaded cavity resonator method, one of the most important factors that limit the measurement sensitivity is the measurement error in the loss tangent ($tan\delta$) of the dielectric rod placed inside the cavity. We have measured the effective surface resistance ( $R_{S}$ $^{eff}$) of$ YBa_2$$_Cu3$$_{7-{\delta}}$ (YBCO) films and the $tan\delta$ of rutile ($TiO_2$) using the 'two-tone'method suggested by Kobayashi et at. [IEEE, MTT-S Digest, 495, (2001)], which enables simultaneous measurements of both the $R_{S}$ $^{eff}$ fof HTS films and the $tan\delta$ of the rutile with high sensitivity. A rutile-loaded cavity resonator with the $TE_{012}$ and $TE_{021}$ resonant frequencies at 13.67 - 14.01 GHz is used for this purpose. At temperatures where the two modes do not couple with other modes, the $R_{S}$ $^{eff}$ of YBCO films and $tan\delta$ of rutile measured by the two-tone method appear to match well with the corresponding values measured using the reported $tan\delta$ values of sapphire within 10 %. Usefulness of the 'two-tone' method for microwave characterization of HTS films and dielectrics is discussed.d.ielectrics is discussed.ussed.

  • PDF