Properties of Insulation System in Rotating Machine Stator Windings

회전기 고정자 권선에서 절연재료의 특성

  • Published : 1997.04.01

Abstract

The surface of mica/epoxy paper(130${\mu}{\textrm}{m}$) is investigated with SEM(scanning electron microscope). SEM micrographs revealed that thermal aging has a strong influence on aged specimens. The mica/epoxy paper was exposed at 187$^{\circ}C$ in an ordinary electrical oven for 72hour. Stater windings from two generators were measured by tan delta(tan $\delta$)and maximum partial discharge(Qm). The values of tan $\delta$and Qm were fecund to be higher for new generator than old one. The insulation condition of mica/epoxy paper were measured by ac current and tan $\delta$. Test results are observed that the sound specimens are higher than those aged. Model bar coils subjected to various accelerated agings were evaluated by Qm.

Keywords